Product Overview
Multi-Alert Sounder:
12 and 24V operation
8 field-selectable tones
System Sensor's Multi-Alert sounder and sounder/strobes are suited to provide primary
or secondary signaling for fire and security applications. The MA and MASS models
provide eight field-selectable warning tones.
Multi-Alert Strobes and Sounder/Strobes:
24V operation
1.5 or 15 candela
UL1638 listed
The Multi-Alert models mount directly to 4″ square back boxes. Optional mounting
plates are available for either flush or semi-flush installations. Model MA12/24D is suitable
for outdoor applications when installed with the WBB weather-proof back box.
Mini-Alert Sounders:
12 and 24V operation
1.5 cd add-on strobe available
Multi-Alert Strobes. System Sensor’s Multi-Alert strobes are UL1638 compliant
electronic visible warning signals that flash approximately every 1.5 seconds. All
circuits are polarized to be compatible with DC alarm supervision.
Mini-Alert Sounders. System Sensor’s PA400 series Mini-Alert sounders operate
at 12 and 24 volts and are ideal for hotel, motel or residential fire system
applications, where a smaller notification device is desired. The PA400
sounders are available with or without FIRE identification, and are offered in
red, beige, and white.
Engineering Specifications
Multi-Alert Sounders shall be a System Sensor Model MA 12/24D capable of operating at 12 and 24VDC. Sounder shall be
listed to Underwriter’s Laboratories Standard UL464 for fire protective signaling systems. Sounder shall have an operating
temperature between –31°F and 151°F. Sounder shall have eight tone options, selected by means of clips.
Mini-Alert Sounders shall be a System Sensor Model ——— capable of operating at 12 and 24VDC. Sounder shall be listed
to Underwriter's Laboratories Standard UL464 for fire protective signaling systems. Sounder shall have an operating temperature between 14°F and 140°F.
Multi-Alert and Mini-Alert Sounder/Strobes shall be a System Model ——— capable of operating at 24VDC. Sounder/strobe
shall be listed to Underwriter’s Laboratories Standards UL464 and UL1638 for fire protective signaling systems.
Sounder/strobe shall have an operating temperature between 32°F and 120°F. Strobe shall be powered independently of the
sounder and shall operate at 24VDC, with a UL range rating of 22.5 to 30VDC. Actual operating voltage must be between
18 and 33VDC. Strobe shall have a minimum light output of 1.5 or 15 candela and shall be UL1638 listed for private
mode applications.
Multi-Alert Sounder Specifications
Dimensions
4″ x 4″ x 21/4″
Weight
5.7 oz. (162 g)
Mounting
Sur face
4″ x 4″ back box (11/2″ to 2 1/8″ deep)
Flush
4″ x 4″ BBD deep back box (2 3/4″ deep)
Semi-flush 4″ x 4″ back box (11/2″ to 2 1/8″ deep)
with MP-SF mounting plate
Operating Voltage
12VDC to 24VDC FWR unfiltered*
Input Terminals
12 to 18 AWG
Operating Temperature Range
–32° to 151°F (–35° to 66°C)
*Actual 12 V operating voltage cannot be less than 9.6VDC or greater than 18.7VDC.
Actual 24 V operating voltage cannot be less than 18VDC or greater than 33VDC.
Multi-Alert Strobe Specifications
Dimensions
4″ x 4″ x 2 15/16″
Mounting
Sur face
4″ x 4″ back box (11/2″ to 21/8″ deep)
Semi-flush 4″ x 4″ back box (11/2″ to 21/8″ deep)
with MP-SF mounting plate
Weight
8.2 oz. (232 g)
Operating Temperature Range
–31° to 151°F (–35° to 66°C)
Input Terminals
12 to 18 AWG
Operating Voltage
24VDC and FWR unfiltered*
*Actual 24V operating voltage cannot be less than 18VDC or greater than 33VDC.
Mini-Alert Specifications
Dimensions
4 1/2″ x 2 3/4″x 11/8″
Mounting
Sur face
Single gang back box
Flush
4″ x 4″ BBD deep back box (2 3/4″deep)
Weight
2.4 oz. (159 g)
Operating Temperature Range
14° to 140°F (–10° to 60°C)
Input Terminals
12 to 18 AWG
Operating Voltage
12VDC to 24VDC FWR unfiltered*
*Actual 12V operating voltage cannot be less than 9.6VDC or greater than 18.7VDC.
Actual 24V operating voltage cannot be less than 18VDC or greater than 33VDC.
Ordering Information/Current Draw
Multi-Alert/Mini-Alert Model Numbers
Description
Voltage
Average
Current
Candela
dB Output
(UL)***
MA12/24D
Multi-Alert sounder
12/24VDC
*
—
75–85
SS24LO
Multi-Alert strobe
24VDC
25 mA
1.5
—
SS24M
Multi-Alert strobe
24VDC
75 mA
15.0
—
SS24LOLA
Multi-Alert strobe (“FUEGO” lens)
24VDC
25 mA
1.5
—
MASS24LO
Multi-Alert sounder /strobe
24VDC
**
1.5
75–85
MASS24M
Multi-Alert sounder /strobe
24VDC
**
15.0
75–85
MASS24LOLA
Multi-Alert sounder/strobe (“FUEGO” lens) 24VDC
**
1.5
75–85
Mini-Alert sounder
12/15 mA
—
82
Red
Beige
PA400R
PA400B
PA400R-F
PA400B-F
PS24LO
White
PA400W
12/24VDC
PA400W-F
Mini-Alert sounder (“Fire” identification)
12/24VDC
12/15 mA
—
82
PS24LOW
Add-on strobe
12/24VDC
5 mA
1.5
82
Accessory Model Numbers
Description
MP-F/MP-FB
Flush mounting plate (red/beige)
MP-SF/MP-SFB
Semi-flush mounting plate (red/beige)
BB-D
Flush mounting deep back box, 2 3/4″ deep
WBB
Weatherproof back box for MA 12/24D
* Current ranges from 10mA to 55mA depending upon voltage and sound selected
** Current ranges from 35mA to 80mA depending upon voltage and sound selected
*** Sound output varies depending upon voltage and sound selected.
Note: LO and M style strobe and sounder/strobe models are not MEA approved.
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800-SENSOR2
Fx: 630/377-6495
Documents on Demand
1-800-736-7672 x3
www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 011.86.29.524.6253
Fx: 011.86.29.524.6259
System Sensor– Far East
Ph: 011.85.22.191.9003
Fx: 011.85.22.736.6580
System Sensor Europe
Ph: 011.44.1403.276500
Fx: 011.44.1403.276501
System Sensor in Singapore
Ph: 011.65.273.2230
Fx: 011.65.273.2610
System Sensor– Australia
Ph: 011.613.54.281.142
Fx: 011.613.54.281.172
© 1999 System Sensor. The company reserves the right to change product specifications without notice.
A05-207-07•11/99(10K)•#571