GENERAL C3362

Product Data Sheet
Part Number: C3362
Revision Level:
0
2P 18 7/26 BC FLEX OAS PVDF
Date:
TYPE CL2P / CMP
A. CONSTRUCTION
Conductor:
Insulation:
Pairing
Cable:
Jacket:
Print Legend:
DIAMETERS
#18 AWG 7/36 Bare Copper
0.047” nom.
0.063" nom.
0.008" Wall FLEXGUARD*
4 conductors into 2 pairs @ 1.50” LHL.
2 pairs @ 2.50” LHL, aluminum/polypro (foil in)
0.185" nom.
& # 22 7/30 TC drain wire.
0.010"Wall PVDF – Natural
0.205" +/- 0.010"
-Plenum ripcord under jacket.
CAROL (R) 18 AWG -- C3362 -- 60C E60233-8 CL2P OR CMP(UL)C(UL) -- MADE IN USA
DATE CODE (PRINT EVERY 2 FT)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 13
Article 725
Type CL2P
National Electrical Code
UL Standard 444
Article 800
Type CMP
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
D. COLOR CODE
1
2
75C
150 Vrms (CL2P); 300 Vrms (CMP)
5.6 Ohms/1000 ft. nom. @ 20C
(Listed as Individual Conductors or Pairs of Conductors)
Black & Yellow
Red & Purple
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.
*FLEXGUARD is a trademark of General Cable Corporation for polymer alloy insulation and jackets.
7/7/2007