P-TEC I38I

iBright ™
I38i T8 LED Tube
G3 IPS US
Family Model
HFL-8030N-06060U-H0
HFL-8060N-12060U-H0
HFL-8080N-15060U-H0
Performance Summary
iBright™ I38i T8 LED Tubes are the next generation solution in replacing
conventional fluorescent lights. They feature higher reliability, easier retrofit, and
higher efficacy in lighting and energy usage.
Length: 1.96 ft (600 mm), 3.93 ft (1200 mm), 4.92 ft (1500 mm)
Higher Reliability
Luminous efficacy:
iBright™ I38i LED Tubes are more reliable than fluorescent tubes for three
reasons. 1) They utilize high quality SMD LEDs, which feature low light decrease
over time and excellent heat dissipation; 2) they use specially designed aluminum
housing that prevents internal heat buildup through a design allowing efficient heat
dissipation; and 3) they use a specially designed loop circuit, meaning one LED
failing won’t make the entire tube fail, as happens with fluorescent tubes.
Lumens:
Power consumption:
8W± 1W,
17W± 1W,
21W± 1W
>95 lm/W
800-850 lm,
1600-1700 lm,
2000-2100 lm
CCT:
2800-3200 K
4250-4750 K
5500-6500 K
CRI: >84
Easier Retrofit
iBright™ I38i LED Tubes can be placed directly into existing T8 sockets, simply by
removing the starter and disconnecting the ballast in the fixture.
Higher Efficacy
iBright™ I38i LED Tubes use high quality SMD LEDs of high efficacy. They provide
versatile lighting well-suited for use in offices, galleries, shop windows, hotels,
meeting rooms. They are especially suited to operation in low temperature areas,
just like conventional fluorescent lights. Choose the iBright™ I38i for general
illumination, task lighting, display lighting, or back lighting.
www.atgelectronics.com
Toll free: 877-461-5333
Recommended Applications
General illumination for homes, offices, restaurants, hotels,
malls, buses, trains, warehouses, parking lots etc;
Task lighting for cabinets, cupboards etc in your homes,
restaurants, and kitchens or any other places where
accent lighting is required.
Retail display lighting for the articles in your stores and shops;
Back lighting for square billboards or advertisement boards.
Ordering Information
Typical Order Example: T8I306HU60S0U0
SERIES
GENERATION
SIZE
VOLTAGE
CCT
Lens Type
T8=T8 Tube
I3=G3 IPS
06=0.6m/2ft
12=1.2m/4ft
15=1.5m/5ft
HU=100-277
VAC
30=3000K
45=4500K
60=6000K
S=Striated Lens
OPTION A
0=Default
OPTION B
U0=US Version
Product Specifications
CONSTRUCTION & MATERIALS
Length
Housing
Tube Type
Base Type
Lens Type
1.96 ft (600 mm)
3.93 ft (1200 mm)
Extrusion Aluminum and PC Diffuser
T10
G13
Striated
4.92 ft (1500 mm)
ENVIRONMENTAL SYSTEM
Work Environment
Operating Temperature
Indoor use (applicable for dry environments)
-20~40℃ (-4~104℉)
OPTICAL SYSTEM
Type
Luminous Flux
Color Temperature
CRI
Beam Angle
1.96 ft (600 mm)
3.93 ft (1200 mm)
800-850 lm
1600-1700 lm
2800-3200 K, 4250-4750 K, 5500-6500 K
>84
120°
4.92 ft (1500 mm)
2000-2100 lm
1.96 ft (600 mm)
8W± 1W
100-277 VAC
50-60 HZ
>0.95
4.92 ft (1500 mm)
21W± 1W
ELECTRICAL SYSTEM
Type
Power Consumption
Input Voltage
Frequency
Power Factor
REGULATORY & VOLUNTARY
QUALIFICATIONS
UL, cUL
CE, RoHS
UL, cUL, CE listed external power supply
www.atgelectronics.com
Toll free: 877-461-5333
3.93 ft (1200 mm)
17W± 1W
Photometric
ZONAL LUMEN SUMMARY
ZONE
LUMENS
% LAMP
% LUMINAIRE
0-30
442.3
26.10%
26.10%
0-40
700
41.30%
41.30%
0-60
1189.7
70.20%
70.20%
60-90
434
26%
26%
70-100
272.7
16.10%
16.10%
90-120
65.8
3.90%
3.90%
0-90
1,623.70
95.80%
95.80%
90-180
70.7
4.20%
4.20%
0-180
1,694.30
100%
100%
LUMINOUS INTENSITY
Gamma
C 0°
C 45°
C 90°
C 135°
C 180°
C 225°
C 270°
C 315°
C 360°
0.0°
392
392
392
392
392
392
392
392
392
15.0°
379
333
304
337
377
274
293
272
379
30.0°
313
292
276
292
315
246
203
248
313
45.0°
193
212
201
212
196
167
192
159
193
60.0°
93
127
213
121
105
126
167
120
93
75.0°
19
115
137
109
21
84
87
80
19
90.0°
0.23
58
58
68
0.06
34
41
32
0.23
ILLUMINANCE AT A DISTANCE
BEAM SPREAD(FT)
HEIGHT(FT)
FOOTCANDLE
HORIZONTAL
VERTICAL
2
166.1 FC
5.5
3.9
12.2
4
41.5 FC
10.9
7.9
24.4
6
18.5 FC
16.4
11.8
36.7
8
10.4 FC
21.8
15.8
48.9
10
6.6 FC
27.3
19.7
61.1
BEAM ANGLE
107.5°
www.atgelectronics.com
Toll free: 877-461-5333
FIELD SPREAD(FT)
HORIZONTAL
VERTICAL
FIELD ANGLE
89.1°
N/A
143.7°
www.atgelectronics.com
Toll free: 877-461-5333
USER GUIDE
Included in this box
ATG Electronics iBright™ I38i T8 LED Tube (G3 IPS US), 1 Pc
User Guide, 1 set
Red-Black Wires, 2 PCs
Wire Nuts, 4 PCs
Note:
Please read this entire manual to fully understand and safety use this product.
Specifications are subject to change without notice. Please visit www.atgelectronics.com for the most recent user guide versions.
Warning:
WARNING – Risk of fire or electric shock. iBright™ I38i T8 LED Tube installation requires knowledge of luminaires electrical systems. If not
qualified, do not attempt installation. Contact a qualified electrician.
WARNING – Risk of fire or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown in the
photographs and/or drawings.
WARNING – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
Lamp replacement instructions shall indicate the manufacturer's custom lamp part number, and a method to order replacement lamps by
phone, website and/or mail. These instructions shall be included on an information sheet packaged with each unit.
 Retrofit Luminaire with Electronic Ballast
Installation Steps
Step 1: Turn off main power before installation.
For safety, make sure main power source is switched off before attempting to install.
Step 2: Take off existing fluorescent light and disconnect the ballast.
Step 3: Cut four leads of G13 lamp holders. (For detailed placement of the cuts, note the X’s on the wiring diagram labeled “Before” shown
below.)
Step 4: Reconnect lamp holder leads L and N to the supply wires of branch circuit according to the wiring diagram below. Both G13 sockets of
the fixture should be connected to the power source directly.
Step 5: Install fixture as before.
Step 6: Adhere a label to the luminaire to the effect of “This luminaire has been modified and can no longer operate fluorescent lamps.” on the
retrofitted luminaire, where readily visible during relamping.
Step 7: Install the iBright™ LED tube into the fixture.
Step 8: Turn on the power.
www.atgelectronics.com
Toll free: 877-461-5333
Wiring Diagram for Electronic Ballast
Before
CUT
CUT
After
 Retrofit Luminaire with Magnetic Ballast
Installation Steps
Repeat Steps 1 to 7 of “retrofit luminaires with electronic ballast” excepting Step 3, changes in which are noted below:
Step 3: Cut the ballast output lead and cut the wirings of the starter. Both the ballast and starter need to remain in place. (For detailed
placement of the cuts, note the X’s on the wiring diagram labeled “Before” shown below.)
www.atgelectronics.com
Toll free: 877-461-5333
Wiring Diagram for Magnetic Ballast
Before
CUT
After
www.atgelectronics.com
Toll free: 877-461-5333
CUT