Models Available
SS2415ADAS Strobe with Sync•Circuit
SS241575ADAS Strobe with Sync•Circuit
MASS2415ADAS Sounder/Strobe with Sync•Circuit
MASS241575ADAS Sounder/Strobe with Sync•Circuit
Features
• Works on two wire circuit
• No synchronization module required
• Synchronized and unsynchronized strobes can be
combined on the same zone in any combination
• Patent pending Sync•Circuit™
• 24 VDC versions only
• 15 and 15/75 cd versions available
• Available with Multi-Alert™ Sounder
• Constant current draw over voltage range
• Stand alone strobe mounts to single gang box with
MP-SF plate
• ADA compliant, UL 1971 listed
• Installer easy plug-in terminal strip
on stand-alone strobe
The SS24ADAS Series Synchronized Strobes are crystal
controlled to flash at precisely one flash per second. When
power is applied to an indicating circuit controlled by one
controller, all SS24ADAS or MASS24ADAS series devices in
that zone will flash simultaneously. No synchronizing
modules or coded supplies are necessary. The strobes can
be used in any combination with other System Sensor
ADA strobes, ADA horn/strobes, and ADA speaker/
strobes.
The unique lens/reflector design maintains the UL 1971
light dispersement pattern while flashing at the ADA
minimum 1 flash per second. Available in red at 24 VDC,
the SS24ADAS strobes can be surface mounted directly to
a standard 4″ backbox or can be mounted to our semiflush plate for recessed electrical boxes. They are also
available in combination with System Sensor Multi-Alert™
horns for both visible and audible signaling.
Specifications
Input terminals:
Shipping Weight:
SS-ADA Strobes:
MASS-ADA
Horn/Strobes:
Operating
Temperature Range:
Mounting:
Surface:
Semiflush:
© System Sensor 8/96
18 – 12 AWG
Dimensions:
TOP
TOP
5 oz. (141g)
4″
4″
10.4 oz. (293g)
32° F to 120° F (0° C to 49° C)
4″ × 4″ × 11/2″ standard backbox
(21/8″ recommended)
4″ × 4″ × 11/2″ standard backbox
(21/8″ recommended) with
MP-SF semiflush mounting plate
(order separately)
4″
23/4″
3″
1/4″
SS Series ADA
This document is not intended to be used for installation purposes.
33/4″
53/32″
4″
111/32″
MASS Series ADA
APPROVED
A05-239-03
General Description
All Series SS24ADAS strobes are suitable for primary
signaling in public mode life safety applications. The
strobes can be connected to the alarm indicating circuit of
a UL listed fire alarm control panel. They are compatible
with DC line supervision. Panels may have full-wave
rectified, unfiltered power supplies. The strobes are
available for 24VDC operation and can be used with the
System Sensor Multi-Alert™ horn. Stand-alone strobe
versions incorporate these “installer easy” features: plug-
in terminal strip, wiring guide, and strip gauge (on back).
Semiflush mounting is available with the addition of an
MP-SF accessory plate. When installed in a zone, the
SS24ADAS and MASS24ADAS Series devices flash
simultaneously. Note: SS24ADAS and MASS24ADAS
Series devices operating in the same zone will not be
synchronized if energized at different times (i.e., if
more than one controller is controlling the same zone).
Sound Output Selection Guide
Multi-Alert Sounder – MA12/24D
Clips on
Tabs (ABC)1
ABC
Available Sounds
Slow Whoop
800 Hz continuous
(factory setting)
800–1000 Hz Alternating
2400 Interrupted
2400 Continuous
1200 Interrupted
Swept Frequency
Fast Warble
BC
AC
AB
C
B
A
None
Multi-Alert Sounder – MA12/24EH
Clips on
Available Sounds
Tabs (ABC)1
Fast Whoop
ABC
800 Hz Continuous
BC
800/1000 Hz Fast Dual
AC
Chirp
AB
2400 Hz Continuous
C
Bell
B
Laser
A
Electro-Mechanical
None
(factory setting)
Current (mA)
DC Regulated/FWR Unfiltered2
24V
30V
38/56
46/72
28/45
34/46
35/56
38/59
23/33
34/47
30/47
Average*
24V
92
35/55
43/58
43/64
46/73
27/41
43/60
38/59
Current (mA)
DC Regulated/FWR Unfiltered2
24V
30V
38/56
46/72
28/45
35/55
34/46
43/58
35/56
43/64
38/59
46/73
23/33
27/41
34/47
43/60
30/47
38/59
Sound Output (dBA)
Peak*
UL (dBA) Ratings
24V
24V
100
85
93
92
90
94
91
92
92
Average*
24V
92
93
92
90
94
91
92
92
99
98
98
104
101
101
100
85
85
85
85
82
85
85
Sound Output (dBA)
Peak*
24V
100
99
98
98
104
101
101
100
UL (dBA) Ratings
24V
85
85
85
85
85
82
85
85
* dBA measured in anechoic room at 10 feet. The acoustical output shall meet the current requirements of UL Standard 464.
1. See Tone Selection diagram below for tab clip removal and storage.
2. All models can be powered using uncoded full wave rectified, unfiltered supplies. Under no circumstances can SSADAS or MASSADAS input voltage exceed 33 VDC or be
less than 20 VDC.
MA Sounder Tone Selection
COVER SLOT
SL
FO
R
ID
CL
IP
E
CO
VE
ST
R
OR
AG
E
TONE
SELECTION TABS
TAB A
TAB B
TAB C
CLIP
STORAGE
CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
USE A
SMALLBLADED
SCREWDRIVER
TO REMOVE
CLIPS
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
Page 2
A05-239-03
Standard Light Distribution
Vertical Dispersion
Horizontal Dispersion
ZERO AXIS
W
A
L
L
90˚ 85 80 75 70 65 60 55
50
Degree
0
5-30
5 35
40
45
10 50
55
15 60
65
70
20 75
80
85
25 90
0
45
40
FLOOR
35
30
Percent of Rating
100
90
65
46
34
27
22
18
16
15
13
12
12
12
0˚
–45˚
45˚
LIGHT
90˚
WALL
Degree
0
5-25
30-45
50
55
60
65
70
75
80
85
–90˚ 90
Percent of Rating
100
90
75
55
45
40
35
35
30
30
25
25
A polar light distribution in both horizontal and vertical directions is mandated for the strobes by the Standard UL 1971 for the Hearing Impaired, with
specific minimum intensity percentages as shown in the graphs above.
Wiring
To Next
Device
or EOL
IN(–)
STROBE
Device
+ VDC
– VDC
– VDC
(–)IN
OUT(–)
or EOL
(–)OUT
IN(+)
OUT(+)
(+)OUT
NONCODED
SUPPLY
CAN BE
SOUNDER CODED
SUPPLY
+ VDC
Break off tab
To Next
– VDC
Device
+ VDC
From
panel or
previous
device
NONCODED
SUPPLY
or EOL
From
panel or
previous
device
From
panel or
previous
device
+ VDC
(+)IN
– VDC
To Next
Note: Jumpers (included in screw-pack) must be
installed as shown for tandem operation.
Strobe Only
Horn/Strobe Independent
Horn/Strobe Combination
Mounting
MA-12/24D
P
TO
Signal Strobe
Signal Strobe
Strobe
Surface Mount
Horn/Strobe
Surface Mount
MP-SF
MP-SF
MA-12/24D
Signal Strobe
P
TO
Signal Strobe
Horn/Strobe
Semiflush Mount
Strobe
Semiflush Mount
Page 3
A05-239-03
Electrical Ratings – Strobe Only
Model
SS2415ADAS
SS241575ADAS
Supply
Voltage Range
20–30VDC
20–30VDC
Average Operating Current
from Regulated
Supply (mA)
106
195
Peak Operating
Current (mA)
200
350
Operating Current from
Full Wave Rectified,
Unfiltered Supply (mArms)*
125
180
* For additional information, see installation manual D900-06-00; for EH models, see installation manual D900-12-00.
Engineering Specifications
Strobe shall be a System Sensor Model ______ listed to
Standard UL 1971 for the Hearing Impaired and shall be
approved for Fire Protective Service. Strobe shall be wired
as a Primary Signaling Notification appliance. Strobe shall
also comply with the Americans with Disabilities Act
requirements for visible signaling appliances. Strobe shall
operate at 24VDC from a regulated DC supply or full-wave
rectified, unfiltered supply. The signaling strobe shall be
powered from a non-coded power supply when powered
with the horn or powered independently. Visual signaling
devices are to be installed in all non-sleeping/corridor and
sleeping areas (110 cd only) per plans and specifications.
The strobe light shall consist of a xenon flash tube and
associated lens/reflector system. Each strobe shall be
designed for one flash per second over all operating
conditions. All strobes shall be capable of mounting to a
standard 4″ × 4″ × 11/2″ backbox, in either a surface mount
or semiflush mount with separate mounting plate. Strobe
shall flash synchronously with other SS24ADAS and
MASS24ADAS Series devices in the same zone for a
minimum of 15 minutes. Note: SS24ADAS,
MASS24ADAS and MAEH24ADAS Series devices
operating in the same zone will not be synchronized if
energized at different times (i.e., if more than one
controller is controlling the same zone).
Ordering Information
Models – ADA Compliant, UL 1971 Listed
Product
Signaling Strobes
SS2415ADAS
Signaling Strobe with Sync•Circuit
SS241575ADAS**
Signaling Strobe with Sync•Circuit
Multi-Alert Sounder with Signaling Strobe
MASS2415ADAS
Sounder with Signaling Strobe with Sync•Circuit
MASS241575ADAS**
Sounder with Signaling Strobe with Sync•Circuit
Electromech. Tone
Operating
Voltage
Strobe Current
(Average mA)
Candela
24 VDC
24 VDC
106
195
15
15/75
24 VDC
24 VDC
*
*
15
15/75
MAEH2415ADAS
MAEH241575ADAS
*Total current = strobe current + sounder current
**UL 1971 listed to 15 cd. Recommended for areas 20′ × 20′ or smaller.
How to Order
SS2415ADAS
Synchronizable Strobe
15 = 15 cd, UL 1971 Strobe
1575 = 15 cd UL 1971
24 Volt
SS = Signal Strobe
MASS = Multi-Alert Sounder/Strobe
MAEH = Multi-Alert Sounder/Strobe
with Electromechanical Tone
System Sensor Worldwide Distribution
In Canada:
System Sensor Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario
Canada L5N 3T5
Telephone: 905-812-0767
Fax: 905-812-0771
Page 4
In the United Kingdom:
System Sensor Europe, Ltd.
Horsham Gates III, North St.
Horsham, West Sussex
RH13 5PJ, United Kingdom
Telephone: 44-1403-276500
Fax: 44-1403-276501
In India:
System Sensor India
A-204 Maheshwari Nagar
Orkay Mills Lane
Andheri East, Mumbai 400093
Telefax: 91-022-8202564
In the Far East:
System Sensor
Pittway Far East, Ltd.
Suite 706, New T&T Centre
7 Canton Road
Tsimshatsui, Kowloon, Hong Kong
Telephone: 852-2730-9090
Fax: 852-2736-6580
A05-239-03