High Speed Fuses Section Contents Page General Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . 88-89 North American fuses & accessories . . . . . . . . . . . . 90-106 Square Body fuses & accessories . . . . . . . . . . . . . 107-180 BS 88 fuses & accessories . . . . . . . . . . . . . . . . . . . .181-190 Ferrule fuses & accessories. . . . . . . . . . . . . . . . . . . .191-212 High Speed Fuses 87 High Speed Fuses General applications Rated Voltage The ac voltage rating of Cooper Bussmann® fuses is given in volts rms. Fuses tested to IEC are tested at 10% above their rated voltage. British Style BS 88 fuses are tested at 5% above its rated voltage. UL recognition tests are performed at the rated voltage. For other power factor values, the total clearing integral can be calculated as a multiple of the clearing integrals, the correction factor K and the correction factor X. X 1.0 0.9 Rated Current Rated current is given in amperes rms. Cooper Bussmann fuses can continuously carry the rated current. 0.8 Melting Characteristic Arc Voltage 104 6 4 2 6 4 2 102 6 4 2 101 6 4 0.1 0.3 2 6 4 2 10–2 6 4 2 –3 6 4 2 10–4 0.5 COS 1.4 1.2 UL 103 9 8 7 6 5 Eg 3 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 10–1 10 1 2 4 6 8 10 2 2 4 6 8 10 3 Prospective Current In Amperes RMS 200 300 400 500 600 660 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 Ib 0.1 30 40 50 60 70 80 90 100% Cut-Off Current 1.5 A fuse operation relating to short-circuits only. When a fuse operates in its current-limiting range, it will clear a short-circuit in less than 1⁄2 cycle. Also, it will limit the instantaneous peak let-through current to a value substantially less than that obtainable in the same circuit if that fuse were replaced with a solid conductor of equal impedance. K 1.0 0.5 0.4 105 0.3 0.2 Eg 100 200 300 400 500 600 660 Peak Let-Through Current The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 104 103 A B 2≈ 10 2 102 103 104 Prospective Current in Amperes RMS 105 A asymmetrical current B symmetrical current 88 0.4 Power Losses 6 4 10 0.2 4 2 100 Clearing Integrals 2 0.7 This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (rms) at a power factor of 15%. 103 Virtual Pre-Arcing Time In Seconds The melting characteristic shows the virtual melting time in seconds as a function of the prospective current in amperes rms. The fuses are specially constructed for short-circuit protection against high level fault currents. Loading and operation of the fuse in the non-continuous/dashed section of the melt curve must be avoided. The curve can also be read as the real melting time as a function of the RMS value of the pre-arc current. For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 106 High Speed Fuses General applications Parallel Connection Frequency of Occurrence Less than once per month When fuses are connected in parallel it is recommended that the applied voltage does not exceed 0.9 UN (the rated voltage of the fuse). This is due to the fact that the energy released within the fuses may be unevenly shared between the parallel connected barrels. When fuses are connected in parallel, one must take into account that the current sharing is not necessarily equal. And it must be checked, that the maximum load current is not exceeded. Series Connection Mounting Guidance The recommendations below have to be followed when mounting a Cooper Bussmann fuse with end plate threaded holes. 1. Screw in studs: 5 N•m Max, 3 N•m Min 2. Attachment of the fuse to buss-bar by means of nut and washer: Thread Configuration 5 ⁄16” – 18, M8 3 ⁄8” – 16, M10 3 ⁄8” – 24 1 ⁄2” – 13, M12 1 ⁄2” – 20 *1 N•m = 0.7375 lb-ft Torque (N•m)* Max Min 25 20 45 40 45 40 65 50 65 50 Impulse Loads (< 1 sec) Imax < 70% x It Imax < 60% x It Several times per day Imax < 60% x It — When impulse loads are an intrinsic/normal parameter of the load current either as single pulse or in trains of pulses or when their level is higher than the melting current at 0.01 seconds (per time-current curve), contact Cooper Bussmann for application assistance. In addition to the parameters set forth in the preceding table, the RMS value of the load current as calculated for any period of 10 minutes or more should not exceed the maximum permissible load current. Furthermore, it is important that a fuse should not be applied in the non-continuous/dashed portion of the associated time-current curve. Any time-current combination point which falls in the non-continuous/dashed portion of the time-current curve is beyond the capability of the fuse to operate properly. DC Operation Depending upon the short-circuit time constant and the magnitude of the prospective short-circuit current, the dc voltage at which a fuse can be applied may be less than its ac rating. Long time constants require a lower dc voltage. Conversely, however, higher available prospective short-circuit currents result in faster fuse openings and thus permit a fuse to be operated at a higher dc voltage. Consult Cooper Bussmann for additional information and application assistance when fuses have to operate under dc conditions. Overloads The design of Cooper Bussmann® fuses is such that they can be operated under rather severe operating conditions imposed by overloads (any load current in excess of the maximum permissible load current). In applications, there will be a maximum overload current, Imax, which can be imposed on the fuse with a corresponding duration and frequency of occurrence. Time durations fall into two categories: 1. Overloads longer than one second 2. Overloads less than one second termed “impulse” loads. The following table gives general application guidelines which, in the expression Imax < (% factor) x It. It is the melting current corresponding to the time “t” of the overload duration as read from the time-current curve of the fuse. The guidelines in the table below determine the acceptability of the selected fuses for a given Imax. Load Current Versus Reduction Factor Conductor Cross Section 1.0 Reduction of permissible load current when the 0.9 conductor cross section is less than that given in IEC 0 . 8 Publication 269-1 & 4 valid for Cooper 0 . 5 0 . 6 0 . 7 0.8 0.9 Bussmann semiconductor ≈ (IEC cross section) fuses. 1.0 Application Assistance If you have application problems or need a fuse outside our standard program, please contact the nearest Cooper Bussmann representative. Phone numbers are shown on the back cover. For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 89 High Speed Fuses Fuses in series may not equally divide the applied voltage. It is recommended that series connected fuses should only be operated at fault currents that yield melting times less than 10 ms and a recovery voltage per fuse of less than or equal to 0.9 UN (the rated voltage of the fuse). Less than twice per week Overloads (> 1 sec) Imax < 80% x It Imax < 70% x It High Speed Fuses North American fuses General Information Introduction North American Contents Catalog Number FWA FWA FWX FWH KAC KBC FWP FWJ Amp Range 1000-4000 70-1000 35-2500 35-1600 1-1000 35-800 5-1200 35-2000 Volts 130 150 250 500 600 600 700 1000 Accessories Fuse Bases 106 North American Fuse Ranges Amps 1000-4000 70-1000 35-2500 35-1600 1-1000 5-1200 40-600 35-2000 90 Page 91-92 93-94 95-96 97-98 99 100 101-103 104-105 Volts 130 150 250 500 600 700 800 1000 AC X X X X X X — X DC X X X X — X X — Cooper Bussmann offers a complete range of North American blade and flush-end style fuses and accessories. Their design and construction were optimized to provide: • Low energy let-through (I2t) • Low watts loss • Superior cycling capability • Low arc voltage • Excellent dc performance North American style fuses provide an excellent solution for medium power applications. While there are currently no published standards for these fuses, the industry has standardized on mounting centers that accept Cooper Bussmann fuses. Voltage Rating All Cooper Bussmann® North American style fuses are tested at their rated voltage. Cooper Bussmann should be consulted for applications exceeding those values. Accessories External and internal open fuse indication is available for selected portions of the North American line. Fuse blocks are available for most applications. For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp High Speed Fuses North American — FWA 130V: 1000-4000A Arc Voltage FWA This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style flush-end high speed fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 130Vac Amps: — 1000-4000A IR: — 200kA RMS Sym. — 50kA @130Vdc Agency Information: CE, UL Recognized on 1000-2000A fuses 1.5 K 1.0 100 Eg 50 0.5 100 150 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 Ib 0.1 30 40 50 60 70 80 90 100% Catalog Numbers 0.3 0.2 Catalog Numbers FWA-1000AH FWA-1200AH FWA-1500AH FWA-2000AH FWA-2500AH FWA-3000AH FWA-4000AH Eg 0.15 26 65 104 130 Electrical Characteristics I2t (A2 Sec) Rated Current Clearing RMS-Amps Pre-arc at 130V 1000 170000 460000 1200 270000 730000 1500 520000 1400000 2000 860000 2400000 2500 1500000 4100000 3000 2100000 5700000 4000 3400000 9200000 Watts Loss 60 70 78 108 130 150 257 • Watts loss provided at rated current. • See accessories on page 106. Dimensions (in) Catalog Number FWA-1000AH-2000AH FWA-2500AH-3000AH FWA-4000AH 200 High Speed Fuses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 300 Power Losses Electrical Characteristics Total Clearing UL Fig. 1 1 2 B 2.0 3.0 3.5 C 1.0 1.5 1.5 D — — 1.5 Thread Depth Tapped 3⁄8”-24 x 1⁄2” Tapped 1⁄2”-20 x 1⁄2” Tapped 1⁄2”-20 x 1⁄2” 1mm = 0.0394∑ / 1∑ = 25.4mm Fig. 1: 1000-3000A Fig. 2: 4000A 1.875 1.875 • • • • Features and Benefits Excellent dc performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters D B C B C For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 91 High Speed Fuses North American — FWA 130V: 1000-4000A FWA 1000-4000A: 130V Time-Current Curve 104 6 4 Did You Know? 2 103 6 4 Protect Against Downtime with Technical Training, and Earn CEUs at the Same Time FWA-1000AH FWA-1200AH FWA-1500AH FWA-2000AH FWA-2500AH FWA-3000AH FWA-4000AH 2 102 6 4 Our application engineering team offers two training seminars at the Cooper Bussmann St. Louis headquarters Technical Center for end-user customers. These two-day seminars provide participants 1.6 Continuing Education Units (CEUs). Attendees are responsible for their own airfare and hotel costs; meals and ground transportation are provided. Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 10 0 6 4 Industrial Machinery This two-day seminar highlights overcurrent protection considerations for industrial machinery and industrial control panels, design standards as well as a review of various overcurrent protective devices. The seminar is offered to: • Engineers for industrials who specify equipment • Electrical panel builders • Machinery builders • Electrical designers 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 Commercial and Industrial Power Systems This two-day seminar provides a comprehensive review of the proper overcurrent protection of building power distribution systems including elevator protection, ground fault protection and compliance with industry standards. The seminar is targeted to: • Consulting engineers • Plant engineers • Electrical contractors • Electrical designers • Inspectors 2 10–4 2 103 4 6 8 2 4 6 104 Prospective Current In Amperes RMS 8 105 Peak Let-Through Curve 2 105 6 Peak Let-Through Current 4 2 FWA-4000AH FWA-3000AH 104 Contact your local district sales engineer or representative, or call our application engineering team for more information: 636-527-1270. Check at www.cooperbussmann.com for schedules and seminar cost. FWA-2500AH FWA-2000AH FWA-1500AH 6 FWA-1200AH FWA-1000AH 4 2 103 103 2 4 6 104 2 4 6 105 2 4 6 Data Sheet: 35785301 92 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp High Speed Fuses North American — FWA 150V: 70-1000A FWA Arc Voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 150Vac Amps: — 70-1000A IR: — 100kA Sym. (70-400A) — 200kA Sym. (450-1000A) — 20kA @150Vdc (70-800A) — 100kA @ 80Vdc (70-400A) Agency Information: CE, UL Recognized 100 50 100 150 1.0 Kp 0.8 0.6 0.5 High Speed Fuses K 1.0 0.4 0.3 0.2 Ib 0.1 30 40 50 60 70 80 90 100% Catalog Numbers 0.5 0.3 0.2 0.15 22 1) 2) Eg 70 102 150 1) 500-1000A Range 2) 70-400A Range Dimensions (in) Fig. 1: 70-400A Catalog Number FWA-70B FWA-80B FWA-100B FWA-125B FWA-150B FWA-200B FWA-250B FWA-300B FWA-350B FWA-400B FWA-500A FWA-600A FWA-700A FWA-800A FWA-1000A Rated Current RMS-Amps 70 80 100 125 150 200 250 300 350 400 500 600 700 800 1000 Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 150V 470 4000 670 6000 1200 12000 1870 18000 2700 26000 4780 45000 7470 70000 10760 100000 15700 140000 20300 180000 39000 120000 46000 140000 75000 220000 92000 280000 170000 510000 Watts Loss 6.9 7.7 9.0 11.2 13.5 17.6 22.5 27.0 30.6 35.2 35.0 47.0 49.0 58.0 60.0 • Watts loss provided at rated current. • See accessories on page 106. 2.656 2.188 1.936 1.156 0.750 0.312 200 Eg Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. 1.5 The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 300 Power Losses Electrical Characteristics Total Clearing I2t UL 0.125 1.000 • • • • Features and Benefits Excellent dc performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters 0.438 Fig. 2: 500-1000A 3.500 2.438 1.250 1.000 0.250 1.500 0.406 1mm = 0.0394 “ / 1” = 25.4mm For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 93 High Speed Fuses North American — FWA 150V: 70-1000A FWA 70-1000A: 150V Time-Current Curve 104 6 4 2 103 6 4 FWA-500A FWA-600A FWA-700A FWA-800A FWA-1000A 2 102 6 4 Virtual Pre-Arcing Time In Seconds 2 Did You Know? 101 6 4 Cooper Bussmann® Equipped Solar Car Wins American Solar Challenge Race 2 100 6 4 2 10–1 6 4 The University of MissouriRolla Solar Car Team won the prestigious American Solar Challenge Race recently with circuit protection provided by Cooper Bussmann FWX series 80 amp semiconductor fuses. FWA-70A FWA-80A FWA-100A FWA-125A FWA-150A 2 10–2 6 4 2 10–3 6 4 FWA-200A FWA-250A FWA-300A FWA-350A FWA-400A 2 10–4 2 102 4 6 8 2 4 6 103 Prospective Current In Amperes RMS 8 The grueling endurance test pitted UM-Rolla’s “Solar Miner IV” against race teams from some of the most famous engineering schools in the nation. By driving approximately 2,300 miles from Chicago to Claremont (a suburb of Los Angeles), in just 51 hours, 47 minutes and 39 seconds, they set a race record by more than four hours. 104 Peak Let-Through Curve 106 6 4 FWA-400A FWA-350A 2 FWA-300A FWA-250A 104 FWA-200A Peak Let-Through Current FWA-150A 6 FWA-100A 4 2 3 10 6 FWA-80A 4 FWA-70A 2 102 2 102 4 6 2 103 4 6 2 104 4 6 2 105 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785310 94 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp High Speed Fuses North American — FWX 250V: 35-2500A FWX Arc Voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Electrical Power Losses Watts loss at rated current is given in the electrical char acteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1.5 K Characteristics 1.0 Total Clearing I t 2 The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 0.5 1) 0.3 0.2 Eg 0.15 75 125 200 250 300 1) 35-800A Range 2) 1000-2500A Range Dimensions (in) Amp Range Fig. A B C 35-60 1 3.19 0.81 1.59 70-200 1 3.13 1.22 1.59 225-600 1 3.84 1.50 1.59 700-800 1 3.84 2.00 1.59 1000-1200 2 2.59 3.00 1.50 1500-2500 3 2.59 3.50 1.50 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-800A D 2.59 2.44 2.94 3.03 — 1.50 E 2.25 2.19 2.25 2.28 — — F 0.34 0.34 0.41 0.41 — — G 0.63 1.00 1.00 1.50 — — Fig. 2: 1000-1200A H 0.13 0.19 0.25 0.25 — — J 0.52 0.47 0.75 0.78 — — Tapped Thread Depth — — — — 3 ⁄8”-24 x 1⁄2” 3 ⁄8”--24 x 1⁄2” Fig. 3: 1500-2500A J A A A D E C D B F G 600 500 400 Catalog Number FWX-35A FWX-40A FWX-45A FWX-50A FWX-60A FWX-70A FWX-80A FWX-90A FWX-100A FWX-125A FWX-150A FWX-175A FWX-200A FWX-225A FWX-250A FWX-275A FWX-300A FWX-350A FWX-400A FWX-450A FWX-500A FWX-600A FWX-700A FWX-800A FWX-1000AH FWX-1200AH FWX-1500AH FWX-1600AH FWX-2000AH FWX-2500AH Rated Current RMS-Amps 35 40 45 50 60 70 80 90 100 125 150 175 200 225 250 275 300 350 400 450 500 600 700 800 1000 1200 1500 1600 2000 2500 C C 1) 300 2) Eg 200 50 100 150 200 250 1) 35-800A Range 2) 1000-2500A Range 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 Ib 0.1 30 40 50 60 Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 250V 50 230 60 310 80 390 100 520 140 740 330 1400 430 1850 570 2450 740 3150 1130 4850 1620 6950 2170 9300 2790 12000 3210 14700 3960 18100 4720 21600 6000 27300 10600 48600 14500 66100 22100 101000 28000 128000 41100 188000 48800 190000 59000 230000 44000 360000 92000 750000 120000 880000 160000 1200000 320000 2300000 670000 4700000 • Watts loss provided at rated current. B 800 Catalog Numbers 2) UL 103 High Speed Fuses Specifications Description: North American style stud-mount and flush-end fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 250Vac Amps: — 35-2500A IR: — 200kA RMS Sym. Agency Information: CE, UL Recognized & CSA Component Acceptance on 35-800A fuses (20kA IR @250Vdc). 1.4 1.2 70 80 90 100% Watts Loss 4.2 5.2 5.7 6.0 8.1 7.2 8.1 9.0 10.0 12.5 15.7 18.5 22 24 27 31 32 39 44 49 54 62 72 84 100 103 140 140 151 163 • See accessories on page 106. Features and Benefits • Excellent dc performance • Low arc voltage and low energy let-through (I2t) • Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters H B For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 95 High Speed Fuses North American — FWX 250V: 35-2500A FWX 35-800A: 250V FWX 1000-2500A(H): 250V Time-Current Curve Time-Current Curve 104 6 4 104 2 103 3 10 FWX-200A FWX-350A FXW-400A FWX-500A FWX-600A FWX-800A 6 4 2 FWX-1000AH FWX-1200AH FWX-1500AH FWX-1600AH FWX-2000AH FWX-2500AH 102 6 4 101 2 100 Virtual Pre-Arcing Time In Seconds Virtual Pre-arcing Time In Seconds 102 FWX-35A FWX-40A FWX-60A FWX-70A FWX-100A FWX-150A 10–1 10–2 10–3 10–4 102 2 103 Prospective Current In Ampere RMS 104 101 6 4 2 100 6 4 2 10–1 6 4 2 10–2 6 4 Peak Let-Through Curve 2 105 –3 10 B 6 4 2 FWX-800A FWX-600A FWX-400A FWX-300A FWX-200A –4 10 2 103 4 6 8 2 4 6 104 Prospective Current In Amperes RMS 8 105 Peak Let-Through Current 104 Peak Let-Through Curve 105 6 FWX-2500AH 4 103 A Peak Let-Through Current FWX-150A FWX-100A FWX-70A FWX-60A FWX-45A FWX-35A FWX-2000AH FWX-1600AH FWX-1500AH FWX-1200AH 2 FWX-1000AH 104 6 4 102 102 103 104 105 Prospective Short-Circuit Current Symmetrical RMS 2 103 103 2 4 6 104 2 4 6 105 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 359 96 Data Sheet: 35785299 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 2 4 6 High Speed Fuses North American — FWH 500V: 35-1600A FWH Arc Voltage 2.0 Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustration. Ratings: Volts: — 500Vac Amps: — 35-1600A IR: — 200kA Sym. — 50kA @ 500Vdc Agency Information: CE, UL Recognition & CSA Component Acceptance on 35-800A only (50kA IR@500Vdc). UL Recognition on 35-1200A only, CSA Component Acceptance: 35-1600A. This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. 1.6 1.5 The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 1.0 Fig. 1 1 1 1 1 1 1 2 C 1.593 1.736 1.836 2.090 2.090 2.090 3.219 1) 0.3 0.2 2) Eg 0.15 100 250 400 500 D 2.541 2.853 2.892 3.440 3.530 4.970 5.465 E 2.193 2.807 2.768 2.750 2.780 3.440 4.475 F 0.344 0.352 0.344 0.410 0.410 0.530 0.625 G 0.719 0.750 1.000 1.000 1.500 2.000 2.375 H 0.125 0.125 0.188 0.250 0.250 0.380 0.438 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-1200A A D E C H G F B J Fig. 2: 1400-1600A 10.219 0.125 0.5 3.219 1) 400 Eg 200 300 400 500 1) 35-200 & 1000-1600A Range 2) 225-800A Range 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 Ib 0.1 30 40 50 J 0.518 0.375 0.406 0.750 0.780 1.300 1.120 Catalog Numbers FWH-35B FWH-40B FWH-45B FWH-50B FWH-60B FWH-70B FWH-80B FWH-90B FWH-100B FWH-125B FWH-150B FWH-175B FWH-200B FWH-225A FWH-250A FWH-275A FWH-300A FWH-325A FWH-350A FWH-400A FWH-450A FWH-500A FWH-600A FWH-700A FWH-800A FWH-1000A FWH-1200A FWH-1400A FWH-1600A Rated Current RMS-Amps 35 40 45 50 60 70 80 90 100 125 150 175 200 225 250 275 300 325 350 400 450 500 600 700 800 1000 1200 1400 1600 60 Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 500V 34 150 76 320 105 450 135 670 210 900 210 900 305 1400 360 1600 475 2000 800 3500 1100 4600 1450 6200 1900 8500 4600 23300 6300 32200 7900 40300 9800 49800 13700 63800 14500 72900 19200 96700 24700 127000 29200 149000 41300 206000 55000 298000 76200 409000 92000 450000 122000 600000 200000 1000000 290000 1400000 • Watts loss provided at rated current. 70 80 90 100% 3.5 0.75 4.25 Watts Loss 8 7.5 7.5 7.5 9.9 10.6 12.7 15 17 25 30 35 40 39 41 46 51 53 58 65 74 84 108 120 129 145 180 210 230 • See accessories on page 106. 0.625 1.625 1.750 6.219 8.969 600 2) 500 Catalog Numbers 0.5 1) 35-800A Range 2) 1000-1600A Range A B 3.188 0.813 3.625 0.947 3.625 1.156 4.340 1.500 4.340 2.000 6.340 2.500 6.969 3.000 See Drawing 800 300 100 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. K Dimensions (in) Amp Range 35-60 70-100 125-200 225-400 450-600 700-800 1000-1200 1400-1600 103 High Speed Fuses Total Clearing I2t 1.2 Power Losses Electrical Characteristics UL Features and Benefits • Excellent dc performance • Low arc voltage and low energy let-through (I2t) • Low watts loss • Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 97 High Speed Fuses North American — FWH 500V: 35-1600A FWH 35-200A(B) & 900-1600A(A): 500V Time-Current Curve 10 FWH 225-800A: 500V Time-Current Curve 103 4 6 4 2 103 6 4 102 FWH-350A FWH-400A FWH-500A FWH-600A FWH-800A 2 102 6 4 101 6 4 2 100 6 4 FWH-80B FWH-90B FWH-100B FWH-125B FWH-150B FWH-175B FWH-200B FWH-35B FWH-40B FWH-45B FWH-50B FWH-60B FWH-70B 2 10–1 6 4 2 Virtual Pre-Arcing Time In Seconds 101 FWH-900A FWH-1000A FWH-1200A FWH-1400A FWH-1600A 2 10–2 6 4 100 10–1 10–2 2 10–3 6 4 10–3 2 10 –4 2 4 6 8 102 2 4 6 8 2 103 Prospective Current In Amper es RMS 4 6 8 104 10–4 102 Peak Let-Through Curve 103 104 Prospective Current In Amperes RMS 105 Peak Let-Through Curve 105 105 B FWH-1600A FWH-1400A 6 FWH-1200A FWH-1000A 4 2 104 Peak Let-Through Current Peak Let-Through Current 104 6 4 2 FWH-800A FWH-600A FWH-500A FWH-400A FWH-300A FWH-250A 3 10 103 FWH-200B 6 FWH-150B FWH-125B 4 FWH-100B A FWH-80B FWH-60B FWH-50B 2 FWH-40B FWH-35B 102 2 2 4 6 3 10 10 2 4 6 4 2 10 4 6 105 2 102 102 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785304 98 103 104 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 360 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 105 High Speed Fuses North American — KAC 600V: 1-1000A KAC Catalog Numbers (-amps) KAC-1 KAC-2 KAC-3 KAC-4 KAC-5 KAC-6 KAC-7 KAC-8 KAC-9 KAC-10 KAC-12 KAC-15 KAC-17.5 KAC-20 Specifications Description: North American style stud-mount fuses. These 600V fuses are supplied as replacements only. For new installations, Cooper Bussmann recommends the 700V FWP series fuse. Dimensions: See Dimensions illustrations. Ratings: Volts: — 600Vac Amps: — 1-1000A IR: — 200kA RMS Sym. Agency Information: CE, UL Recognition on 1-600A only. A 2.875 4.375 5.000 5.140 6.182 6.250 7.250 B1 2.500 — — — — 4.750 4.750 B2 — 3.750 4.063 4.390 4.815 — — B3 C — 1.875 3.5002.750 3.6562.750 3.7662.906 4.5653.000 — 3.063 — 3.063 D 0.406 0.625 0.750 1.000 1.625 2.000 2.750 E F — 0.563 0.3430.813 0.4061.000 0.4061.500 0.5622.000 — 2.500 — 3.500 • • • • Features and Benefits Excellent dc performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High Speed Fuses Fig. 1 2 2 2 2 1 1 KAC-175 KAC-200 KAC-225 KAC-250 KAC-300 KAC-350 KAC-400 KAC-450 KAC-500 KAC-600 KAC-700 KAC-800 KAC-1000 • Consult Cooper Bussmann for dc ratings. • See accessories on page 106. Dimensions (in) Amp Range 1-30A 35-60A 70-100A 110-200A 225-400A 450-800A 1000A KAC-25 KAC-30 KAC-35 KAC-40 KAC-45 KAC-50 KAC-60 KAC-70 KAC-80 KAC-90 KAC-100 KAC-110 KAC-125 KAC-150 G H 0.063 0.257 0.094 0.468 0.125 0.609 0.188 0.718 0.250 0.687 0.250 0.563 0.375 0.563 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 1-30 & 450-1000A A B1 C G D F H Fig. 2: 35-400A A B2 B3 C D G F E H For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 99 High Speed Fuses North American — KBC 600V: 35-800A KBC Catalog Numbers (-amps) Specifications Description: North American style stud-mount and flush-end fuses. These 600V fuses are supplied as replacements only. For new installations, Cooper Bussmann recommends the 700V FWP series fuse. Dimensions: See Dimensions illustrations. Ratings: Volts: — 600Vac Amps: — 35-800A IR: — 200kA RMS Sym. Agency Information: CE, UL Recognition on 35-600A only. KBC-35 KBC-40 KBC-45 KBC-50 KBC-60 KBC-70 KBC-80 KBC-90 KBC-100 KBC-110 KBC-125 KBC-150 KBC-175 KBC-200 KBC-225 KBC-250 KBC-300 KBC-350 KBC-400 KBC-450 KBC-500 KBC-600 KBC-800 • Consult Cooper Bussmann for dc ratings. • See accessories on page 106. • • • • Features and Benefits Excellent dc performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Dimensions (in) Amp Range 35-60A 70-100A 110-200A 225-400A 450-600A 800A Fig. 1 2 1 1 1 3 A B 4.375 3.750 See Drawing 4.406 3.719 5.125 4.188 5.125 4.389 See Drawing C D E F G H I 3.500 2.7500.343 0.625 0.8130.094 0.468 3.594 2.9060.312 0.875 1.2190.187 0.375 3.563 2.9060.406 1.000 1.5000.250 0.719 3.687 2.8750.406 1.500 2.0000.250 0.757 1mm = 0.0394” / 1” = 25.4mm Cooper Bussmann® Paul P. Gubany Center Receives Prestigious ASTA Accreditation Fig. 1: 35-60 and 110-600A A B C D E H F The Cooper Bussmann Paul P. Gubany Center in St. Louis is certified by Britain’s prestigious ASTA (Associated Short Circuit Testing Authority) to perform short testing of its own devices designed to operate to ASTA requirements which are closely tied to IEC requirements. The Gubany Center is the only testing facility available in North or South America for this product certification. G I 0.312 0.750 1.000 0.125 4.406 3.656 2.906 Fig. 2: 70-100A Fig. 3: 800A 4.000 3.750 Did You Know? ‹Ω•" - 24 ≈ ⁄Ω™" 0.750 The Gubany Center has equipment capable of generating 300,000A of current at 600Vac threephase, and 100,000A at 170Vdc, under carefully controlled conditions. It offers a wider range of current voltage and frequency configurations than any other facility of its kind in the world, and is built to exceed the short circuit capacity of today’s high power electrical distribution systems. 2.500 2.859 0.750 100 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp High Speed Fuses North American — FWP 700V: 5-1200A FWP Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustrations. Ratings: Volts: — 700Vac Amps: — 5-1200A IR: — 200kA RMS Sym. — 50kA @700Vdc Agency Information: CE, UL Recognition & CSA Component Acceptance on 5-800A A B 2.870 0.563 4.375 0.813 4.406 0.947 5.090 1.500 5.090 2.000 7.090 2.500 6.630 2.000 See Drawing See Drawing C 1.855 2.750 2.594 2.840 2.840 2.840 2.844 K 1.0 2) 1) 0.3 0.2 3) Eg 0.15 316 460 F 0.250 0.344 0.344 0.410 0.410 0.530 0.625 Fig. 2: 900-1000A 604 700 G H 0.4050.063 0.7250.125 0.7500.125 1.0000.250 1.5000.250 2.0000.380 1.5000.250 I 0.250 0.542 0.375 0.750 0.780 1.300 0.875 Fig. 3: 1200A 3.500 1.375 0.125 J 0.500 5.966 7.594 A D E C 9.590 6.840 3.844 0.625 1.031 2.750 0.5 3.500 H B Eg 300 400 500 600 0.750 4.250 Catalog Numbers FWP-5B FWP-10B FWP-15B FWP-20B FWP-25B FWP-30B FWP-35B FWP-40B FWP-50B FWP-60B FWP-70B FWP-80B FWP-90B FWP-100B FWP-125A FWP-150A FWP-175A FWP-200A FWP-225A FWP-250A FWP-300A FWP-350A FWP-400A FWP-450A FWP-500A FWP-600A FWP-700A FWP-800A FWP-900A FWP-1000A FWP-1200A Rated Current RMS-Amps 5 10 15 20 25 30 35 40 50 60 70 80 90 100 125 150 175 200 225 250 300 350 400 450 500 600 700 800 900 1000 1200 700 1) 125-600A Range 2) 35-100 & 700-1200A Range 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 Ib 30 40 50 60 Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 700V 1.6 10 3.6 20 10 75 26 180 44 340 58 450 34 160 76 320 135 600 210 950 305 2000 360 2400 415 2700 540 3500 1800 7300 2900 11700 4200 16700 5500 22000 7700 31300 10500 42500 17600 71200 23700 95600 31000 125000 36400 137000 45200 170000 66700 250000 54000 300000 78000 450000 91500 530000 120000 600000 195000 1100000 70 80 90 100% Watts Loss 1.5 4 5.5 6 7 9 12 12 12 15.5 18 21 25 27 28 32 35 43 45 48 58 65 78 94 107 122 125 140 150 170 190 • Watts loss provided at rated current. • See accessories on page 106. 1.625 1.750 0.625 G 3.844 10.844 5.154 F 6 5 Catalog Numbers 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 5-800A 2) 8 0.1 0.5 D E 2.4772.477 3.7083.312 3.6253.563 4.1903.500 4.2803.530 5.7204.190 5.5625.062 1) High Speed Fuses 1.5 Dimensions (in) Fig. 1 1 1 1 1 1 1 2 3 UL 3 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. 1) 35-100A Range 2) 125-600A Range 3) 700-1200A Range Amp Range 5-30 35-60 70-100 125-200 225-400 450-600 700-800 900-1000 1200 1.6 1.4 1.2 103 4 2 The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2 This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Power Losses Electrical Characteristics Total Clearing I t Arc Voltage Features and Benefits • Excellent dc performance • Low arc voltage and low energy let-through (I2t) • Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 101 High Speed Fuses North American — FWP 700V: 5-1200A FWP 5-30A(B): 700V FWP 35-100A(B) & 700-1200A(A): 700V Time-Current Curve Time-Current Curve 104 6 4 104 6 4 2 2 103 103 6 4 6 4 2 2 6 4 6 4 2 Virtual Pre-Arcing Time In Seconds Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 100 6 4 FWP-5B FWP-10B FWP-15B FWP-20B FWP-25B FWP-30B 2 10–1 6 4 101 6 4 FWP-35B FWP-40B FWP-50B FWP-60B FWP-70B FWP-80B FWP-90B FWP-100B 2 100 6 4 2 10–1 6 4 2 2 10–2 6 4 10–2 6 4 2 10–3 2 6 4 10–3 6 4 2 10–4 2 10–4 FWP-700A FWP-800A FWP-900A FWP-1000A FWP-1200A 102 102 2 4 6 8 101 2 4 6 8 2 102 4 6 8 2 4 6 8 102 103 2 4 6 8 2 103 Prospective Current In Amperes RMS 4 6 8 104 Prospective Current In Amperes RMS Peak Let-Through Curve Peak Let-Through Curve 106 104 FWP-1200A 6 FWP-1000A 6 FWP-800A 4 4 FWP-700A 2 FWP-30B FWP-25B 2 104 6 4 Peak Let-Through Current Peak Let-Through Current 10 3 2 10 FWP-20B FWP-15B FWP-10B FWP- 5B 2 6 4 6 4 2 103 2 6 FWP-100B 4 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 105 FWP-70B 2 FWP-60B Prospective Short-Circuit Current FWP-50B 2 FWP-40B FWP-35B 102 2 4 6 102 2 103 4 6 2 104 Prospective Short-Circuit Current Data Sheet: 35785316 102 Data Sheet: 35785308 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 4 2 6 105 High Speed Fuses North American — FWP 700V: 5-1200A FWP 125-600A: 700V Time-Current Curve 103 102 Did You Know? Cooper Bussmann Named First in Fuses by Readers of Plant Services Magazine 100 High Speed Fuses Virtual Pre-Arcing Time In Seconds 10 FWP-150A FWP-200A FWP-300A FWP-400A FWP-600A 1 10–1 10–2 10–3 10–4 102 103 104 105 Prospective Current In Amperes RMS Peak Let-Through Curve Cooper Bussmann has been named as the vendor offering the highest value in electrical fuses in a recent fill-in-the-blank survey of nearly 40,000 qualified readers of Plant Services Magazine. A full 70 percent of survey respondents said Cooper Bussmann was their number one choice. The nearest competitor weighed in at only 7 percent. The 63 percent spread was the widest of all 63 product categories, ranging from aerial work platforms to welding equipment. According to Plant Services editors, the products chosen are those “that deliver the combination of functionality, durability and low maintenance that add up to the lowest estimated life-cycle cost”—those offering the very best value in their product category. 105 B Peak Let-Through Current 104 FWP-600A FWP-400A FWP-300A FWP-200A FWP-150A 103 A 102 102 103 104 105 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 361 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 103 High Speed Fuses North American — FWJ 1000V: 35-2000A FWJ Arc Voltage Specifications Description: North American style stud-mount fuses. Dimensions: See Dimensions illustration. Ratings: Volts: — 1000Vac Amps: — 35-200A IR: — 25kA (35-200A) — 100kA (250-2000A) — 50kA @ 800Vdc (450600A) Agency Information: CE, UL Recognition on 35-600A only. 1.5 B 0.940 1.125 1.526 2.000 2.500 3.500 C 3.110 3.085 3.261 3.500 3.465 3.312 K 600 1000 1400 1800 Kp Ib 60 70 80 90 100% Catalog Numbers 1.0 0.5 0.3 0.2 Eg 500 800 1000 D E 4.2354.180 4.2664.156 4.8034.055 4.8114.150 5.9844.706 5.4724.962 F 0.352 0.352 0.445 0.433 0.562 0.625 G H 0.7500.125 1.0000.188 1.0000.250 1.5000.250 2.0000.375 2.7500.500 I 0.380 0.407 0.819 0.764 1.201 0.880 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-2000A A D E C H G F B J 104 400 30 40 50 Dimensions (in) A 5.000 4.932 5.685 5.768 7.201 6.811 800 Eg Watts loss at rated current is given in the electrical char- 1.0 0.8 acteristics. The curve allows the calculation of the 0.6 0.5 power losses at load cur0.4 rents lower than the rated current. The correction fac- 0.3 tor, Kp, is given as a func- 0.2 tion of the RMS load current, Ib, in % of the rated current. 0.1 0.15 200 Fig. 1 1 1 1 1 1 1200 200 Total Clearing I2t Amp Range 35-60 70-100 125-200 250-400 500-600 800-2000 UL 1600 Power Losses Electrical Characteristics The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2000 This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Catalog Numbers FWJ-35A FWJ-40A FWJ-50A FWJ-60A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-125A FWJ-150A FWJ-175A FWJ-200A FWJ-250A FWJ-300A FWJ-350A FWJ-400A FWJ-500A FWJ-600A FWJ-800A FWJ-1000A FWJ-1200A FWJ-1400A FWJ-1600A FWJ-1800A FWJ-2000A Rated Current RMS-Amps 35 40 50 60 70 80 90 100 125 150 175 200 250 300 350 400 500 600 800 1000 1200 1400 1600 1800 2000 Electrical Characteristics I2t (A2 Sec) Clearing Pre-arc at 1000V 210 2000 300 2500 470 3500 670 5000 1100 6900 1550 9700 1900 12000 2800 17500 4800 35000 6300 45000 7500 65000 11700 80000 16000 112000 23500 164000 33000 231000 47000 330000 39500 329000 61000 520000 87000 500000 190000 1100000 370000 2100000 470000 2700000 700000 4000000 925000 5300000 1330000 7600000 • Watts loss provided at rated current. • See accessories on page 106. • • • • Features and Benefits Excellent dc performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability • • • • Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp Watts Loss 7 8 10 11 12 13 14 15 16 25 30 32 50 56 62 67 95 105 182 206 240 248 267 239 244 High Speed Fuses North American — FWJ 1000V: 35-2000A FWJ 35-600A: 1000V FWJ 800-2000A: 1000V Time-Current Curve Time-Current Curve 104 104 6 4 6 4 2 2 103 103 6 4 6 4 2 2 102 102 101 2 100 6 4 FWJ-800A FWJ-1000A FWJ-1200A FWJ-1400A FWJ-1600A FWJ-1800A FWJ-2000A 2 101 6 4 High Speed Fuses 6 4 Virtual Pre-Arcing Time In Seconds 2 Virtual Pre-Arcing Time In Seconds 6 4 FWJ-200A FWJ-250A FWJ-300A FWJ-350A FWJ-400A FWJ-500A FWJ-600A 6 4 2 100 6 4 2 10–1 2 6 4 10–1 6 4 2 10–2 6 4 2 10–3 2 FWJ-40A FWJ-50A FWJ-60A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-125A FWJ-150A FWJ-175A 10–2 6 4 2 10–3 6 4 2 6 4 10–4 2 2 4 6 8 2 103 4 6 8 104 2 4 6 8 105 Prospective Current In Amperes RMS 10–4 2 102 4 6 8 2 103 4 6 8 104 Prospective Current In Amperes RMS Peak Let-Through Curve Peak Let-Through Curve 2 2 105 6 4 Peak Let-Through Current 2 10 4 6 4 2 103 6 4 2 10 4 6 4 2 103 6 6 4 4 2 10 FWJ-2000A FWJ-1800A FWJ-1600A FWJ-1400A FWJ-1250A FWJ-1000A FWJ-600A FWJ-800A FWJ-400A FWJ-500A FWJ-350A FWJ-300A FWJ-250A FWJ-200A FWJ-175A FWJ-150A FWJ-125A FWJ-100A FWJ-90A FWJ-80A FWJ-70A FWJ-60A FWJ-50A FWJ-40A 105 Peak Let-Through Current FWJ-2000A FWJ-1800A FWJ-1600A FWJ-1400A FWJ-1250A FWJ-1000A FWJ-600A FWJ-800A FWJ-400A FWJ-500A FWJ-350A FWJ-300A FWJ-250A FWJ-200A FWJ-175A FWJ-150A FWJ-125A FWJ-100A FWJ-90A FWJ-80A FWJ-70A FWJ-60A FWJ-50A FWJ-40A 2 2 102 2 4 6 2 103 4 6 104 2 4 6 105 2 4 6 10 2 102 2 4 6 103 2 4 6 104 2 4 6 105 2 4 6 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785303 Data Sheet: 35785309 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 105 High Speed Fuses North American fuse accessories Fuse Bases (Blocks) Modular Style Cooper Bussmann offers a comprehensive line of fuse bases that provide the user with design and manufacturing flexibility. Two identical half bases make up a Cooper Bussmann® modular fuse base. These “split” units can be panel mounted any distance apart to accommodate any length fuse. Stud Type Stud Type The simpler design is the C5268 series modular fuse base. With this design, the fuse terminal and cable (with termination) are mounted on the same stud, minimizing labor needed for installation. The stud type base is available in the configuration shown in the table below. Catalog Max Fuse Stud Stud Dia. Number Amp Rating Height (in) & Threads 5 C5268-1 200 1.00 ⁄16”-18 5 C5268-2 200 1.75 ⁄16”-18 5 C5268-3 200 0.75 ⁄16”-18 1 C5268-4 100 1.00 ⁄4”-20 1 C5268-5 100 1.75 ⁄4”-20 Connector Type Connector Type Cooper Bussmann also offers a modular style fuse base that utilizes a tin-plated connector (for wire termination and heat dissipation) and a plated-steel stud (for fuse mounting). The connector type fuse base is available in the configurations shown below. Consult Cooper Bussmann for additional product details. Modular Max Max Fuse Data Sheet Base Style Voltage Amp Rating Number 1BS101 600 100 1206 1BS102 600 400 1207 1BS103 600 400 1208 1BS104 600 600 1209 BH-0xxx 700 100 1200 BH-1xxx 2500 400 1201 BH-2xxx 5000 400 1202 BH-3xxx 1250 700 1203 Fixed Center Base Style Cooper Bussmann offers a comprehensive line of fixed mount style fuse bases under the trademark TRON® rectifier fuse blocks. The cable and fuse connections are similar to the stud type fuse base — both are mounted on the same stud. Consult Cooper Bussmann for complete product details. 106 Fixed Center For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp