REPORT
on
COMPONENT – TERMINAL BLOCKS
Weidmueller Interface GmbH & Co. KG
Klingenbergstrasse 16, 32758 Detmold
Copyright © 2005 Underwriters Laboratories Inc.
*Underwriters Laboratories Inc. authorizes the above named company to
reproduce the latest pages of that portion of this Report consisting of this
Cover Page through Page 3A.
File E60693
Vol. 1
Sec. 82
and Report
Page 1
Issued:
Revised:
2005-10-13
2008-02-21
DESCRIPTION
PRODUCT COVERED:
USR, CNR Component - Terminal Blocks, Cat. Nos. as follows:
PDU 2.5/4
PDU 2.5/4/3AN
PDU 2.5/4/4AN
PPE 2.5/4
PPE 2.5/4/3AN
PPE 2.5/4/4AN
USR, CNR Recognized Component – Terminal Block Cat. Nos. PDK 2.5/4, may
be followed by N/L, V, L-PE, N-PE or PE.
USR, CNR Recognized Component – Terminal Block Cat. Nos. PTR 2.5/4, may
be followed by 3AN, 4AN, BL, 3AN BL or 4AN BL.
USR, CNR Component - Terminal Blocks,
Cat. Nos. PDL 4 followed by /L, /N or /NT, followed by L may be followed by
PE. Cat. No. PDL 4 followed by /TR followed by /DU may be followed by O TNHE,
/PE, /PE O TNHE.
USR, CNR Component – Terminal Blocks, Cat. Nos. PDU 16 may be followed
by BL, PEI 16 may be followed by BL, PPE 16.
USR, CNR Component – Terminal Blocks, Cat. Nos. PDU 6/10 may be followed
by /3AN, PPE 6/10 may be followed by /3AN.
GENERAL CHARACTER AND USE:
The terminal blocks covered by this Report are intended for use in the
following applications and within the ratings specified.
PDU and PPE types are similar in construction except the PPE types are
molded of green-yellow color and are provided with a grounding current bar to
the DIN Rail.
Cat. No. PEI 16 is similar to PDU 16 except different shape of current
bar and body in the middle for measuring point.
PDL 4 types are similar in construction. All devices are provided with 2
current paths. Types with /PE in the suffix are provided with an additional
grounding current bar to the DIN Rail. Types with /TR/DU or /NT in the suffix
are provided with one disconnect current bar. Types with O TNHE in the suffix
are not provided with a disconnect lever.
PDU 6/10/3AN is similar to PDU 6/10 except with three connections
instead of two.
File E60693
Vol. 1
Sec. 82
and Report
Page 1-1
Issued:
New:
2005-10-13
2008-02-21
GENERAL CHARACTER AND USE continued:
PDK 2.5/4 types are similar in construction. All devices are provided
with two current bars. Current bars of types with suffix V are interconnected.
Types with suffixes L-PE and N-PE are provided with grounding foot for
mounting to DIN Rails. Types with suffix PE are green-yellow colored
protective conductor terminal blocks with interconnected current bars. These
types are also provided with grounding foot for mounting to DIN Rail.
PTR 2.5/4 tapes are similar in construction. All types are provided with
one disconnecting lever. Numbers of poles are varying.
File E60693
Vol. 1
Sec. 82
and Report
Page 1A
Issued:
New:
2005-10-13
2008-02-21
RATINGS:
Application Commercial appliances (such as business and EDP equipment, etc.)
General industrial (such as motor controllers, pushbutton stations,
etc.)
Industrial control devices having limited ratings (see note A under
Ratings).
Terminal Type - Push-In Type (Wire Secured by Spring Type Action)
Type Wiring - Factory and Field wiring
File E60693
Vol. 1
Sec. 82
and Report
Page 2
Issued:
Revised:
2005-10-13
2008-02-21
Cat. No. Series
PDU 2.5/4+
Wire Range
AWG/kcmil
26-10
Wire Type,
Cu
SOL/STR
Voltage V
600
Current A
30
PDU 2.5/4/3AN+
26-10
SOL/STR
600
30
C
PDU 2.5/4/4AN+
26-10
SOL/STR
600
30
C
PPE 2.5/4
26-10
SOL/STR
-
#
C
PPE 2.5/4/3AN
26-10
SOL/STR
-
#
C
PPE 2.5/4/4AN
26-10
SOL/STR
-
#
C
PDL 4
28-10
SOL/STR
300
17, 20#1
B
PDL 4
28-10
SOL/STR
150
17, 20#1
C
*PDL 4
28-10
SOL/STR
300
PDL 4 with PE in
Suffix
28-10
SOL/STR
300
*PDL 4 with PE in
Suffix
PDU 16+, PEI 16
PPE
PDU
PDU
PPE
PPE
PDK
16
6/10+,
6/10/3AN+
6/10,
6/10/3AN
2.5/4
A
UG
C
D
17, 20#1
B
#2
A
, #2
D
600
75, 78#1
B, C
SOL/STR
-
#
B, C
14-8
SOL/STR
600
44, 46#1
B, C
14-8
SOL/STR
-
#
B, C
26-10
SOL/STR
600
30A
B, C, D
A
B, C, D
28-10
SOL/STR
300
14-4
SOL/STR
14-4
PDK 2.5/4 V
26-10
SOL/STR
600
30
PDK 2.5/4 N/L
26-10
SOL/STR
600
30A
B, C, D
A
PDK 2.5/4 L-PE
26-10
SOL/STR
600/-
30 /-##
B, C, D
PDK 2.5/4 N-PE
26-10
SOL/STR
600/-
30A/-##
B, C, D
PDK 2.5/4 PE
26-10
SOL/STR
-
-###
B, C, D
PTR 2.5/4
26-10
SOL/STR
600
24A
B, C, D
A
B, C, D
PTR 2.5/4 3AN
26-10
SOL/STR
600
24
PTR 2.5/4 4AN
26-10
SOL/STR
600
24A
B, C, D
A
B, C, D
PTR 2.5/4 BL
26-10
SOL/STR
600
24
PTR 2.5/4 3AN BL
26-10
SOL/STR
600
24A
B, C, D
600
A
B, C, D
PTR 2.5/4 4AN BL
26-10
SOL/STR
24
File E60693
Vol. 1
Sec. 82
and Report
Page 2-1
Issued:
New:
2005-10-13
2008-02-21
Note A - These limited ratings are applicable to a terminal block for
use in or with industrial control equipment whereby the load on any single
circuit of the terminal block does not exceed 15 A at 51-150 V, 10 A at 151300 V, or 5 A at 301-600 V, or the maximum ampere rating, whichever is less
Strip length – 12 mm
# -
Has been evaluated for its suitability as a protective conductor
terminal block and complies with the applicable grounding requirements
for terminals for use in a protective circuit.(General Industrial
Applications). These Models can be provided in green and yellow.
## -
These terminal blocks consisting of two current bars where the lower
current bar has been evaluated for its suitability as a protective
conductor terminal block and complies with the applicable grounding
requirements for terminals for use in a protective circuit. (Commercial
Applications, Industrial Applications and Industrial, devices having
limited ratings)
### - Has been evaluated for its suitability as a protective conductor
terminal block and complies with the applicable grounding requirements
for terminals for use in a protective circuit. (Commercial Applications,
Industrial Applications and Industrial, devices having limited ratings).
These Models shall be provided in green and yellow.
#1 – For Canadian Recognition only
#2 -
The PE Terminal has been evaluated for its suitability as a protective
conductor terminal block and complies with the applicable grounding
requirements for terminals for use in a protective circuit. (Commercial
appliances and Industrial control devices having limited ratings). These
PE Terminal can be marked in green and yellow.
File E60693
Vol. 1
Sec. 82
and Report
Page 2A
Issued:
New:
2005-10-13
2008-02-21
+ - Cat. Nos. PDU 2.5/4 4AN, PDU 2.5/4 3AN, PDU2.5/4, PDU 6/10 3AN, PDU 6/10
and PDU 16 have optional short circuit current rating evaluated for use with
copper conductors only. Must be protected by the max ampere and Class of
overcurrent protective device noted below:
Cat. No.
Suitable Copper
Conductor Range
Line
Load
PDU 2.5/4 4AN,
PDU 2.5/4 3AN,
PDU 2.5/4
14-10
PDU 6/10 3AN,
PDU 6/10
14-8
PDU 16
12-4
Limiter Fuse
Ampere
Max
60
Fuse Class
J, T
14-10
100
30
RK1,G, CC
60
J, T
30
RK1,G, CC
100
J, T
60
RK1, G
30
RK5, CC
14-8
12-4
SCCR
(kA)
100
100
File E60693
Vol. 1
Sec. 82
and Report
Page 2A
Issued:
New:
2005-10-13
2008-02-21
MODEL NOMENCLATURE for PDK..:
Example:
I
PDK
2.5/4
N/L
I
II
III
-
Basic Construction PDK (Push in type twin terminal block)
II -
Wire Size:
2.5/4
III - Model
Blank
N/L
V
L-PE
N-PE
PE
of terminal block:
one phase per current bar
neutral conductor/phase conductor
interconnection of current bars
phase conductor/protective conductor
neutral conductor/protective conductor
protective conductor terminal block, green and yellow
MODEL NOMENCLATURE for PTR..:
Example:
PTR
2.5/4
3AN
BL
I
II
III
IV
I Basic Construction PTR (Push in type terminal block with disconnect
lever)
II
- Wire Size:
2.5/4
III - Number of poles:
Blank 2 poles
3AN
3 poles
4AN
4 poles
IV
- Color of insulating body
BL
blue
Blank gray
File E60693
Vol. 1
Sec. 82
and Report
Page 3
Issued:
Revised:
2005-10-13
2008-02-21
ENGINEERING CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE USE):
Products designated USR have been investigated using requirements
contained in UL 1059, the Standard for Terminal Blocks.
Products designated CNR have been investigated using requirements
contained in Canadian Standard CSA C22.2 No. 158, Terminal Blocks.
Conditions of Acceptability –
For use only in (or with) complete equipment where the acceptability of
the combination is determined by Underwriters Laboratories Inc.
1.
The insulating bodies are molded of polymeric materials as specified in
the Section General, designated “I-1”. The use of these materials shall be
judged in the end use application. The maximum operating temperature shall
not exceed 105°C.
2.
The field
evaluated using
Aluminum and/or
terminals shall
wiring terminals of this terminal block have been
the Standard for Equipment Wiring Terminals For Use With
Copper Conductors, UL 486E. The suitability of these
be determined in the end-use investigation.
3.
An additional Conditioning-Temperature-Dielectric Sequence (until
stabilized temperatures) was conducted with the device PDL 4/TR/DU/PE O TNHE
in combination with the for this manufacturer recognized fuseholder Siha 3/G20
with a Current of 9 A and 16AWG solid and stranded wire. The temperature rise
did not exceed 30 °C in all cases.
4.
The terminal block short-circuit ratings on Cat. Nos. PDU 2.5/4, PDU
2.5/4 4AN, PDU 2.5/4 3AN, PDU 6/10, PDU 6/10 3AN and PDU 16 were determined
based on testing in a minimum size enclosure measuring 16 x 12 x 6 inches. The
suitability of smaller enclosures shall be determined in the end-use
investigation.
5.
The terminal blocks of type PTR 2.5/4.. and type PDL 4/..are intended
for disconnecting use only. These devices shall not interrupt the flow of
current under load.
File E60693
Vol. 1
Sec. 82
and Report
Page 3A
Issued:
New:
2005-10-13
2008-02-21
6.
The insulating bodies are molded of polymeric materials as
specified in the following tabulation. The use of these materials shall be
judged in the end use application.
Cat. Nos.
Material Manufacturer Name
and Grade Designation
PDK 2.5/4, may be
followed by N/L, V,
L-PE, N-PE or PE
BASF AG, KR4205(m), C3U(m)
PTR 2.5/4, may be
followed by 3AN, 4AN,
BL, 3AN BL or 4AN BL
Bada AG, KR4205, C3U,
LC70FR HF
Base material Temperature
Rating, °C
105 (generic)
File E60693
Vol. 1
Sec. 82
and Report
Page 4
Issued:
Revised:
2005-10-13
2008-02-21
MARKING:
See Section General.
Short-circuit current ratings may be marked on the terminal block or on
instructions provided with the terminal block.
For Terminal Blocks with Short-circuit current ratings:
The minimum enclosure size of 16 x 12 x 6 in. shall be marked on an
information sheet packed within the unit container.
A terminal block with a short circuit rating greater than 10,000 amperes rms
shall be marked similar to below:
“When protected by (1) ampere maximum Class (2) fuse, this terminal block is
rated for use on a circuit capable of delivering no more than (4) rms
symmetrical or dc amperes (5) volts maximum”
where: 1)
Fuse ampere rating
2)
Fuse designation (G, J, L, RK1, RK5, or T)
3)
Short Circuit rating
4)
Circuit voltage
Terminal blocks with disconnect lever intended for disconnecting use shall be
marked “Not for current interrupting” or “For disconnecting use only”or with
an equivalent statement. This marking shall be located on the device, or in or
on the smallest unit container or carton.