MODEL: MODEL NUMBER: Switched PDU OSP-V-16-23-16-N1 Input (left) Features Current Meter Digital True RMS Current Meter Power Monitor Remote Total Power Monitoring by Meter, Web, SNMP, Free Bundle Software Protocols http, https, SNMP, DHCP, UDP Outlet Control Individual Outlet Control Power Delay Power On/Off Sequence can be Defined Alarm Thresholds User-Defined Alarm Thresholds for Warning and Overload Event Alert Email, Trap, Audible Alarm Specification: General Communication Operation Output: (14) IEC320 C13 (2) IEC320 C19 Input: (1) IEC320 C20 Inlet; Enclosed IEC320 C19 to C20 Power Cord 3 Meters long Protection (1) 16 Amp Circuit Breaker SSL Indication (1) Yellow LED DHCP Indication (1) Green LED Output Status (16) Red LED Network (1) RJ45 for Ethernet Current Meter 3 Digits Seven Segments for True RMS Meter Range: 0A ~ 20A Resolution: 0.1A Precision: +/-2%+/-0.1 Amp Nominal Voltage 230V Voltage 200V~ 240V full range Frequency 50/60HZ full range Max. Output Current 16 Amp (UL derated 12 Amp) Temperature 0 ~ 40 Celsius degree Humidity 0% ~ 90% Size 56 x 1245 x 44 mm Weight 4 kg Regulatory Approvals: UL 60950-1, UL Listed, CSA, cUL Listed, CB by UL CE, EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3 C-Tick AS/NZS CISPR 22: 2006 FCC Part 15 Class A, ICES-003 Orion Fans 10557 Metric Drive Dallas, TX 75243 800.323.2439 A division of Knight Electronics, information and data are subject to change without prior notification.