COOPER 170M6814D

High Speed Fuses
Square Body DIN 43 620 — 690V/700V (IEC/UL):
40-1000A
690V/700V (IEC/UL) 40-1000A
Arc Voltage
This curve gives the peak
arc voltage, UL, which
may appear across the
fuse during its operation
as a function of the
applied working voltage,
Eg, (rms) at a power factor
of 15%.
Specifications
Description: Square body DIN
43 620 blade style high speed
fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 690Vac (IEC)
— 700Vac (UL)
Amps: — 40-1000A
IR: — 200kA RMS Sym.
Ag ency Information: CE, Designed and tested to IEC
60269: Part 4, UL Recognized.
Power Losses
Watts loss at rated current
is given in the electrical
characteristics. The curve
allows the calculation of
the power losses at load
currents lower than the
rated current. The
correction factor, Kp, is
given as a function of the
RMS load current, Ib, in %
of the rated current.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at
rated voltage and at power
factor of 15% are given in
the electrical
characteristics. For other
voltages, the clearing I2t is
found by multiplying by
correction factor, K, given
as a function of applied
working voltage, Eg, (rms).
•
•
•
•
Features and Benefits
Excellent DC performance
Low arc voltage and low energy let-through (I2t)
Low watts loss
Superior cycling capability
•
•
•
•
Typical Applications
DC common bus
DC drives
Power converters/rectifiers
Reduced voltage starters
For Full Range Fuses in This Body Style
• See page 140
Dimensions (mm)
Type DIN 1*, DIN 2, DIN 3
Size
1*
2
3
A
69
69
68
B
135
150
150
D
58
71
88
A
E
45
55
76
F
40
48
60
H
20
26
33
Indicator
H
1mm = 0.0394” / 1” = 25.4mm
D
F
B
E
132
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
6
High Speed Fuses
Square Body DIN 43 620 — 690V/700V (IEC/UL):
40-600A
Size 1* — 40-630A: 690V
Catalog Numbers
Siz e
1*
2
3
Electrical Characteristics
Rated
I2t (A2Sec)
Current
Clearing
RMS-Amps Pre-arc
at 660V
40
40
285
50
78
550
63
120
850
80
185
1350
100
360
2600
125
550
3900
160
1150
8250
200
2300
16500
250
4350
31000
315
7300
52000
350
10000
73000
400
16000
115000
450
21500
155000
500
27000
190000
550
33500
240000
630
48500
345000
700
69500
495000
400
11000
79000
450
16000
115000
500
21500
155000
550
29000
215000
630
41000
295000
700
60500
430000
800
86000
610000
900
125000
895000
1000
180000 1300000
1100
245000 1750000
500
14000
99500
550
19500
140000
630
31000
220000
700
45000
320000
800
69500
490000
900
100000
720000
1000
140000
985000
1100
190000 1400000
1250
300000 2150000
1400
380000 2700000
1500
470000 3350000
1600
585000 4150000
Time-Current Curve
Watts
Loss
4
4.5
6.5
8.5
10
11
12
12.5
16
20
21.5
60
26.3
28.5
33
37.5
39
29
32
34
36
42
43
48
52
53
56
43
44
45
46
48
50
56
57
61
70
72
74
• Watts loss provided at rated current.
• Microswitch indicator ordered separately. See accessories on pages 185-186.
• For fuse curves see page 134.
High Speed
Fuses
Catalog Numbers
DIN Type T
Indicator
for Micro
170M3808D
170M3809D
170M3810D
170M3811D
170M3812D
170M3813D
170M3814D
170M3815D
170M3816D
170M3817D
170M3818D
170M3819D
170M4863D
170M4864D
170M4865D
170M4866D
170M4867D
170M5808D
170M5809D
170M5810D
170M5811D
170M5812D
170M5813D
170M5814D
170M5820D
170M5816D
170M5817D
170M6808D
170M6809D
170M6810D
170M6811D
170M6812D
170M6813D
170M6814D
170M6892D
170M8554D
170M8555D
170M8556D
170M8557D
Peak Let-Through Curve
Rated Current
The rated current of this fuse range has been given with
copper conductors that have a current density of 1.3 A/mm2
(IEC 60269-4). For conductor cross section according to IEC
60269-1, the fuses must be derated. Please contact Cooper
Bussmann for application assistance.
Data Sheet: 17056314
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
133
High Speed Fuses
Square Body DIN 43 620 — 690V/700V (IEC/UL):
40-1000A
Size 2 — 400-1250A: 690V
Size 3 — 500-2000A: 690V
Time-Current Curve
Time-Current Curve
Peak Let-Through Curve
Data Sheet: 17056318
134
Peak Let-Through Curve
Data Sheet: 17056320
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa