Signaling Strobe
Features
• 93mA avg. current draw at 24VDC, regulated power
supply for SS241575ADA
• Multiple light intensities
–24 VDC: 15, 15/75, 75, or 110 cd models
–12 VDC: 15 or 15/75 cd
• No measurable in-rush in excess of peak current
• Intended for primary signaling
• Installer Easy strobe features
–Mounts to single gang box with MP-SF plate
–Plug-in terminal strip
–Wire strip gauge and wiring diagram on back
• Available with Multi-Alert™ horn, Sound Choice™
SP101, or V400 Series speaker
• 3 year warranty
System Sensor SS12/24ADA Series signaling strobes
comply with the Americans with Disabilities Act (ADA)
and the demanding requirements of the Underwriters
Laboratories Standard UL 1971 for the Hearing Impaired.
The 15/75 strobe models are UL 1971 listed at 15 cd.
To insure compliance with ADA and UL 1971, use the
System Sensor 75 candela models for non-sleeping areas,
and the wall-mounted 110 candela models for sleeping
areas. Available in red or beige at 12 or 24 VDC, the
SS12/24ADA series of signaling strobes can be surface
mounted directly to a standard 4″ backbox or can be
mounted to our semi-flush plate for recessed electrical
boxes. They are also available in combination with System
Sensor Multi-Alert horns and Sound Choice SP101 or V400
speakers for both visible and audible signaling.
Specifications
Input terminals:
Shipping Weight:
SS Series Strobes:
MASS Series
Horn/Strobes:
Operating
Temperature Range:
Mounting:
Surface:
Semiflush:
© System Sensor 8/96
18 – 12 AWG
Dimensions:
TOP
TOP
5 oz. (141g)
4″
4″
10.4 oz. (293g)
32° F to 120° F (0° C to 49° C)
4″ × 4″ × 11/2″ standard backbox
(21/8″ recommended)
4″ × 4″ × 11/2″ standard backbox
(21/8″ recommended) with
MP-SF semi-flush mounting
plate (order separately)
4″
23/4″
3″
1/4″
SS12/24ADA Series
This document is not intended to be used for installation purposes.
4″
33/4″
53/32″
111/32″
MASS12/24ADA Series
APPROVED
A05-206-04
Engineering Specifications
Strobe shall be a System Sensor Model ______ listed to
Standard UL 1971 for the Hearing Impaired and shall be
approved for Fire Protective Service. Strobe shall be wired
as a Primary Signaling Notification appliance. Strobe shall
also comply with the Americans with Disabilities Act
requirements for visible signaling appliances. Strobe shall
operate on 12 or 24VDC from a regulated DC supply or
full-wave rectified, unfiltered supply. The signaling strobe
shall be powered from a non-coded power supply when
powered with the horn or powered independently. Strobe
shall have no measurable in-rush current in excess of
operating peak current. Visual signaling devices are to be
installed in all non-sleeping/corridor and sleeping areas
per plans and specifications. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system.
All strobes shall be capable of mounting to a standard 4″ ×
4″ × 11/2″ backbox, in either a surface mount or semiflush
mount with separate mounting plate.
Sound Output Selection Guide
Multi-Alert Sounder – MA12/24D
Clips on
Tabs (ABC)1
ABC
Available Sounds
Slow Whoop
800 Hz continuous
(factory setting)
800–1000 Hz Alternating
2400 Interrupted
2400 Continuous
1200 Interrupted
Swept Frequency
Fast Warble
BC
AC
AB
C
B
A
None
Current (mA)
DC Regulated/FWR Unfiltered2
12V
24V
30V
21/40
38/56
46/72
15/24
17/32
19/23
21/31
13/19
17/24
15/27
28/45
34/46
35/56
38/59
23/33
34/47
30/47
35/55
43/58
43/64
46/73
27/41
43/60
38/59
Average*
12V
24V
85
92
87
85
89
85
85
85
85
93
92
90
94
91
92
92
Sound Output (dBA)
Peak*
UL (dBA) Ratings
12V
24V
12V
24V
93
100
79
85
94
91
96
93
95
96
93
99
98
98
104
101
101
100
79
79
79
79
75
79
79
85
85
85
85
82
85
85
Multi-Alert Sounder – MA12/24EH
Current (mA)
Sound Output (dBA)
Average*
Peak*
UL (dBA) Ratings
Clips on
DC Regulated/FWR Unfiltered2
Available Sounds
Tabs (ABC)1
12V
24V
30V
12V
24V
12V
24V
12V
24V
Fast Whoop
ABC
21/40
38/56
46/72
85
92
93
100
79
85
800 Hz Continuous
BC
15/24
28/45
35/55
87
93
96
101
79
85
800/1000 Hz Fast Dual
AC
17/32
34/46
43/58
85
92
95
101
79
85
Chirp
AB
19/23
35/56
43/64
89
90
93
104
79
85
2400 Hz Continuous
C
21/31
38/59
46/73
85
94
96
98
79
85
Bell
B
13/19
23/33
27/41
85
91
91
98
75
82
Laser
A
17/24
34/47
43/60
85
92
94
99
79
85
Electro-Mechanical
None
15/27
30/47
38/59
85
92
93
100
79
85
(factory setting)
* dBA measured in anechoic room at 10 feet.
1.See Tone Selection diagram below for tab clip removal and storage.
2.All models can be powered using uncoded full wave rectified, unfiltered supplies. Under no circumstances can the MA12/24 or SS12/24 Series device input
voltage exceed 33 VDC or be less than 9.6 VDC.
MA Sounder Tone Selection
COVER SLOT
SL
FO
R
ID
CL
IP
E
CO
VE
R
ST
OR
AG
E
TONE
SELECTION TABS
TAB A
TAB B
TAB C
CLIP
STORAGE
CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
USE A
SMALLBLADED
SCREWDRIVER
TO REMOVE
CLIPS
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
Page 2
A05-206-04
Standard Light Distribution
Vertical Dispersion
Horizontal Dispersion
ZERO AXIS
W
A
L
L
90˚ 85 80 75 70 65 60 55
50
Degree
0
5-30
5 35
40
45
10 50
55
15 60
65
70
20 75
80
85
25 90
0
45
40
FLOOR
35
30
Percent of Rating
100
90
65
46
34
27
22
18
16
15
13
12
12
12
0˚
–45˚
45˚
LIGHT
90˚
WALL
Degree
0
5-25
30-45
50
55
60
65
70
75
80
85
–90˚ 90
Percent of Rating
100
90
75
55
45
40
35
35
30
30
25
25
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with
specific minimum intensity percentages as shown in the graphs above.
Wiring
To Next
Device
or EOL
IN(–)
– VDC
(–)IN
OUT(–)
STROBE
Device
+ VDC
– VDC
or EOL
(–)OUT
IN(+)
OUT(+)
(+)OUT
NONCODED
SUPPLY
CAN BE
SOUNDER CODED
SUPPLY
+ VDC
Break off tab
To Next
– VDC
Device
+ VDC
From
panel or
previous
device
NONCODED
SUPPLY
or EOL
From
panel or
previous
device
From
panel or
previous
device
+ VDC
(+)IN
– VDC
To Next
Note: Jumpers (included in screw-pack) must be
installed as shown for tandem operation.
Strobe Only
Horn/Strobe Independent
Horn/Strobe Combination
Mounting
MA-12/24D
P
TO
Signal Strobe
Signal Strobe
Strobe
Surface Mount
Horn/Strobe
Surface Mount
MP-SF
MP-SF
MA-12/24D
Signal Strobe
P
TO
Signal Strobe
Horn/Strobe
Semiflush Mount
Strobe
Semiflush Mount
Page 3
A05-206-04
Electrical Ratings – Strobe Only
Model
Red
SS2415ADA
SS241575ADA
SS2475ADA
SS24110ADA
SS1215ADA
SS121575ADA
Beige
SS2415ADAB
SS241575ADAB
SS2475ADAB
SS24110ADAB
SS1215ADAB
SS121575ADAB
Supply
Voltage Range
20–30 VDC
20–30 VDC
20–30 VDC
20–30 VDC
12–14 VDC
12–14 VDC
Average Operating Current
from Regulated Supply
(mA)
75
93
170
210
170
225
In-rush Current in
Excess of Peak
Operating Current (mA)
0
0
0
0
0
0
Peak Operating
Current (mA)
180
220
400
500
380
560
Average Operating Current
from Full Wave Rectified,
Unfiltered Supply (mArms)*
90
120
200
245
200
270
* For additional information, see installation manual D900-01-00
Actual 12 volt operating voltage cannot be less than 9.6 VDC or greater than 15.4 VDC; actual 24 volt operating voltage cannot be less than 16 VDC or
greater than 33 VDC
Ordering Information
Models – ADA Compliant, UL 1971 Listed
Electromechanical
Red
Beige(B)/White(W)
Tone
Signaling Strobes
SS2415ADA
SS2415ADAB
SS241575ADA
SS241575ADAB
SS2475ADA
SS2475ADAB
SS24110ADA
SS24110ADAB
SS1215ADA
SS1215ADAB
SS121575ADA
SS121575ADAB
Multi-Alert Sounder with Signaling Strobe
MASS2415ADA
MASS2415ADAB
MAEH2415ADA
MASS241575ADA
MASS241575ADAB
MAEH241575ADA
MASS2475ADA
MASS2475ADAB
MAEH2475ADA
MASS24110ADA
MASS24110ADAB
MAEH24110ADA
MASS1215ADA
MASS1215ADAB
MAEH1215ADA
MASS121575ADA
MASS121575ADAB
MAEH121575ADA
V400 Series Speaker with Signaling Strobe
V4R2415ADA
V4R241575ADA
V4R2475ADA
V4R24110ADA
SP101 Series Speaker with Signaling Strobe
SP1R2415ADA
SP1W2415ADA
SP1R241575ADA
SP1W241575ADA
SP1R2475ADA
SP1W2475ADA
SP1R24110ADA
SP1W24110ADA
*Total current = strobe current + sounder current
Note: All 1575ADA strobe products are recommended for 20′ × 20′ areas or
Operating
Voltage
Product
Signaling
Signaling
Signaling
Signaling
Signaling
Signaling
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe Current
(Average mA)
Candela
24
24
24
24
12
12
VDC
VDC
VDC
VDC
VDC
VDC
75
93
170
210
170
225
15
15/75
75
110
15
15/75
Sounder
Sounder
Sounder
Sounder
Sounder
Sounder
with
with
with
with
with
with
Signaling
Signaling
Signaling
Signaling
Signaling
Signaling
Strobe
Strobe
Strobe
Strobe
Strobe
Strobe
24
24
24
24
12
12
VDC
VDC
VDC
VDC
VDC
VDC
*
*
*
*
*
*
15
15/75
75
110
15
15/75
Speaker
Speaker
Speaker
Speaker
with
with
with
with
Signaling
Signaling
Signaling
Signaling
Strobe
Strobe
Strobe
Strobe
24
24
24
24
VDC
VDC
VDC
VDC
75
93
170
210
15
15/75
75
110
Speaker
Speaker
Speaker
Speaker
with
with
with
with
Signaling
Signaling
Signaling
Signaling
Strobe
Strobe
Strobe
Strobe
24
24
24
24
VDC
VDC
VDC
VDC
75
93
170
210
15
15/75
75
110
less.
How to Order
SS1215ADAB
B=Beige Strobe
15 = 15 cd, UL 1971 Strobe
1575 = 15 cd, UL 1971, 75 cd on axis
75 = 75 cd, UL 1971 Strobe
110 = 110 cd, UL 1971 Strobe
12 = 12 Volt
24 = 24 Volt
SS = Signal Strobe
MASS = Multi-Alert Sounder/Strobe
MAEH = Multi-Alert Sounder/Strobe
with Electromechanical Tone
V4R = 400 Series Speaker, Red
SP1R = SP101 Series Speaker (Strobe), Red
SP1W = SP101 Series Speaker (Strobe), White
System Sensor Worldwide Distribution
In Canada:
System Sensor Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario
Canada L5N 3T5
Telephone: 905-812-0767
Fax: 905-812-0771
Page 4
In the United Kingdom:
System Sensor Europe, Ltd.
Horsham Gates III, North St.
Horsham, West Sussex
RH13 5PJ, United Kingdom
Telephone: 44-1403-276500
Fax: 44-1403-276501
In India:
System Sensor India
A-204 Maheshwari Nagar
Orkay Mills Lane
Andheri East, Mumbai 400093
Telefax: 91-022-8202564
In the Far East:
System Sensor
Pittway Far East, Ltd.
Suite 706, New T&T Centre
7 Canton Road
Tsimshatsui, Kowloon, Hong Kong
Telephone: 852-2730-9090
Fax: 852-2736-6580
A05-206-04