ETC AZ692

`
AZ692/AZ693
10 AMP MINIATURE
POWER RELAY
FEATURES
Isolation spacing greater than 8mm
Dielectric strength 4000 Vrms coil to contact
Approvals/Standards include UL, CSA,VDE, IEC, CEE,
SEMKO
Single pole – Forms A, B and C available
10A switching
Life expectancy to 30 million operations
Epoxy sealed version for automatic wave soldering and
cleaning
UL file E44211 ; CSA file LR85091 ; VDE
4120-4940-4002/A1
GENERAL DATA
CONTACTS
Arrangement
SPDT (1 Form C)
SPST (1 Form A and 1 Form B)
Ratings
Resistive load:
Max switching power : 300W or 2500VA
Max switched current : 10A ; 64A for 2ms
Max switched voltage : 150* VDC or 380VAC
10A at 24VDC or 115VAC
0.25HP 120VAC motor load
10A at 250VAC
B300 pilot duty
UL Rating
* If switching voltage is greater than 30VDC, special precautions
must be taken. Please consult the factory.
Material
Silver cadmium oxide
Resistance
<30 milliohms initially
(at rated current, voltage drop method)
COIL
Power
At Pickup Voltage
(typical)
Standard coil 337mW
Sensitive coil 234mW
Max Continuous
Dissipation
1.9W at 20°C ambient
1.4W at 40°C ambient
Temperature Rise
Standard 40°C at nominal coil voltage
Sensitive 26°C at nominal coil voltage
Max Temperature
110°C
Life Expectancy
Mechanical
Electrical
Minimum operations
30 million operations
1x105 at 10A, 30VDC or 115VAC
2x105 at 8A, 250VAC
Operate Time (typical)
6ms at nominal coil voltage
Release Time (typical)
2ms at nominal coil voltage
(with no coil suppression)
Dielectric Strength
(at sea level for 1 min)
4000 Vrms coil to contact
1000 Vrms between open contacts
Insulation Resistance
10,000 megohms min at 500VDC, 20°C,
50% RH
Dropout
Greater than 10% of nominal coil voltage
Ambient Temperature
Operating
Storage
At nominal coil voltage
Standard -55°C to 70C
Sensitive -55°C to 80C
Both -55°C to 110C
Vibration
0.062” DA at 10 – 55 Hz
Shock
20g
Enclosure
PBT Polyester
Terminals
Tinned copper alloy, PC
Weight
17 grammes
NOTES
1. All values at 20°C
2. Relay may pull in with less than ‘Must Operate’ value
3. PCB layout viewed towards terminals
4. Specifications subject to change without notice
5. Unsealed relays should not be dip cleaned
Logistic Design (UK) Limited
Unit 3 Eagle Centre Way, Sedgwick Road
Luton LU4 9US, United Kingdom
Tel +44 (0)1582 599 600
Fax +44 (0)1582 599 700
www.zettlerrelay.com
[email protected]