SLPOWER GLM110-12

GLC110 Commercial/GLM110 Medical
110 Watt Global Performance Switchers
GLOBAL PERFORMANCE SWITCHERS
FEATURES:
• Cost-effective power source
• Single- and dual-output units
• Low height (1.30”)
• 2-year warranty
• Power fail signal standard
• Commercial Approved to UL60950-1, EN60950-1,
CSA22.2 No. 950-95 3rd Ed.
• Medical Approved to UL2601-1, EN60601-1,
CSA-C22.2 No. 601.1
• Complies with EN61000-3-2 Class A
• RoHS Compliant Model Available (G suffix)
SPECIFICATIONS
Ac Input
90-264 Vac, 47-63 Hz single phase.
Input Current
Maximum input current at 90 Vac, 60 Hz with full rated output load not to
exceed 2.9 A.
Hold-up Time
20 ms minimum from loss of ac input at full load, nominal line (120 Vac).
Output Power
Normal continuous output power is 75 W for unrestricted natural convection,
or 110 W with 26 cfm air flow.
Output Regulation
Load regulation on dual output models is measured by ±40% load change
from 60% rated load and input voltage change from minimum to maximum
ratings.
Output #1 requires 1A minimum load for proper regulation of other outputs.
Initial set tolerance is measured with all outputs at 60% of full rated load.
Load regulation for single-output models measured by changing load from
5% to 50% load or 50% to full load in either direction.
Voltage Adjustment
Output #1 adjustment is ±5%. Note: output #1 must not be more than 1%
below nominal to achieve full output regulation on output #2. High voltage
settings may degrade the reliability of the unit due to excessive power
Transient Response
Main Output: 500 μs typical response time for return to within 0.5% of final value
for a 50% load step change, ∆i/∆t<0.2 A/μs. Maximum voltage deviation is 3.5%.
Startup/shutdown overshoot less than 3%. Turn-On Time less than 1 second at 120
Vac, 25.
Overvoltage Protection
Built in on main output.
Efficiency
72-85% depending on model.
Input Protection
Internal ac fuse provided on all units. Designed to blow only if a catastrophic
failure occurs in the unit.
Inrush Current
Inrush limited by internal thermistors. Inrush at 240 Vac, averaged over the first ac
half-cycle under cold start conditions will not exceed 37 A.
Temperature Coefficient
0.03%/°C typical on all outputs.
EMI/EMC Compliance
All models include built-in EMI filtering to meet the following emissions requirements:
dissipation in some outputs.
EMI SPECIFICATIONS
COMPLIANCE LEVEL
Overload Protection
Fully protected against short circuit and output overload. Short circuit protection is cycling type power limit. Factory set to begin power limiting at 120 W.
Conducted Emissions GLC110
Conducted Emissions GLM110
Static Discharge
RF Field Susceptibility
Fast Transients/Bursts
Surge Susceptibility
Line Frequency Harmonics
EN55022 Class B; FCC Class B
EN55011 Class B: FCC Class B
EN61000-4-2, 6 kV contact, 8 kV air
EN61000-4-3, 3 V/meter
EN61000-4-4, 2 kV, 5 kHz
EN61000-4-5, 1 kV diff., 2 kV com.
EN61000-3-2 Class A
Output Noise
0.5% rms, 1% pk-pk, 20 MHz bandwidth, differential mode. Measured with
noise probe directly across output terminals of the power supply.
POWER FAIL
Power fail signal is TTL or CMOS compatible (output goes low <0.5 V) 5 ms
before output voltage drops more than 4% below nominal voltage upon
loss of AC power. The signal is factory set to trip on 84 to 94 Vac brown-out
depending upon incoming line impedance and distortion. Other settings are
available to the user through adjustment of built in potentiometer (consult
factory for assistance). Output will stay low for 20 ms minimum.
Commercial Safety
All GLC models are approved to UL60950-1, CSA22.2 No. 950-95 3rd Ed, and
EN60950-1.
Medical Safety
All GLM models are approved to UL2601-1, CSA-C22.2 No. 601.1, EN60601-1.
All specifications are typical at nominal input, full load at 25OC unless otherwise stated
Commercial
Model
Medical
Model
GLC110-212
GLM110-212
GLC110-215
GLC110-524
GLM110-215
GLM110-524
RoHS
Suffix*
Output
No.
Output
Output
Minumum
Output
Normal (A)
Forced Air
(B)
Output Peak
Noise P-P
OVP
Total Regulation ( C )
G
1
+12 V
1A
6.3 A
9.1 A
9.5 A
100 mV
15.6 ± 1.1 V
2%
2
-12 V
0A
2.5 A
3A
4A
120 mV
1
+15 V
1A
5A
7.3 A
7.7 A
120 mV
2
-15 V
0A
2.5 A
3A
4A
150 mV
1
+24 V
1A
3.2 A
4.6 A
4.75 A
200 mV
28 ± 2.5 V
2%
2
+5 V
0A
1.5 A
2A
2.5 A
50 mV
6.2 ± 0.6 V
2%
G
G
2%
18.5 ± 1.5 V
2%
2%
GLC110-12
GLM110-12
G
1
12 V
0A
6.3 A
9.1 A
9.5 A
120 mV
15.6 ± 1.1 V
2%
GLC110-15
GLM110-15
G
1
15 V
0A
5A
7.3 A
7.7 A
150 mV
18.5 ± 1.5 V
2%
GLC110-24
GLM110-24
G
1
24 V
0A
3.2 A
4.6 A
5A
240 mV
28 ± 2.5 V
2%
* Add “G” suffix to part number for RoHS compliant model. Contact factory for availability.
A. Rating with unrestricted convection cooling. Total power not to exceed 75 W; no output can exceed rated current.
B. Rating with 26 cfm forced air cooling. Total power not to exceed 110 W.
C. To maintain regulation V1 current must be at least 1/5 of V2. V1 must not be adjusted more than 1% below nominal and have at least 10% of rated load.
GLC110/GLM110 MECHANICAL SPECIFICATIONS
ENVIRONMENTAL SPECIFICATIONS
OPERATING
NON-OPERATING
Temperature (A)
0 to 50°
-40 to +85°C
Humidity (A)
0 to 95% RH
0 to 95% RH
Shock (C)
20 gpk
40 gpk
Altitude
-500 to 10,000 ft
-500 to 40,000 ft
Vibration (B)
1.5 g rms’ 0.003 g /Hz
5 g rms’ 0.026 g2/Hz
2
A. Units should be allowed to warm up/operate under non-condensing
conditions before application of power. Derated output current and toal
output power by 2.5% per °C above 50°C.
B. Random vibration—10 to 2000Hz, 6dB/octave roll-off from 350 to
2000Hz, 3 orthogonal axes. Tested for 10 min./axis operating and 1
hr./axis non-operating.
C. Shock testing—half-sinusoidal, 10 ± 3 ms duration, ± direction, 3
orthogonal axes, total 6 shocks.