2-Wire Low-Flow
Duct Smoke Detector
Model
DH100LP
2-Wire Photoelectric Duct Smoke Detector
with Low-Flow
Technology
Product Overview
Air velocity rating from
100 to 4000 feet per minute
(0.5 to 20.32 m/sec.)
Patented telescopic sampling tube
12/24 VDC operation
Built-in reset button
Outside mounting tabs
Easy and quick mounting to round
or rectangular ducts from 1′–12′
(0.3–3.7 meters) wide
The System Sensor Innovair™ DH100LP is a 2-wire photoelectric air duct smoke
detector capable of sensing smoke in air velocities from 100 to 4,000 feet per
minute (0.5 to 20.32 m/sec). This Innovair features Low-Flow technology
enabling duct smoke detection throughout a broad range of airflow environments. Many difficult to solve HVAC applications occur in low airflow duct
applications where reliable smoke detection is critical. Innovair with Low-Flow
technology can detect smoke at air speed velocities of 100 feet per minute or
greater, while continuing the same reliable performance to 4,000 feet per minute.
Photoelectric models available
The Innovair family is designed for simplified installation and easy maintenance.
The modular construction allows for easy cleaning and uncomplicated field
replacement of the UL recognized power and sensor boards.
Easy to clean
WARNING: Duct smoke detectors have specific limitations.
UL recognized field-replaceable
power and sensor boards
Remote annunciator option
DUCT SMOKE DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire detection system.
Transparent cover for convenient
visual inspection
Refer to NFPA 72 and 90A for additional duct smoke detector application
information.
UL 268A listed
Remote test station option
3-year warranty
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor Model DH100LP Series Duct Smoke Detector. The detector housing shall
be UL listed per UL 268A specifically for use in air handling systems. The detector shall operate at air velocities of 100 feet per
minute to 4000 feet per minute (0.5 to 20.32 m/sec.). It shall be capable of local testing via magnetic switch or remote testing
using the RTS451KEY Remote Test Station. The unit shall be reset by local reset button or RTS451KEY. The duct detector housing
shall incorporate an airtight smoke chamber in compliance with UL 268A, Standard for Smoke Detectors for Duct Applications. The
housing shall be capable of mounting to either rectangular or round ducts without adapter brackets. An integral filter system shall
be included to reduce dust and residue effects on detector and housing, thereby reducing maintenance and servicing. Sampling
tubes shall either be plastic or be easily installed after the housing is mounted to the duct by passing through the duct housing.
The enclosure shall meet all applicable NEC and NFPA standards regarding electrical junction boxes. Terminal connections shall
be of the strip and clamp method suitable for 12–18 AWG wiring.
Standard Specifications
Size
143/8″ (37 cm) Length
51/2″ (14 cm) Width
23/4″ (7 cm) Depth
Shipping Weight
31/4 lbs. (1.5 kg.)
Operating Temperature Range
32° to 131° F (0° to 55° C)
Storage Temperature Range
–22° to 158°F (–30° to 70° C)
Operating Humidity Range
10% to 93% relative humidity
Air Duct Velocity
100 to 4000 ft./min.
(0.5 to 20.32 m/sec.)
Electrical Ratings
System Voltage
12/24 VDC
Ripple Voltage
4 Volts peak to peak
Star t-up Capacitance
0.02µF maximum
Standby Ratings
8.5 VDC minimum
35 VDC maximum
120µA maximum
Alarm Ratings
4.2 VDC minimum at 10mA
6.6 VDC maximum at 100mA
Alarm current must be limited to
100mA or less by the control panel.
If used, the RA400Z remote lamp operates within the specified alarm currents.
Reset Voltage:
2.50 VDC minimum
Reset Time:
0.3 Sec. maximum
Star t-up Time
34.0 Sec. maximum
DH100LP Wiring Guide
System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating device circuit):
UL LISTED
COMPATIBLE 2-WIRE
CONTROL PANEL
1ST DETECTOR
IN LOOP DH100LP
LAST DETECTOR
IN LOOP DH100LP
DETECTOR
BOARD
7
6
DETECTOR
BOARD
7
6
EOL RESISTOR
SPECIFIED BY
PANEL MANUFACTURER
(+)
(+) IN
(+) OUT
(+)
4
ALARM
INITIATION
LOOP
(+)
4
RA400Z (OPTIONAL)
REMOTE ALARM LED
(–)
5
(–)
8
(–) IN
(–)
(+) IN
5
2.8 VDC NOM.
IN ALARM
8
(–) IN
(–) OUT
(+) OUT
(+)
(+)
(–)
(–)
RA400Z (OPTIONAL) E
REMOTE ALARM LED O
L
R
2.8 VDC NOM.
IN ALARM
(–) OUT
STYLE D OPTIONAL WIRING
H0263-00
2-Wire Wiring to RTS 451 KEY
Wiring diagram for the DH100LP to RTS451/RTS451KEY:
Note:
Terminal 6 of the RTS451KEY is not used when wired
to a 2-wire detector. The RTS451 does not have a
terminal 6.
DH100LP
RTS451/RTS451KEY
Test +
1
5
Test / Reset –
2
4
Reset +
3
3
RA +
4
1
RA –
5
2
V Out +
6
6 No Connection
Test
Alarm
LED
Reset
H0264-00
Ordering Information
Part Number
Description
DH100LP 2-wire photoelectric duct smoke detector
with low-flow technology
A5180
Replacement 2-wire photoelectric detector board
A5061
Replacement 2-wire power board
Accessories
ST-1.5
Metal sampling tube duct widths 1′–2′ (0.3–0.6 m)
APA451
ST-3
Metal sampling tube duct widths 2′–4′ (0.6–1.2 m)
MOD400R
Remote annunciator with piezo alarm
Sensitivity test module
ST-5
Metal sampling tube duct widths 4′–8′ (1.2–2.4 m)
F36-09-11
Replacement air filters (two per package)
ST-10
Metal sampling tube duct widths 8′–12′ (2.4–3.7 m)
M02-04-00
Test magnet
T80-71-00
Replacement telescoping sampling tube
P48-21-00
End cap for metal sampling tubes
P48-55-00
Replacement end cap for T80-71-00
S08-39-01
Photo replacement screen
RTS451KEY
Remote test station with key lock
PA400W Mini-Aler t sounder
RTS451
Remote test station
PS24LOW Mini-Aler t add-on strobe
Remote annunciator alarm LED
PS12/24SLENSW
Wall-mount “SMOKE” lens
RA400Z Accessories
System Sensor provides system flexibility with a variety of accessories, including two remote test stations, and several different
means of visible and audible system annunciation. As with our duct detectors, all duct smoke detector accessories are UL listed.
ALARM
ALARM
RESET
ON
TEST
RESET
RTS451KEY
Remote Test Station
with Key (UL S2522)
RTS451
Remote Test Station
(UL S2522)
ALARM
RA400Z
Remote Annunciator
(UL S2522)
S
M
O
K
E
POWER
PA400W
Mini-Aler t Sounder (UL S3593)
shown with PS24LOW add-on strobe
(PS12/24SLENSW smoke lens option
available)
Device cannot be directly wired to 2-wire
Innovair; must be operated independently
by the panel.
APA451
Piezo Annunciator (UL S4011)
Device cannot be directly
wired to 2-wire Innovair; must
be operated independently by
the panel.
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495 www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767 Fx: 905.812.0771
System Sensor in China
Ph: 86.29.8832.0119 Fx: 86.29.8832.5110
System Sensor – Far East
Ph: 85.22.191.9003 Fx: 85.22.736.6580
System Sensor – India
Ph: 91.124.637.1770 x.2700
Fx: 91.124.637.3118
System Sensor Europe
Ph: 44.1403.891920 Fx: 44.1403.891921
System Sensor in Singapore
Ph: 65.6273.2230 Fx: 65.6273.2610
System Sensor – Australia
Ph: 613.54.281.142 Fx: 613.54.281.172
System Sensor – Russia
Ph: 70.95.937.7982
Fx: 70.95.937.7983
­© 2004 System Sensor. The company reserves the right to change product specifications without notice.
A05-1043-002•1/04•#981