SYSTEMSENSOR A5052-00

2-Wire Low-Profile
Duct Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 (736-7672), Fax 630-377-6495
http://www.systemsensor.com
Models Available
DH100I 2-wire Ionization Detector
DH100P 2-wire Photoelectronic Detector
Features
Outside mounting tabs
Telescoping sampling tube*
Built-in reset button
Easy to clean
12/24 VDC operation
Ion or photo models available
Remote test station option
Air velocity rating from 500 to 4000 FPM
Remote annunciator option
Easy and quick mounting to round or rectangular ducts
from 1′–12′ wide
• Textured cover for convenient visual inspection
• UL 268A listed
• 3-year warranty
maintenance, or a change in application without removing
the duct housing. The DH100 samples air currents passing
through a duct and gives dependable performance for
management of fans, blowers, and air conditioning
systems, preventing the spread of toxic smoke and fire
gases through the protected area.
System Sensor DH100 2-wire duct smoke detector is
available as either an ionization or photoelectric model.
This new design allows for simplified cleaning and
Refer to NFPA 72 and 90A for additional duct detector
application information.
•
•
•
•
•
•
•
•
•
•
WARNING: Duct smoke detectors have specific limitations.
DUCT DETECTORS ARE:
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire
detection system.
Specifications
Length:
Width:
Depth:
Shipping Weight:
Operating
Temperature Range:
143/8 inches (37 cm.)
51/2 inches (14 cm.)
23/4 inches (7 cm.)
3.75 lbs. (1.7 kg.)
Operating
Humidity Range:
Air Duct Velocity:
10% to 93% relative humidity
500 to 4000 ft./min.
23° to 131° F (–5° to 55° C)
*Patent pending
© System Sensor 1/98
This document is not intended to be used for installation purposes.
A05-976-00
Architectural/Engineering Specifications
The air duct smoke detector shall be a System Sensor
Model DH100 Series Duct Smoke Detector. The detector
housing shall be UL listed per UL 268A specifically for use
in air handling systems. The detector shall operate at air
velocities of 500 feet per minute to 4000 feet per minute. It
shall be capable of local testing via magnetic switch or
remote testing using the RTS451KEY Remote Test Station.
The unit shall be reset by local reset button or RTS451KEY.
The duct detector housing shall incorporate an airtight
smoke chamber in compliance with UL 268A, Standard for
Smoke Detectors for Duct Applications. The housing shall
be capable of mounting to either rectangular or round
ducts without adapter brackets. An integral filter system
shall be included to reduce dust and residue effects on
detector and housing, thereby reducing maintenance and
servicing. Sampling tubes shall either be telescoping or be
easily installed after the housing is mounted to the duct by
passing through the duct housing. The enlosure shall meet
all applicable NEC and NFPA standards regarding electrical
junction boxes. Terminal connections shall be of the strip
and clamp method suitable for 12-18 AWG wiring.
Electrical Ratings – DH100 (Includes Detector)
System Voltage:
Ripple Voltage:
Start-up Capacitance:
Standby Ratings:
Alarm Ratings:
Reset Voltage:
Reset Time:
Start-up Time:
Page 2
12/24 VDC
4 Volts peak to peak
0.02 µF maximum
8.5 VDC minimum
35 VDC maximum
120 µA maximum
4.2 VDC minimum at 10mA
6.6 VDC maximum at 100mA
Alarm current must be limited to 100mA or less by the control panel.
If used, the RA400Z remote lamp operates within the specified alarm currents.
2.50 VDC minimum
0.3 Sec. maximum
34.0 Sec. maximum
A05-976-00
DH100 Wiring Guide
UL LISTED
COMPATIBLE 2-WIRE
CONTROL PANEL
LAST DETECTOR
IN LOOP DH100
1ST DETECTOR
IN LOOP DH100
EOL RESISTOR
SPECIFIED BY
PANEL MANUFACTURER
SUPERVISORY
SWITCH
7
6
SUPERVISORY
SWITCH
7
6
(+)
(+) IN
4
ALARM
INITIATION
LOOP
(–)
5
8
(–) IN
(+) IN
(+) OUT
(+)
(+)
(+) OUT
(+)
4
(+)
RA400Z (OPTIONAL)
REMOTE ALARM LED
(–)
(–)
(–)
5
2.8 VDC NOM.
IN ALARM
8
(–) IN
(–) OUT
(–)
RA400Z (OPTIONAL) E
REMOTE ALARM LED O
L
R
2.8 VDC NOM.
IN ALARM
(–) OUT
STYLE D OPTIONAL WIRING
System wiring diagram for 2-wire duct detectors (detectors powered from initiating circuit)
V In +
7
V In / V Out –
8
DH100
RTS451 KEY
Test +
1
5
Test / Reset –
2
4
Reset +
3
3
RA +
4
1
RA –
5
2
V Out +
6
6 No Connection
V In +
7
Panel
+
V In / V Out –
8
–
Test
Alarm
LED
Reset
Wiring diagram for RTS451/RTS451KEY Remote Test Station to 2-wire duct detectors
Page 3
A05-976-00
Ordering Information
Part No.
DH100I
DH100P
A5052-00
A5069-00
A5061-00
Accessories
ST-1.5
ST-3
ST-5
ST-10
T80-71-00
P48-55-00
RTS451KEY
RTS451
RA400Z
APA451
MOD400R
F36-09-00
M02-04-00
P48-21-00
S08-39-01
PA400B
PS24LOB
PS12/24LENSC
PS12/24LENSW
Description
2-wire ionization duct detector
2-wire photoelectronic duct detector
Replacement ionization sensor board
Replacement photoelectronic sensor board
2-wire power board
Metal sampling tube duct widths 1′–2′
Metal sampling tube duct widths 2′–4′
Metal sampling tube duct widths 4′–8′
Metal sampling tube duct widths 8′–12′
Telescoping sampling tube
End cap for T80-71-00
Remote test station with key lock
Remote test station
Remote annunciator alarm LED
Remote annunciator with piezo alarm
Sensitivity test module
Replacement air filters (two per package)
Test magnet
End cap for metal sampling tubes
Photo replacement screen
Mini-Alert sounder
Mini-Alert add-on strobe
Ceiling-mount “SMOKE” lens
Wall-mount “SMOKE” lens
Accessories
annunciation. As with our duct detectors, all duct detector
accessories are UL listed.
System Sensor provides system flexibility with a variety of
accessories, including two remote test stations, and several
different means of visible and audible system
F
I
R
E
ALARM
ALARM
POWER
RESET
APA451
Piezo
Annunciator
(UL S4011)
ON
TEST
RTS451KEY
Remote Test
Station with Key
(UL S2522)
ALARM
RESET
PA400 with
PS24LOW Add-on Strobe
(PS12/24LENSW
smoke lens option available)
(UL S3593)
RTS451
Remote Test
Station
(UL S2522)
RA400Z
Remote
Annunciator
(UL S2522)
System Sensor Worldwide Manufacturing & Distribution
In Canada:
Telephone: 905-812-0767
Fax: 905-812-0771
In the Far East:
Telephone: 852-2191-9003
Fax: 852-2736-6580
In Italy:
Telephone: 39-40-9490-111
Fax: 39-40-382137
In China:
Telephone: 852-2191-9003
Fax: 852-2736-6580
In India:
Telefax: 91-022-8202564
In Singapore:
Telephone: 65-273-2230
Fax: 65-273-2610
Page 4
In the United Kingdom:
Telephone: 44-1403-276500
Fax: 44-1403-276501
A05-976-00