ASTEC AP6C64AA

48V 400-600 Amp
Breaker Panel (BIP)
ASIA
EUROPE
AMERICAS
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
AP6C64AA
A breaker interface panel, also knows as a power distribution unit
(PDU), or frame supervisory panel (FSP), improves system power
stability and provides a convenient centralized location for all
customer load circuit breakers, alarms, and filtering.
Electrical Specs
INPUT
DC input
-40 VDC to –75 VDC
Transients
ANSI T1.315-1994, FTZ19, BTR2511
Input feeds
4 x 100A each
4 x 150A each (available in the future)
OUTPUT
DC output
20 x 25A breakers total
Four breaker modules,
each with 5 x 25A breakers
Alarm signals
Critical, major, minor alarms
Special Features
• Low profile:
• Fits in 2U height,
• 3.47", 88.1 mm
• 23" width
• 4 x 100 A input feeds, upgradeable to 4 x 150A
input feeds
• supports A & B redundant input feeds
• 4 hot swappable Breaker Modules + one Alarm
Module
• Breaker Modules available in various configurations,
all come equipped with:
• 28,200 µF capacitor bank
• automatic inrush current limiting
• hot swappable, field replaceable without
service interruption
• Breaker Module configurations:
• 5A 5A 5A 5A 5A
• 20A 20A 20A 20A 20A
• 25A 25A 5A 25A 25A
• 10A 5A 30A 5A 10A
• 25A 25A 25A 25A 25A
• 30A 30A 5A 30A 30A
• other configurations available on request,
please consult your Astec representative
• Standard Alarm module comes equipped with:
• isolated alarm contacts
• input feed fail alarm
• output breaker trip alarm
• critical, major, minor alarms
• end aisle lamp drive
• fully programmable, 6 bit, shelf ID
• LED test switch
• connections for voice and data jacks
• Enhanced, customized alarm modules available by
special order
182
America’s (USA): 1-888-41-ASTEC
Environmental
EMC/EMI:
No switching components, inherently
EMI/EMC benign
ESD:
Bellcore GR-1089-CORE, ETSI 300 386-1,
(15kV)
Operating Temperature and Humidity
-5°C to +55°C normal, 5% to 85% RH, non-condensing
-8°C to +65°C short term
Shock and
Vibration:
Fire Resistance:
Bellcore GR-063-CORE and ETSI 300 019
Zone 4 earthquake
UL94V-0
Safety
UL
CSA
EN
Bellcore
Europe (UK): 44 (1384) 842-211
1950
C22.2 950
60850, 41003
GR-063-CORE
Asia (HK): 852-2437-9662
rev 12.01.01