ETC 808-H-3A

Magnetic Overcurrent Circuit Breaker 808-...
Description
Single pole miniaturised magnetic circuit breakers with unique highspeed operating mechanism and push/pull on/off manual actuation.
Fitted with electrically separate excitation and switching circuits, and
one pair of auxiliary contacts which close when the main circuit is open.
Also suitable for impulse operation. Designed for printed circuit board
mounting. Low temperature sensitivity.
NEW
Typical applications
Printed circuit boards and components, safety and control systems.
808
Ordering information
Technical data
Type No.
808
fast-acting
Manual release (optional)
H
manual release facility
Current ratings
0.01 ...8 A
808 -
H
- 1A
ordering example
Packaging quantity: 250 pcs
Voltage rating
DC 24 V
UL, CSA: AC 120 V, DC 60 V
Current ratings
0.01...8 A
Max. continuous load
excitation circuit (2-3)
2.65 x IN
Max. continuous load
switching circuit 6-7
auxiliary circuit 4-5
5A
Typical life
6,000 operations
at 5 A for switching circuit
Ambient temperature
-30...+70 °C (-22...+158 °F)
Insulation co-ordination
(IEC 60664 and 60664A)
Rated impulse
withstand voltage
1.5 kV
3
Pollution
degree
2
Current
Internal
Current
Internal
rating (A)
0.01
resistance (Ω)
625
rating (A)
0.8
resistance (Ω)
0.096
Dielectric strength
(IEC 60664 and 60664A)
excitation to
switching circuit
excitation to
auxiliary circuit
0.02
170
0.9
0.085
Insulation resistance
> 100 MΩ (DC 500 V)
0.03
77
1
0.073
0.04
47
1.2
0.050
Interrupting capacity
(o-o-o)
100 A
0.05
29.2
1.5
0.031
0.08
10.3
2
≤ 0.02
0.1
5.6
2.5
≤ 0.02
0.2
1.65
3
≤ 0.02
0.3
0.89
3.25
≤ 0.02
Degree of protection
(IEC 60529/DIN 40050)
operating area IP 30
terminal area IP 00
0.4
0.39
4
≤ 0.02
Vibration
0.5
0.28
4,5
≤ 0.02
0.6
0.198
5
≤ 0.02
3 g (57-500 Hz), ±0.23 mm (10-57 Hz),
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
0.7
0.143
8
≤ 0.02
Shock
25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH
to IEC 60068-2-3, test Ca
Mass
approx. 10 g
Standard current ratings and typical internal resistance values
Interrupting capacity
(UL 1077)
Test voltage
AC
840 V
AC 1,680 V
1,000 A AC 120 V
200 A DC 60 V
Approvals
Authority
Voltage ratings
Current ratings
CSA
AC 120 V, DC 60 V
0.01 ...5 A
UL
DC 60 V
0.01 ...8 A
AC 120 V
0.01 ...5 A
Issue C
☎
USA (847) 827-7600 - CANADA (905) 764-9510
171
Magnetic Overcurrent Circuit Breaker 808-...
Dimensions
Internal connection diagram
20
.787
ø9.3
.366
ø4
.157
5
.197
0 ON
5 OFF
.197
808
4
5
6
7
5
.197
2
2-3: excitation circuit
6-7: switching circuit
4-5: auxiliary circuit
3
+
30
1.18
-
14
.551
Typical time/current characteristics at +23°C/+73.4°F
3
0.6
.024
1000
100
10
1
ø4
.157
5
.197
2.5 ON
.098
7.5 OFF
.295
808-H
20
.787
ø9.3
.366
10000
Trip time in milliseconds
15
.591
0.5
.020
10
.394
15.5
.610
5
.197
0.1
1
2
4
6 8 10
20
40
14
.551
30
1.18
... times rated current
15
.591
0.5
.020
10
.394
15.5
.610
0.6
.024
mm
This is a metric design and millimeter dimensions take precedence ( inch )
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications without
notice is reserved.Product markings may not be exactly as the ordering codes. Errors and
omissions excepted.
172
☎
USA (847) 827-7600 - CANADA (905) 764-9510
Issue C