COOPER 16021-4

Power Distribution Blocks & Terminal Blocks with High
Short-Circuit Current Ratings
Table of Contents
Page
Selection Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Power Distribution Blocks
PDBFS Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-8
PDB Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-12
Terminal Blocks
16XXX Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-15
14002-3-UL, TB300-03SP-UL, NDN63-WH-UL,
NDN111-WH-UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-18
Application Notes . . . . . . . . . . . . . . . . . . . . . . . .19-23
TOOLS TO ASSIST
Panel Layout
2D and 3D CAD files for some products to facilitate panel
layouts found at www.cooperbussmann.com
Engineering Services for SCCR
OSCAR™ Compliance Software Eliminates the Guesswork in
Assembly Short-Circuit Current Rating (SCCR) Calculations.
The Cooper Bussmann innovative OSCAR™ Compliance
Software assists customer compliance with new Code and
standards requirements for short-circuit current ratings as they
relate to industrial control panels, equipment and assemblies.
Go to www.cooperbussmann.com
SCCR Panel Design Review for Improving Your Assembly
SCCR. If your SCCR needs improvement, contact the Cooper
Bussmann team for a design review. We guarantee our panel
SCCR review service for UL508A Supplement SB pre-certification.
Other Application Information on SCCR
Publications:
• Advanced Guide To Understanding Assembly Short-Circuit
Current Rating
• Simplified Guide To Understanding Short-Circuit Current
Rating – Find It, Fix It, Forget it
• SPD (Selecting Protective Devices) Sections on Industrial
Control Panels and also Conductor & Terminations.
1011
SB-BU09622
Technical Assistance
Application Engineering
Application Engineering assistance is available to
customers. The Application Engineering team is staffed by
engineers and available by phone with technical and
application support Monday – Friday, 8:00 a.m. – 5:00 p.m.
Central Time.
Application Engineering can be reached via phone, fax or
email:
• Phone: 636-527-1270
• Fax: 636-527-1607
• E-mail: [email protected]
Online Resources
Visit www.cooperbussmann.com for the following
resources:
• Arc-flash calculator
• OSCAR™ compliance software
• Training modules
Services
• Engineering
• Training
• Testing
Contact us for more information on Services:
• Phone: 636-207-3294
• E-mail: [email protected]
Page 1 of 23
Data Sheet 1049
Selection Table for SCCR Power Distribution Blocks and
Terminal Blocks
Short-Circuit Current Rated Power Distribution
Blocks
Cooper Bussmann offers three distinctly different styles of
short-circuit current rated power distribution blocks (PDBs)
and terminal blocks (TBs) to match different application
needs. The differences are whether the power
distribution blocks are enclosed or not, and whether they are
UL1953 Listed PDBs or UL1059 Recognized TBs, which have
different minimum spacing requirements. The table on this
page can assist in the selection of the right series for your
application requirements.
Why these are important?
Assembly short-circuit current ratings (SCCRs) are now
required in the 2005 NEC® and UL508A Listed Industrial
Control Panels. Marking the SCCR on Industrial Control
Panels (NEC® 409.110), Industrial Machinery Electrical
Panels (NEC® 670.3(A)), and HVAC equipment (NEC®
440.4(B)) is now required by the National Electrical Code.
PDBs or TBs not marked with a SCCR are typically one of
the weakest links and may limit an assembly to no more than
10kA SCCR. The PDBFS and PDB Series have increased
spacing required where used in feeder circuits in equipment
listed to UL508A (UL1059 TBs must be evaluated for proper
spacings). Also, for building wiring systems, the PDBFS
Series and PDB Series power distribution blocks can be used
to meet the new 2005 NEC® requirements in section
376.56(B) for PDBs in wireways.
More application info rmation on pages 19-23.
Selection Table
Product
Catalog
Page
Series PDBFS
3
Series PDB
9
Series
16XXX
13
NDN63-WH-UL,
NDN111-WH-UL,
14002-3-UL,
TB300-03SP-UL
UL
High
Enclosed SCCR*
UL 1059 Recognized
Terminal Blocks
HVAC
UL
1995
Wireways
NEC®
376.56(B)
(Requires
UL 1953)
Yes
Yes
Yes
Yes
Yes
Yes
No***
Yes
Yes
Yes
Yes
Yes
Yes
w/optional
cover
No***
Yes
No****
Yes
No****
Yes
No
No
Yes
No
Yes
No
Yes
No
UL 1059 Recognized
Terminal Blocks
16
Industrial
Control
Panels
UL 508A
Feeder
Circuit
Yes†
UL 1953 Listed
Power Distribution Blocks
UL 1953 Listed
Power Distribution Blocks
Spacing**
1” Air
2” Surface
Industrial
Control
Panels
UL 508A
Branch
Circuit
† IP-20 finger-safe under specific conditions, see datasheet page 8.
*When protected by proper fuse class with maximum ampere rating specified or smaller.
** See PDB Spacing Requirements for Equipment table below.
***Optional covers are available. Not IP-20, but provide a safety benefit.
****No, except: Yes, if single pole units installed with proper spacings.
PDB & TB Minimum Spacing
Requirements for Equipment
UL Standard
508A Feeder
Circuits
508A Branch
Circuits
1995 HVAC
Series PDB
1˝
2˝
1˝
3
1
1
⁄8˝
3⁄ ˝
8
⁄2˝
1⁄ ˝
2
⁄2˝
⁄2˝
1
Note: Refer to Specific UL standards for complete spacing details.
1011
SB-BU09622
Series PDBFS
Spacing between
Spacing between
live parts of
live parts and
opposite polarity
grounded parts
or enclosure
Through air Over surface
@600V
@600V
@600V
Magnum Terminal Blocks
Page 2 of 23
Data Sheet 1049
Series 162 and 163
Series PDBFS Enclosed Power Distribution Blocks
Feature/Benefits
• Enclosed for enhanced
safety; IP-20 finger-safe
under specific conditions,
see page 8
• High Short-Circuit Current
Ratings up to 200,000A:
PDBs do not have to be
a weak link in achieving a
high SCCR for an
industrial control panel
• Suitable for installation in
wireways and industrial
control panel feeder and branch circuits. Listed to UL1953
which has minimum spacing requirements at 600V of at least
1” through air and 2” over surface
• Small footprint saves panel space. Stack side by side and still
meet 1˝ and 2˝ spacing requirements
• For 2D and 3D CAD drawings visit www.cooperbussmann.com
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
• CSA Certified, Class 6228-01, File 15364
• CE component IEC 60947-7-1
• IEC 60529, IP-20 (Finger Safe) under specific conditions,
see page 8
Electrical
• 600Vac or dc (UL 1953), 690Vac or dc (IEC)
• Short-Circuit Current Ratings up to 200kA, see table below
• Ampacities up to 760 Amps
• 75ºC rated connectors
• CU Wire range 14 AWG to 500 kcmil or 2.5 to 240 mm2
Mechanical
• DIN rail or panel mount; PDBFS330 & PDBFS504 panel
mount only
• Captive termination screws; screws do not get misplaced
• Wire ready: captive termination screws shipped backed out
to save time on conductor installation
• Sliding DIN rail latch for easy mounting
• Single pole, gang mountable for multiple pole applications
with interlocking dovetail accessory (optional Part 2A1279)
One pin interlocks two units, two pins to interlock three units
(see illustration on page 6)
• Flammability, UL 94V0
• Tin-plated AL connectors suitable for CU conductors
• Elongated hole for panel mounting; easier mounting with
greater flexibility in matching up with drilled panel holes
• DIN rail end anchors required to prevent damage to block
when torquing, anchors not offered by Cooper Bussmann
Series PDBFS
Electrical
Terminal Copper Conductor Capability
Line
Load
Configuration
Catalog
Number
(All Single
Pole)
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp**
Openings per Pole
Amps
Wire Range
Wire Range
Line
Load
Line
Load
J
T
RK1
RK5
AWG or
kcmil
AWG or
kcmil
LPJ
JJS
JJN
LPS-RK
LPN-RK
FRS-R
FRN-R
2/0 to 8 200
200
100
60
200kA
4 to 12
200
175
200
200
175
200
100
100
100
60
30
60
200kA
100kA
50kA
350 to 6 400
400
200
100
200kA
400
200
175
600
400
200
400
200
175
600
400
200
200
100
100
400
200
100
100
60
30
200
100
60
200kA
50kA
100kA
200kA
100kA
50kA
350 to 4 600
600
400
200
200kA
600
800*
600
200
200kA
500 to 6 600
600
400
200
100kA
PDBFS204
175A
2/0 to 8 AWG
70 to 10 mm2
2/0 to 8 AWG
70 to 10 mm2
2/0 to 8
PDBFS220
175A
2/0 to 8 AWG
70 to 10 mm2
4 to 14 AWG
25 to 2.5 mm2
2/0 to 8
PDBFS303
310A
350kcmil to 6 AWG 350kcmil to 6 AWG
150 to 16 mm2
150 to 16 mm2
350 to 6
PDBFS330
380A
500kcmil to 6 AWG
240 to 16 mm2
2 to 14 AWG
35 to 2.5 mm2
500 to 6
PDBFS377
570A
300kcmil to 4 AWG
150 to 12 mm2
4 to 14 AWG
25 to 2.5 mm2
PDBFS500
620A
350kcmil to 4 AWG 350kcmil to 4 AWG
185 to 12 mm2
185 to 12 mm2
PDBFS504
760A 500kcmil to 6 AWG 500kcmil to 6 AWG
240 to 16 mm2
240 to 16 mm2
4 to 14
2 to 6
300
300 to 4
350 to 4
500
500 to 6
2 to 14
4 to 8
4
4 to 14
500
Ampacities 75C per NEC® Table 310.16 and UL508A Table 28.1
*Class L 800A (KRP-C 800_SP) or less fuses suitable for this particular SCCR case.
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all SCCRs in this table.
1011
SB-BU09622
Page 3 of 23
Data Sheet 1049
SCCR
Series PDBFS Enclosed Power Distribution Blocks
Item
1
2
3
4
5
6
7
Part No.
PDBFS204
PDBFS220
PDBFS303
PDBFS330
PDBFS377
PDBFS520
PDBFS504
Width
A
1.030[26.16]
1.030[26.16]
1.550[39.37]
1.550[39.37]
1.875[47.62]
2.380[60.45]
2.560[65.02]
Length
B
3.372[94.80]
3.372[94.80]
4.665[118.50]
4.665[118.50]
4.665[118.50]
4.665[118.50]
4.665[118.50]
Dimensions in[mm]
Height
C
D
2.146[54.50] 3.550[90.17]
2.146[54.50] 3.550[90.17]
2.874[73.00] 4.475[113.67]
2.950[74.93] 4.475[113.67]
2.933[74.50] 4.475[113.67]
2.598[66.00] 4.475[113.67]
3.150[80.00] 4.475[113.67]
E
2.905[73.79]
2.905[73.79]
3.810[96.77]
3.810[96.77]
3.810[96.77]
3.810[96.77]
3.810[96.77]
PDBFS204
F
0.197[5.00]
0.197[5.00]
0.197[5.00]
0.197[5.00]
0.197[5.00]
0.197[5.00]
0.197[5.00]
G
H
0.197[5.00]
N/A
0.197[5.00]
N/A
0.236[6.00]
N/A
0.236[6.00]
N/A
0.236[6.00]
N/A
0.236[6.00]
N/A
0.236[6.00] 46.00[1.811]
PDBFS220
C
PDBFS303
1011
SB-BU09622
PDBFS330
Page 4 of 23
Data Sheet 1049
Series PDBFS Enclosed Power Distribution Blocks
PDBFS377
PDBFS500
PDBFS504
1011
SB-BU09622
Page 5 of 23
Data Sheet 1049
Series PDBFS Enclosed Power Distribution Blocks
Panel Mounting
Capable on all part numbers
Use 2 screws for mounting
each pole (#10 or M5 screw)
(4 screws for PDBFS504)
OR
Hook load side onto
35mm DIN RAIL
Open the latch using
screwdriver
Close the latch
DIN Rail anchors are required on each
side of block or blocks.
Anchors must be used to prevent
damage to the plastic housing when
tightening terminals.
DIN Rail Mounting
PDBFS204, PDBFS220, PDBFS303,
PDBFS377, and PDBFS500 only.
Rotate PDB down
For interlocking two or more blocks on a DIN
Rail, insert male dove tail part number 2A1279
into the female dove tail opening.
Fully insert male dove tail to
interlock blocks.
2A1279 accessory ordered separately.
1011
SB-BU09622
Page 6 of 23
Data Sheet 1049
Series PDBFS Enclosed Power Distribution Blocks
Series PDBFS
Line
Part Number
PDBFS204
CU Wire Range
2/0 to 8 AWG
70 to 10mm2
Load
Torque
Trim Length
Lb-in (Nm)
in (mm)
110 (12.4)
0.850 (21.6)
Hex Key
3/16˝
CU Wire Range
2/0 to 8 AWG
70 to 10mm2
4 to 6 AWG
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.750 (19.0)
8 AWG
3/16˝
150 to 16mm2
275 (31.1)
1.350 (34.3)
5/16˝
350 Kcmil to 6 AWG
150 to 16mm2
2 to 3 AWG
4 to 6 AWG
500 Kcmil to 6 AWG
500 (56.5)
1.250 (31.8)
3/8˝
8 AWG
10 to 14 AWG
4 to 6 AWG
275 (31.1)
1.15 (29.2) top row
1.400 (35.6) bottom row
8 AWG
1/4˝
20 (2.3)
6 to 2.5mm2
PDBFS504
350 Kcmil to 4 AWG
185 to 25mm2
500 Kcmil to 6 AWG
240 to 16mm2
275 (31.1)
1.250 (31.8)
5/16˝
500 (56.5)
1.250 (31.8)
3/8˝
1.250 (31.8)
5/16˝
0.590 (15.0) top row
1/8˝
1.200 (30.5) bottom row
0.550 (14.0) top row,
25 (2.8)
10mm2
10 to 14 AWG
PDBFS500
350 Kcmil to 4 AWG
185 to 25mm2
500 Kcmil to 6 AWG
240 to 16mm2
1.00 (25.4) middle row
Wire Connector Hole Diameter
275 (31.1)
1.250 (31.8)
5/16˝
500 (56.5)
1.250 (31.8)
3/8˝
1011
SB-BU09622
Part No.
Minimum Enclosure
in (mm)
PDBFS204
16˝ X 16˝ X 6.75˝
0.450 (11.5)
0.450 (11.5)
PDBFS220
16˝ X 16˝ X 6.75˝
0.450 (11.5)
0.246 (6.25)
PDBFS303
36˝ X 30˝ X 12.625˝
PDBFS303
0.720 (18.3)
0.720 (18.3)
PDBFS330
24˝ X 20˝ X 6.75˝
PDBFS330
0.870 (22.1)
0.314 (8.0)
PDBFS377
24˝ X 20˝ X 6.75˝
PDBFS377
0.687 (17.5)
0.265 (6.7)
PDBFS500
36˝ X 30˝ X 12.625˝
PDBFS500
0.718 (18.2)
0.718 (18.2)
PDBFS504
36˝ X 30˝ X 12.625˝
PDBFS504
0.875 (22.2)
0.875 (22.2)
Line
Load
Number
in (mm)
PDBFS204
PDBFS220
Size
Page 7 of 23
1/8˝
1.220 (31.0) bottom row
Trim
Part
1/8˝
35 (4.0)
25 to 16mm2
150 to 25mm2
3/16˝
35 (4.0)
6 to 2.5mm2
300 Kcmil to 4 AWG
275 (31.1)
40 (4.5)
10mm2
PDBFS377
0.550 (14.0) top row,
0.850 (21.6) bottom row
45 (5.1)
25 to 16mm2
240 to 16mm2
0.970 (24.6)
50 (5.7)
35mm2
PDBFS330
110 (12.4)
Hex Key
20 (2.3)
6 to 2.5mm2
350 Kcmil to 6 AWG
in (mm)
25 (2.8)
10mm2
10 to 14 AWG
PDBFS303
Trim Length
Lb-in (Nm)
35 (4.0)
25 to 16mm2
PDBFS220
Torque
Data Sheet 1049
Series PDBFS Enclosed Power Distribution Blocks
Specific Conditions to Achieve IP-20 Finger-Safe Status for Series PDBFS
Line
Part
Number
Trim Length
in (mm)
PDBFS204
0.850 (21.6)
PDBFS220
PDBFS303
PDBFS330
0.750 (19.0)
1.350 (34.3)
1.250 (31.8)
1.15 (29.2) top row,
PDBFS377 1.400 (35.6) bottom
row
Installed Wire
2/0 to 8 AWG
70 to 10mm2
2/0 to 8 AWG
70 to 10mm2
350 Kcmil to 2/0 AWG
150 to 70mm2
1/0 to 6 AWG
50 to 16mm2
500 to 250 Kcmil
240 to 150mm2
4/0 to 6 AWG
120 to 16mm2
300 Kcmil to 4/0 AWG
150 to 120mm2
3/0 to 4 AWG
95 to 25mm2
screws fully
opened
no wire in hole
PDBFS500
PDBFS504
1011
SB-BU09622
1.250 (31.8)
1.250 (31.8)
350 Kcmil to 2/0 AWG
185 to 70mm2
1/0 to 4 AWG
50 to 25mm2
screws fully
opened
no wire in hole
500 to 350 Kcmil
240 to 185mm2
300 Kcmil to 6 AWG
150 to 16mm2
screws fully
opened
no wire in hole
Load
IP-20
Conductor Screw
Openings Opening
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
N/A
No
No
N/A
Yes
Yes
No
Yes
N/A
No
No
N/A
Yes
Yes
No
Yes
N/A
No
No
N/A
Trim Length
in (mm)
0.970 (24.6)
0.550 (14.0)
top row,
0.850 (21.6)
bottom row
1.250 (31.8)
0.590 (15.0)
top row,
1.200 (30.5)
bottom row
0.550 (14.0)
top row,
1.00 (25.4)
middle row,
1.220 (31.0)
bottom row
1.250 (31.8)
1.250 (31.8)
Page 8 of 23
Installed Wire
2/0 to 8 AWG
70 to 10mm2
4 to 14 AWG
25 to 2.5mm2
screws fully
opened
no wire in hole
350 Kcmil to 2/0 AWG
150 to 70mm2
1/0 to 6 AWG
50 to16mm2
2 to 14 AWG
35 to 2.5mm2
screws fully
opened
IP-20
Conductor Screw
Openings Opening
Yes
Yes
Yes
Yes
N/A
Yes
No
N/A
Yes
Yes
No
Yes
Yes
Yes
N/A
Yes
no wire in hole
No
N/A
4 to 14 AWG
25 to 2.5mm2
Yes
Yes
screws fully
opened
N/A
Yes
no wire in hole
Yes
N/A
Yes
Yes
No
Yes
N/A
No
No
N/A
Yes
Yes
No
Yes
N/A
No
No
N/A
350 Kcmil to 2/0 AWG
185 to 70mm2
1/0 to 4 AWG
50 to 25mm2
screws fully
opened
no wire in hole
500 to 350 Kcmil
240 to 185mm2
300 Kcmil to 6 AWG
150 to 16mm2
screws fully
opened
no wire in hole
Data Sheet 1049
Series PDB Power Distribution Blocks
Agency/Standards
• UL Listed 1953, Guide QPQS, File E256146
Electrical
• 600Vac or dc (UL 1953)
• Short-Circuit Current Ratings up to 200kA, see table
• 75ºC rated connectors, ampacities up to 310A
• Wire range 14 AWG to 350 kcmil CU
• Spacing between uninsulated opposite polarities or ground
meets UL 1953 which requires at least 1” through air and
2” over surface for 301 to 600V
Feature/Benefits
• High Short-Circuit Current Ratings up to 200kA
PDBs do not have to be a weak link in achieving high
SCCR for an industrial control panel
• Suitable for installation in wireways (with optional covers)
and industrial control panel feeder and branch circuits.
Listed to UL1953 which has minimum spacing
requirements at 600V of at least 1” through air and 2”
Mechanical
• Panel mount
• Flammability, UL 94V0
• Tin-plated AL connectors suitable for CU conductors
Series PDB
Terminal Copper Conductor Capability
Line
Load
Configuration
Part
Number
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp**
Openings per Pole
Amps
Wire Range
Wire Range
Line
Load
Line
Load
J
T
RK1
RK5
AWG or
kcmil
AWG or
kcmil
LPJ
JJS
JJN
LPS-RK
LPN-RK
FRS-R
FRN-R
2/0 to 8 200
200
200
60
200kA
4 to 12
200
200
200
60
200kA
4 to 14
175
175
100
60
100kA
Stud
200
200
100
60
200kA
4 to 12
400
400
200
100
200kA
4 to 12
175
175
100
60
100kA
4 to 8
400
400
200
100
200kA
4 to 12
175
175
100
60
100kA
4 to 8
400
400
200
100
200kA
4 to 14
175
175
100
60
100kA
1/0 to 6 400
400
200
100
200kA
1/0 to 12 175
175
100
60
100kA
PDB204-1
PDB204-3
175A
2/0 to 8 AWG
2/0 to 8 AWG
2/0 to 8
PDB220-1
PDB220-3
175A
2/0 to 8 AWG
4 to 14 AWG
2/0 to 8
PDB280-1
PDB280-3
175A
2/0 to 8 AWG
1/4-20 X 3/4 STUD
2/0 to 8
PDB321-1
PDB321-2
PDB321-3
175A
2/0 to 8 AWG
4 to 14 AWG
2/0 to 8
PDB323-1
PDB323-3
310A 350kcmil to 4 AWG
PDB370-1
PDB370-3
310A 350kcmil to 4 AWG
4 to 14 AWG
350 to 4
PDB371-1
PDB371-3
310A 350kcmil to 4 AWG
(6) 2 to 12 AWG
(3) 1/0 to 12
350 to 4
4 to 12 AWG
350 to 4
Ampacities 75C per NEC® Table 310.16 and UL508A Table 28.1
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all SCCR in this table.
These blocks available in 1 or 3 poles. PDB321 available in 1, 2, and 3 poles.
Part Number:
Example: PDB204-1 = single pole
PDB204-3 = three pole
1011
SB-BU09622
Page 9 of 23
Data Sheet 1049
SCCR
Series PDB Power Distribution Blocks
Part Numbers
PDB204-3, PDB220-3, PDB280-3
PDB323-3, PDB370-3, PDB371-3
PDB323-1, PDB370-1, PDB371-1
PDB204-1, PDB220-1, PDB280-1
PDB321-1
PDB321-2
PDB321-3
Width
A
4.27 [108.3]
6.00 [152.4]
1.96 [49.8]
1.07 [27.2]
1.96 [49.8]
3.58 [90.9]
5.20 [132.1]
Length
B
2.88 [73.2]
5.50 [139.7]
3.38 [85.7]
2.88 [73.2]
4.00 [101.6]
4.00 [101.6]
4.00 [101.6]
Top
Dimensions in [mm]
Height
C
D
2.13 [54.0]
1.62 [41.1]
3.70 [93.9]
3.25 [82.6]
3.32 [85.7]
—
1.75 [44.5]
3.32 [84.3]
1.62 [41.1]
3.32 [84.3]
1.62 [41.1]
3.32 [84.3]
1.62 [41.1]
E
2.25 [57.2]
4.75 [120.7]
2.25 [57.2]
3.37 [85.6]
3.37 [85.6]
3.37 [85.6]
F (Hole)
0.22 [5.7]
0.22 [5.7]
0.21 [2.5] X 0.41 [10.4]
0.20 [5.1]
0.21 [5.3] X 0.41 [10.4]
0.21 [5.3] X 0.41 [10.4]
0.21 [5.3] X 0.41 [10.4]
Top
Side
Side
PDB204-3, PDB220-3, PDB280-3
PDB323-1,
PDB370-1,
PDB371-1
Top
PDB323-3, PDB370-3, PDB371-3
Side
Side
F
PDB204-1,
PDB220-1,
PDB280-1
C
PDB321-1, PDB321-2, PDB321-3
1011
SB-BU09622
Page 10 of 23
Data Sheet 1049
Series PDB Power Distribution Blocks
Optional covers
Covers are ordered for each individual pole, i.e. three
1-pole covers for 3-pole block, see table A.
Except PDB321 blocks have one cover for 1, 2 or 3 pole
versions, see table B. (Shipped with mounting screws)
Table A
Table B
Block
Cover
Block
Cover
PDB2XX-(pole): CPB162-1
PDB321-1
CPDB-1
PDB3XX-(pole): CPDB-1
PDB321-2
CPDB-2
PDB321-3
CPDB-3
Series 163 Cover
Series 162 Cover
Supplied with (4) #4 thread-cutting
screws assembled as shown
4.14"
Textured surface for marking
CPDB-1 (single pole)
CPDB-2 (two pole)
CPDB-3 (three pole)
2.10"
3.72"
5.34"
Part No.
Minimum Enclosure
PDB204-1, -3
16˝ X 16˝ X 6.75˝
PDB220-1, -3
16˝ X 16˝ X 6.75˝
PDB280-1, -3
16˝ X 16˝ X 6.75˝
Flat Cover
Part Number
˝A˝ Dimension
CPB162-1
0.94˝
CPB162-2
1.75˝
CPB162-3
2.56˝
Size
PDB321-1, -2, -3
24˝ X 20˝ X 6.75˝
PDB323-1, -3
24˝ X 20˝ X 6.75˝
PDB370-1, -3
24˝ X 20˝ X 6.75˝
PDB371-1, -3
24˝ X 20˝ X 6.75˝
1011
SB-BU09622
Page 11 of 23
Data Sheet 1049
Series PDB Power Distribution Blocks
Line
Part Number
CU Wire Range
PDB204-1, -3
2/0 to 8 AWG
70 to 10mm2
Load
Torque
Trim Length
Lb-in (Nm)
in (mm)
110 (12.4)
0.700 (17.8)
Hex Key CU Wire Range
3/16˝
2/0 to 8 AWG
70 to 10mm2
4 to 6 AWG
25 to 16mm2
PDB220-1, -3
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.670 (17.0)
3/16˝
8 AWG
10mm2
10 to 14 AWG
6 to 2.5mm2
PDB280-1, -3
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.670 (17.0)
3/16˝
N/A
25 to 16mm2
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.700 (17.8)
3/16˝
8 AWG
10mm2
10 to 14 AWG
6 to 2.5mm2
4 to 6 AWG
25 to 16mm2
PDB323-1, -3
350 Kcmil to 4 AWG
185 to 25mm2
275 (31.1)
0.900 (22.9)
5/16˝
8 AWG
10mm2
10 to 12 AWG
6 to 4mm2
4 to 6 AWG
25 to 16mm2
PDB370-1, -3
350 Kcmil to 4 AWG
185 to 25mm
2
275 (31.1)
0.900 (22.9)
5/16˝
8 AWG
10mm
2
10 to 14 AWG
6 to 2.5mm2
2 to 3 AWG
35mm2
4 to 6 AWG
PDB371-1, -3
350 Kcmil to 4 AWG
185 to 25mm
275 (31.1)
0.900 (22.9)
5/16˝
2
Trim Length
Hex Key,
Lb-in (Nm)
in (mm)
Slot, Stud
110 (12.4)
0.700 (17.8)
3/16˝ Hex
35 (4.0)
25 (2.8)
0.470 (11.9) top row,
0.780 (19.8) bottom row
25 to 16mm2
8 AWG
10mm2
10 to 12 AWG
6 to 4mm2
N/A
PDB220-1, -3
1011
SB-BU09622
Top Row
Bottom Row
Bottom Row
25 (2.8)
0.480 (12.2) top row,
0.800 (20.3) bottom row
Slot
35 (4.0)
25 (2.8)
1.00 (25.4) top row,
0.450 (11.43) bottom row
Slot
20 (2.3)
35 (4.0)
0.450 (11.4) top row
25 (2.8)
0.630 (16.0) middle row,
Slot
0.920 (23.4) bottom row
20 (2.3)
50 (5.7)
45 (5.1)
40 (4.5)
0.450 (11.4) top row
Slot top row
0.630 (16.0) middle row,
Slot middle row,
0.920 (23.4) bottom row
3/16˝ Hex
bottom row
35 (4.0)
Bottom Row
PDB370-1, -3
PDB371-1, -3
Page 12 of 23
Stud
20 (2.3)
Middle Row
PDB321-1, -2, -3
PDB323-1, -3
1/4 - 20
35 (4.0)
Top Row
Top Row
Slot
20 (2.3)
50 (5.7)
4 to 6 AWG
PDB321-1, -2, -3
Torque
Data Sheet 1049
Trim
Series 16XXX Terminal Blocks
Feature/Benefits
• High Short-Circuit Current Ratings up to 200kA
• UL1059 Recognition
Mechanical
• Panel mount
• Flammability, UL 94V0
• Tin-plated AL connectors suitable for CU
conductors
Agency/Standards
• UL 1059 Recognized, Guide XCFR2, File E221592
• General Industry Class per UL 1059, usage catagory C
• CSA Certified, Class 6228-01, File 15364
Electrical
• 600Vac or dc
• Short Circuit Current Ratings up to 200kA, see table
• Ampacities up to 310 Amps
• 75ºC rated connectors
• Wire range 14 AWG to 350 kcmil CU
Series 162 and 163
Series 16XXX
Terminal Copper Conductor Capability
Line
Load
Configuration
Part
Number
Openings per Pole
Amps
Wire Range
Wire Range
Line
16204-1,
-2,-2,
-3 -3
Short-Circuit Current Rating Data
Conductors
Max Fuse Class & Amp**
Load
Line
Load
J
T
RK1
RK5
AWG or
kcmil
AWG or
kcmil
LPJ
JJS
JJN
LPS-RK
LPN-RK
FRS-R
FRN-R
2/0 to 8 200
200
200
60
200kA
4 to 12
200
200
200
60
200kA
4 to 14
175
175
100
60
100kA
Stud
200
200
100
60
200kA
4 to12
400
400
200
100
200kA
4 to 12
175
175
100
60
100kA
4 to 8
400
400
200
100
200kA
4 to 12
175
175
100
60
100kA
4 to 8
400
400
200
100
200kA
4 to 14
175
175
100
60
100kA
1/0 to 6 400
400
200
100
200kA
1/0 to 12 175
175
100
60
100kA
175A
2/0 to 8 AWG
2/0 to 8 AWG
2/0 to 8
175A
2/0 to 8 AWG
4 to 14 AWG
2/0 to 8
16280-1,
-2, -3
175A
2/0 to 8 AWG
1/4-20 X 3/4 STUD
2/0 to 8
16321-1,
-2, -3
175A
2/0 to 8 AWG
4 to 14 AWG
2/0 to 8
16220-1,
-2, -3
16323-1,
-2, -3
310A 350kcmil to 4 AWG
16370-1,
-2,-2,
-3 -3
310A 350kcmil to 4 AWG
4 to 14 AWG
350 to 4
16371-1,
-2, -3
310A 350kcmil to 4 AWG
(6) 2 to 12 AWG
(3) 1/0 to 12
350 to 4
4 to 12 AWG
350 to 4
Ampacities 75C per NEC® Table 310.16 and UL508A Table 28.1
** Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30)
or less are suitable for all the SCCRs in this table.
These blocks available in 1, 2, or 3 poles
Part Number:
Example: 16204-1 = single pole
16204-3 = three pole
1011
SB-BU09622
Part No.
Minimum Enclosure
16204-1, -2, -3
16˝ X 16˝ X 6.75˝
16220-1, -2, -3
16˝ X 16˝ X 6.75˝
16280-1, -2, -3
16˝ X 16˝ X 6.75˝
16321-1, -2, -3
24˝ X 20˝ X 6.75˝
16323-1, -2, -3
24˝ X 20˝ X 6.75˝
16370-1, -2, -3
24˝ X 20˝ X 6.75˝
16371-1, -2, -3
24˝ X 20˝ X 6.75˝
Size
Page 13 of 23
Data Sheet 1049
SCCR
Series 16XXX Terminal Blocks
Series 16XXX-X
Line
Part Number
CU Wire Range
16204-1, -2, -3
2/0 to 8 AWG
70 to 10mm2
Load
Torque
Trim Length
Lb-in (Nm)
in (mm)
110 (12.4)
0.700 (17.8)
Hex Key CU Wire Range
3/16˝
2/0 to 8 AWG
70 to 10mm2
4 to 6 AWG
25 to 16mm2
16220-1, -2, -3
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.670 (17.0)
3/16˝
8 AWG
10mm2
10 to 14 AWG
6 to 2.5mm2
16280-1, -2, -3
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.670 (17.0)
3/16˝
N/A
4 to 6 AWG
25 to 16mm2
16321-1, -2, -3
2/0 to 8 AWG
70 to 10mm2
120 (13.6)
0.700 (17.8)
3/16˝
8 AWG
10mm2
10 to 14 AWG
6 to 2.5mm2
4 to 6 AWG
25 to 16mm2
16323-1, -2, -3
350 Kcmil to 4 AWG
185 to 25mm2
275 (31.1)
0.900 (22.9)
5/16˝
8 AWG
10mm2
10 to 12 AWG
6 to 4mm2
4 to 6 AWG
25 to 16mm2
16370-1, -2, -3
350 Kcmil to 4 AWG
185 to 25mm2
275 (31.1)
0.900 (22.9)
5/16˝
8 AWG
10mm2
10 to 14 AWG
6 to 2.5mm2
2 to 3 AWG
35mm2
4 to 6 AWG
16371-1, -2, -3
350 Kcmil to 4 AWG
275 (31.1)
0.900 (22.9)
5/16˝
185 to 25mm2
25 to 16mm2
8 AWG
10mm2
10 to 12 AWG
6 to 4mm2
Torque
Trim Length
Hex Key,
Lb-in (Nm)
in (mm)
Slot, Stud
110 (12.4)
0.700 (17.8)
3/16˝ Hex
35 (4.0)
25 (2.8)
0.470 (11.9) top row,
0.780 (19.8) bottom row
Slot
20 (2.3)
50 (5.7)
N/A
1/4 - 20
Stud
35 (4.0)
25 (2.8)
0.480 (12.2) top row,
0.800 (20.3) bottom row
Slot
20 (2.3)
35 (4.0)
25 (2.8)
1.00 (25.4) top row,
0.450 (11.43) bottom row
Slot
20 (2.3)
35 (4.0)
0.450 (11.4) top row
25 (2.8)
0.630 (16.0) middle row,
Slot
0.920 (23.4) bottom row
20 (2.3)
50 (5.7)
45 (5.1)
0.450 (11.4) top row
0.630 (16.0) middle row,
40 (4.5)
0.920 (23.4) bottom row
Slot top row
Slot middle row,
3/16˝ Hex
bottom row
35. (4.0)
Trim
Top Row
16220-1, -2, -3
1011
SB-BU09622
Top Row
Top Row
Bottom Row
Bottom Row
Middle Row
16321-1, -2, -3
16323-1, -2, -3
Bottom Row
16370-1, -2, -3
16371-1, -2, -3
Page 14 of 23
Data Sheet 1049
Series 16XXX Terminal Blocks
Dimensions for Series 162 & 163 (Inches)
Width
Length Height
Part No. A1
A2
A3
B
C
162
1.06 1.88 2.60
2.85
1.75
163
1.96 3.58 5.20
4.0
3.32
D
0.81
1.62
Series 162
(Available 1, 2, and 3 pole)
E
2.25
3.37
F
0.53
—
G
0.31
—
H
0.84
—
J
K
L
0.31
0.20
0.42
—
Slot 0.20˝ wide x 0.41˝ long Slot 0.42˝ wide x 0.62˝ long
Series 163
(Available 1, 2, and 3 pole)
H J
LINE
SIDE
C
Side
A
F
D
D
B E
F
C
K Dia.
G
L C'Bore
LOAD
SIDE
Optional covers
Block
Cover
Series 162:
CPD162-(pole)*
Series 163:
CPDB-(pole)*
*Provided with mounting screws
Series 163 Cover
Series 162 Cover
Supplied with (4) #4 thread-cutting
screws assembled as shown
4.14"
Textured surface for marking
CPDB-1 (single pole)
CPDB-2 (two pole)
CPDB-3 (three pole)
2.10"
3.72"
5.34"
Flat Cover
1011
SB-BU09622
Page 15 of 23
Data Sheet 1049
Part Number
˝A˝ Dimension
CPB162-1
0.94˝
CPB162-2
1.75˝
CPB162-3
2.56˝
Terminal Blocks With High Short-Circuit Current Ratings
Part Number
Amps
14002-3-UL
115
TB300-03SP-UL
NDN63-WH-UL
NDN111-WH-UL
30
65
90
Short-Circuit Current Rating Data
Max. Fuse Class and Amp**
J
T
RK1
RK5
SCCR
JJS
LPS-RK
FRS-R
LPJ
JJN
LPN-RK
FRN-R
CU Wire
Range
Line & Load
Torque
lb-in
MAX.
(1) CU Wire
Range
AWG
Minimum
Enclosure
Size
2 to 3 AWG
4 to 6 AWG
8 AWG
10 to 14 AWG
10 to 18 AWG
6 to 18 AWG
2 to 18 AWG
50
45
35
35
16
35
32
2 to 8
200
200
100
60
200kA
2 to 14
175
175
100
60
100kA
8˝ x 8˝ x 4˝
10 to 18
6 to 18
2 to 18
60
100
200
60
100
200
60
60
200
—
30
60
100kA
100kA
100kA
8˝ x 8˝ x 4˝
8˝ x 8˝ x 4˝
8˝ x 8˝ x 4˝
**Class G 60A (SC-60) or less or Class CC 30A (LP-CC-30, FNQ-R-30, KTK-R-30) or less are suitable for all SCCRs in this table
14002-3-UL
Barrier Terminal Block
Agency/Standards
• UL 1059 Recognized, Guide XCFR2, File E62622
• General Industry Class per UL 1059, usage category C
Electrical
• 600Vac or dc
• Short-Circuit Current Rating up to 200kA, See table
• 75ºC rated connectors, 115A ampacity
• Wire range 2 to 4 AWG CU
2.375
(60.32)
0.875
(22.23)
0.375
(9.52)
0.750
(19.05)
Mechanical
• Panel mount
• 3 pole configuration
• Flammability, UL94 HB
0.625
(15.88)
1.250
(31.75)
1011
SB-BU09622
Page 16 of 23
Data Sheet 1049
Terminal Blocks With High Short-Circuit Current Ratings
NDN63-WH-UL
Agency/Standards
• UL 1059 Recognized, Guide XCFR2, File E62622
• General Industry Class per UL 1059, usage category C
Electrical
• 600Vac or dc
• Short-Circuit Current Rating up to 100kA, See table page 16
• 65A ampacity
• Wire range 6 to 18 AWG CU
Mechanical
• 35mm DIN rail and C-rail mount
• .375˝ (9.52) pole to pole spacing
• 3 pole configuration
• Marking tape MT12-1⁄2
• Flammability, UL94 V2
1.50
(38.10)
1.67
(42.41)
1.45
(36.83)
1.17
(29.71)
TB300-03SP-UL
Double Row Terminal Block
Agency/Standards
• UL 1059 Recognized, Guide XCFR2, File E62622
• General Industry Class per UL 1059, usage category C
Electrical
• 600Vac or dc
• Short-Circuit Current Rating up to 100kA, See table page 16
• 30A ampacity
• Wire range 10 to 18 AWG CU
Mechanical
• Panel mount
• .562˝ (14.28) pole to pole spacing
• 3 pole configuration
• Flammability, UL94 V0
8-32 binding head screw - TB 300
2.25
(57.15)
.22
(5.6)
2.69
(68.32)
.90
1.33
(22.8) (33.8)
.50 (12.7)
.56
(14.2)
.21dia.
(5.3)
.412
(10.4)
.81
(20.5)
.33 (8.4)
1011
SB-BU09622
Page 17 of 23
.21 x .25 slots
(5.3 x 6.3)
.56
(14.2)
Data Sheet 1049
Terminal Blocks With High Short-Circuit Current Ratings
NDN111-WH-UL
Agency/Standards
• UL 1059 Recognized, Guide XCFR2, File E62622
• General Industry Class per UL 1059, usage category C
Electrical
• 600Vac or dc
• Short-Circuit Current Rating up to 100kA, See table page 16
• 90A ampacity
• Wire range 2 to 18 AWG CU
Mechanical
• Panel mount
• 35mm DIN rail and C-rail mount
• .635˝ (16.13mm) pole to pole spacing
• 3 pole configuration
• Marking tape MT12-1⁄2
• Flammability, UL94 V2
Mtg. holes
.18 (4.57) dia.
.28 (7.11) c'bores
1.46
(37.13)
1.71
(43.48)
Dovetail
Option
.62
(15.75)
1.87
(47.50)
1.44
(36.57)
1011
SB-BU09622
Page 18 of 23
Data Sheet 1049
Application Notes
Proper Application
When applying Power Distribution Blocks (PDBs) and
terminal blocks, there are several requirements that must be
satisfied, based upon various UL Standards, the NEC®, and
the specific application. Some of the requirements and ratings
include: voltage, continuous current, wire range (load and line
side), conductor terminal temperature rating, short-circuit
current rating or withstand rating (SCCR), type and amp
rating of upstream overcurrent protective device (fuse or
circuit breaker) and spacing (between uninsulated live part
and uninsulated grounded part or uninsulated live parts of
opposite polarity). The requirements vary, based on the
application for industrial control panels (feeder circuit or
branch circuit), field applications, or HVAC applications.
New requirements in the 2005 NEC® for a marked shortcircuit current rating (SCCR) on industrial control panels
(NEC® 409.110), industrial machinery (NEC® 670.3A), and
commercial/industrial HVAC equipment (NEC® 440.4(B)) have
resulted in considerable attention being placed upon the
proper selection and application of power distribution blocks
and terminal blocks. In addition, UL508A Industrial Control
Panels has a requirement that the assembly be marked with
its short-circuit current rating. Per UL508A, each power
circuit component in the panel, such as a PDB, has a SCCR
expressed in amperes or kiloamperes and voltage. The
SCCR shall be established by either being marked on the
product, the instruction sheet provided with it, or from
UL508A Supplement SB Table SB4.1. If an assembly shortcircuit current rating above 10,000 amperes is desired, a
power distribution block or a terminal block with a high
short-circuit current rating must normally be utilized.
The following material includes some application notes on
power distribution block and terminal block SCCR, UL Listed
1953 vs UL Recognized 1059, spacing requirements,
conductor ampacities, conductor termination ratings affecting
conductor ratings, and SCCR for multi-lug switches and
circuit breakers.
there is adequate spacing for the OEM application in which
they are being applied. Power distribution blocks are
evaluated to UL1953, the power distribution block outline of
investigation and are listed for general installation, which
means they have adequate spacing for most OEM and field
applications. These power distribution blocks are marked with
a listing mark, which means that the inspector does not need
to check ”conditions of acceptability” as is needed with
recognized products. As listed products, PDBs evaluated to
UL1953 are suitable for use in the field. For example, an
electrical contractor may install them in a metal wireway,
something that may not be done with a recognized product
such as a terminal block.
Marking Equipment with SCCR
Marking the equipment with its short-circuit current rating
(SCCR) is another important consideration in the proper
application of PDBs and terminal blocks. This datasheet
provides the details on Cooper Bussmann power distribution
blocks and terminal blocks that have high short-circuit
current ratings. Using these PDBs and terminal blocks with
appropriate overcurrent protective devices makes it easier to
achieve a high short-circuit current rating for the entire panel
assembly.
SCCR for Wire Management Products
There are different ways to determine the SCCR for wire
management products (power distribution blocks, terminal
blocks and multi-lug connectors) per UL508A Supplement SB:
(1) Use tested and listed combinations, which consist of a
specific part number and a specific type and maximum size
overcurrent protective device. For instance, the power
distribution blocks in this datasheet are all SCCR tested and
listed combinations with fuses. An upstream current-limiting
fuse of a specific class and maximum ampere rating as
shown in the tables can be used to achieve the SCCR in the
tables. Otherwise, the SCCR of the power distribution block
will be determined by (2) or (3).
Combination SCCRs
Up to 200KA
UL Listed 1953 vs. UL Recognized 1059
Listed products simply require checking to ensure that the
product is used in accordance with its listing and labeling.
However, for recognized products, such as terminal blocks,
the “Conditions of Acceptability” must be investigated to
ensure the product is suitable for the specific application, and
then the procedure description must be documented in the
manufacturer’s procedure for the assembly.
Use Tables
Specified fuse class
with amp rating no
greater than maximum
shown
Most power distribution blocks available today are actually
terminal blocks, and are recognized to UL 1059, the terminal
block standard. Terminal blocks may or may not meet the
spacing needed for OEM applications. Terminal blocks are
marked with a UL recognition mark to ensure that the
designer and UL inspector checks, among other things, that
1011
SB-BU09622
Page 19 of 23
Data Sheet 1049
Application Notes
(2) UL508A has provisions to raise the rating of power
distribution blocks by the use of current-limiting
overcurrent protective devices such as current-limiting
fuses (i.e. class J, T, RK1, etc.) in the feeder portion of the
circuit.
(3) If the SCCR rating for a power distribution block, terminal
block or multi-lug connector is not established by (1) or (2)
above, then the SCCR is the default 10kA per UL508A,
Supplement SB, Table SB4.1.
For more in depth application material on SCCR see
Industrial Control Panel section of publication SPD or
Advanced Guide To Understanding Assembly Short-Circuit
Current Rating.
SCCR for Multi-Lug Connector (Power Distribution
Lug) Switch and Circuit Breaker
Switches or circuit breakers with multi-lug connectors for
conductor terminations serve a very similar wire management
function as power distribution blocks. However, it cannot be
assumed that when a multi-lug connector is installed on a
circuit breaker or switch, that the SCCR of the multi-lug
connector is the same as the interrupting rating of the
protective device. Multi-lug connectors are covered under UL
Standard 486 A/B. Much like a power distribution block,
multi-lug connectors are components for distributing tap
conductors to power loads and are not an integral part of the
overcurrent protective device operation. Therefore, the
multi-lug connector must be evaluated in a short-circuit test
with the specific overcurrent protective device and listed with
a specific combination SCCR. It is important to note, most
switches and circuit breakers are not short-circuit tested with
multi-lug connectors. If a multi-lug connector on a circuit
breaker or switch does not have a combination SCCR with
the specific overcurrent protective device used, then it is to
be treated in the same manner as an unmarked power
distribution block, which means the SCCR is the default 10kA
(UL508A, Supplement SB). To repeat, unless the switch or
circuit breaker with a multi-lug connector is specifically
marked with a short-circuit current rating, the actual shortcircuit current rating is 10,000 amperes (or less, if the
interrupting rating of the circuit breaker or fuse is less than
10,000 amperes). The use of a listed and tested combination
SCCR will ensure that a higher rating is achieved for the
product and aid in achieving a higher overall SCCR for the
industrial control panel.
PDB Spacing Requirements for Equipment:
Depending upon the specific application and the standard to
which the equipment is being designed, there are certain
PDBs that can meet these spacing requirements, some with a
high SCCR. The following details the spacing requirements at
600V based upon the equipment standards.
1011
SB-BU09622
UL Standard
508A Feeder
Circuits
508A Branch
Circuits
1995 HVAC
Spacing between
Spacing between
live parts of
live parts and
opposite polarity
grounded parts
or enclosure
Through air Over surface
@600V
@600V
@600V
1˝
2˝
1˝
3
1
1
⁄8˝
3⁄ ˝
8
⁄2˝
1⁄ ˝
2
⁄2˝
⁄2˝
1
Note: Refer to Specific UL standards for complete spacing details.
Industrial Control Panels (UL508A):
UL508A contains three important requirements to consider
when applying power distribution blocks.
• Spacing of 1˝ through air, 2˝ over surface (301 to 600V) is
required when used in a feeder circuit (that’s everything
ahead of or on the line side of the final branch circuit
overcurrent protective device).
• An assumed short-circuit current rating of 10kA for power
distribution and terminal blocks not marked with a higher
short-circuit current rating, per UL508A Table SB4.1.
• Conductor ampacity requirements based on conductor
terminal temperature ratings and UL508A conductor
ampacities
The following details the requirements regarding the use of
power distribution blocks in industrial control panels.
Use of Power Distribution Blocks in Industrial Control
Panel Feeder Circuits (600V & below)
• A Listed PDB (UL1953) can be used “as is” since it meets
the 2˝ and 1˝ spacing requirements for feeder circuits in
UL508A section 10.2 (see Table 10.2) & 28.2.4.
• A Recognized Terminal Block (UL1059) can only be used if
it meets the spacing requirements in UL508A sections 10.2
(see Table 10.2) & 28.2.1 and it is suitable for field wiring
(use Group A, C or D of UL 1059).
– Use Group A: Service — including dead-front switch
boards, panelboards, service equipment, and the like.
– Use Group B: Commercial appliances, including
business equipment, electronic data processing
equipment, and the like.
– Use Group C: Industrial, general.
– Use Group D: Industrial, devices having limited ratings.
Such as where the load on any single circuit of the
terminal block does not exceed 15 amperes at 51 to
150 volts, 10 amperes at 151 to 300 volts, 5 amperes at
301 to 600 volts, or the maximum ampere rating,
whichever is less.
Listed PDBs have adequate spacing for feeder
circuit applications but most recognized terminal
blocks don’t have the spacing required
for use in feeder circuits
Page 20 of 23
Data Sheet 1049
Application Notes
Use of Power Distribution Blocks in Industrial Control
Panel Branch Circuits (600V & below)
• A Listed PDB (UL1953) can be used “as is” since it exceeds
the spacing requirements for branch circuits in UL508A
section 10.2 (see table 10.1) & 28.2.4.
• A Recognized Terminal Block (UL1059) can only be used if
it meets the spacing requirements at the required voltage in
UL 508A, section 10.2 (see Table 10.1) & 28.2.1 and it is
suitable for field wiring (Use Group A, C or D of UL 1059).
Listed PDBs have adequate spacing for branch
circuit applications and most recognized terminal
blocks are also adequate for branch
circuit applications
Termination Ratings
Important considerations in the electrical and thermal
relationship for components in a circuit are the conductor
size, material, rated ampacity, conductor insulation
temperature rating and the permissible connector device
conductor temperature limits.
If a conductor terminates at two devices that have conductor
terminations rated at two different temperatures, the
conductor ampacity must correlate to the terminal with the
lowest temperature rating.
60°C terminal
75°C terminal
Power Distribution Block Application Examples –
UL 508A
Conductor size and insulation rating?
Conductors with higher temperature ratings can be used at
their rated ampacities if the terminations of the circuit devices
are rated for the higher temperature rated conductor [NEC
110.14(C)(1)(a)(3)]. However, the industry norm is that most
devices rated 100A or less, such as blocks, disconnects,
controllers and circuit breakers, have 60°C or 75°C rated
terminations. For circuits greater than 100A, the norm is
75°C terminations. UL508A has further internal wiring
restrictions requiring 90°C insulated conductors, but these
conductors are sized based on either 60ºC or 75ºC
allowable ampacities.
PDB in UL 508A, 480V Feeder Circuit must have spacing of 1˝ through air and 2˝
over suface. PDBs listed to UL 1953 meet these spacing requirements. Terminal
Blocks recognized to UL 1059 must be verified to have required spacing.
Terminations have a temperature rating that must be
observed and this has implications on permissible conductor
temperature rating and ampacity. Shown below are three
common termination ratings and the rules. The conductor
ampacity may also have to be derated due to ambient,
conduit fill or other reasons.
Terminal
Temp Rating
60°C
75°C
PDB in UL508A, 480V Branch Circuit must have spacing of 3⁄8˝ through air and 1⁄2˝
over surface. PDBs listed to UL 1953 meet these spacing as well as most
terminal blocks recognized to UL 1059.
60°C/75°C
1011
Page 21 of 23
SB-BU09622
60°C, 75°C, 90°C or higher temperature rated
conductor can be used, but the ampacity of the
conductor must be based as if conductor is
rated 60°C.
75°C, 90°C or higher temperature rated conductor
can be used, but the ampacity of the conductor must
be based as if conductor is rated 75°C. A 60°C
conductor is not permitted to be used.
Dual temperature rated termination. Either 60°C
conductors at 60°C ampacity or 75°C conductors at
75°C ampacity can be used. If 90°C or higher
temperature rated conductor is used, the ampacity of
the conductor must be based as if conductor is
rated 75°C.
Data Sheet 1049
Application Notes
For more information on this see section Conductor &
Terminations – Application Considerations in the Cooper
Bussmann publication SPD – Selecting Protective Devices on
www.cooperbussmann.com
UL 508A Industrial Control Panels Conductors for
Internal Wiring: Copper conductors only. Conductors are
sized based on either the 60°C or 75°C allowable conductor
ampacities from UL508A, Table 28.1 (following). The 75°C
ampacities can only be used if the termination temperature
ratings at both ends of the conductor are rated 75°C or
60°C/75°C. In addition, the conductor insulation is required
to be 90°C or higher temperature rated even though the
ampacity is based on 60°C or 75°C (UL508A, 29.2.1 &
29.6.1(b)).
HVAC Equipment (UL1995):
The electrical panel is required to be marked with the
assembly SCCR per NEC® 440.4(B). The larger spacing that
is mandated in UL508A is not present in UL1995. If the
control panel for the HVAC equipment is a listed UL508A
panel, then the larger UL508A spacing is required.
Power Distribution Block Application UL 1995
Example
UL508A, Table 28.1 (Partial)
Wire size
AWG
(mm2)
14
(2.1)
12
(3.3)
10
(5.3)
8
(8.4)
6
(13.3)
4
(21.2)
3
(26.7)
2
(33.6)
1
(42.4)
1/0
(53.5)
2/0
(67.4)
3/0
(85.0)
4/0
(107.2)
250 kcmil
(127)
300
(152)
350
(177)
400
(203)
500
(253)
600
(304)
700
(355)
750
(380)
800
(405)
900
(456)
1000
(506)
1250
(633)
1500
(760)
1750
(887)
2000
(1013)
60ºC (140ºF)
Copper
15
20
30
40
55
70
85
95
110
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
75ºC (167ºF)
Copper
15
20
30
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
420
460
475
490
520
545
590
625
650
665
PDB in 480V UL 1995 HVAC Equipment must have spacing of 3/8˝
through air and 1/2˝ over surface. PDBs listed to UL 1953 meet this spacing
as well as most terminal blocks recognized to UL 1059.
NOTES
1 For multiple-conductors of the same size (1/0 AWG or larger) at a terminal, the
ampacity is equal to the value in this table for that conductor multiplied by the
number of conductors that the terminal is able to accommodate.
1011
SB-BU09622
Page 22 of 23
Data Sheet 1049
Application Notes
New 2005 NEC® Requirements For Wireways:
UL1953 listed power distribution blocks are suitable for the
new 2005 NEC® requirement in section 376.56(B) for field
installation in metal wireways, if they are the enclosed type
(Series PDBFS) or open type with cover. UL1953 is explicit in
paragraph 1.1 that these devices are used for splicing and
tapping conductors in metallic wireways, junction boxes,
auxilary gutters, etc. Listed devices can be field installed;
however, recognized devices are not intended for field
installation. UL1059 devices are recognized and are terminal
blocks, not power distribution blocks. Therefore UL1059
devices are not suitable for field installation and are not
suitable for metal wireway applications even if enclosed or
with covers. Also, the SCCR rating of a power distribution
block installed in a metal wireway shall be equal to or greater
than the available short-circuit current at the point of
application (NEC® 110-10).
National Electrical Code®:
376.56(B) Power Distribution Blocks.
“(1) Installation. Power distribution blocks installed in metal
wireways shall be listed.”
“(4) Live Parts. Power distribution blocks shall not have
exposed live parts in the wireway after installation.”
Power Distribution Block Application Wireway
Example
Series PDB (open style) with covers and Series PDBFS (enclosed style) are
suitable for installation in metal wireways.
When installed in metal wireways, the NEC® now
requires a power distribution block that is listed
(acceptableto AHJ). It must be an enclosed PDB or
equipped with a cover to prevent exposure of live
parts. Series PDBFS (enclosed style) and Series
PDB with optional covers are UL1953 Power
Distribution Blocks and are suitable for metal
wireway applications. Terminal blocks, UL1059
recognized devices, are not suitable for
this application.
1011
SB-BU09622
Page 23 of 23
Data Sheet 1049