GENERAL C3215

Product Data Sheet
Part Number: C3215
Revision Level:
2
3P 24 7/32 TC FEP OAS PVDF
Date:
TYPE CMP, SHIELDED
A. CONSTRUCTION
Conductor:
Insulation:
Pairing
Cable:
Jacket:
Print Legend:
DIAMETERS
#24 AWG 7/32 Tinned Copper
0.024” nom.
0.045" nom.
0.011" Wall FEP
6 conductors into 3 pairs @ 1.50” LHL.
0.088" NOM.
3 pairs @ 2.50” LHL, aluminum/polypro (foil in)
0.157" nom.
& # 24 7/32 TC drain wire.
0.010"Wall PVDF – Natural
0.177" +/- 0.008"
-Plenum ripcord under jacket.
CAROL (R) 24 AWG -- C3215 -- 150C E111240-8 CMP (UL) C(UL) -- MADE IN USA
DATE CODE (PRINT EVERY 2 FT)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 444
Article 800
Type CMP (UL) C(UL)
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
D. COLOR CODE
1
2
3
150 C
300 Vrms
25.7 Ohms/1000 ft. nom. @ 20C
(Listed as Individual Conductors or Pairs of Conductors)
Black & Yellow
Red & Purple
Dark Blue & Brown
Note: Data are subject to change without notice. Contact your Customer Service representative for latest information.
*FLEXGUARD is a trademark of General Cable Corporation for polymer alloy insulation and jackets.