Description: A. Tinned Copper conductor, FEP Insulation, Individually shielded pairs, and overall Plenum PVC Jacketed Plenum Cable. Construction: 1.0 Primaries: 1.1 1.2 B. R E V Conductor: AWG Stranding Nom. Dia Insulation: Material Nom. thickness Nom. OD 22 AWG 7/30 Tinned Copper; .030" FEP .010” .050" 2.0 Pair construction: 2.1 Shield: 2.2 Drain Wire: 2.3 No. of Pairs 2.4 Pair Color Code: Two insulated conductors twisted together Aluminum/Polyester Tape; 100% coverage; (Aluminum Side IN) 22 AWG ( 7/30 ) Tinned Copper 3 Black & Red Black & White Black & Green 3.0 Overall Cabling: Three pairs cabled 4.0 Jacket Plenum PVC 5.0 Overall Diameter of Cable Nom. 6.0 Marking: Characteristics: 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 Conductor DC Resistance @20C Max. (Ohm): Capacitance between conductors Nom. (pF/ft): Capacitance Cond. To other Cond.& Shield Nom. (pF/ft): Inductance Nom. (µH/ft): Characteristic Impedance Nom.(Ohms): Velocity of Propagation Nom. : Operating Voltage Nom.: Continuous Operating Temp: Min. Bend Radius (inches): Max. Pulling Tension Lbs: DATE Material: Nom. wall: .018” Color: TBD .237” Surface Print: GENERAL CABLE (F) C8131 3PR 22 AWG SHIELDED CMP (UL) C(UL) ---- ROHS AAAAA* * Indicates Shop Order number 16 35 76 .18 46 62 300 V 75C 2.4 75 CHANGE DETAIL General Cable 20 Forge Park, Franklin, Ma 02038 Phone: 508-541-7100 Fax: 508-541-8122 Title: C8131 Description: 3 PR 22 AWG Shielded Plenum Cable Created By: A 05/19/09 Initial Release -VM Final Approval: VM 5/19/09 PAGE 1 of 1 General Cable reserves the right to modify this information without prior notification and does not make a warranty or representation of any kind, whether implied or expressed with respect to the information contained herein. General Cable assumes no risks, and will not be liable for direct or indirect, special; incidental or consequential damages, any defect or personal injury resulting from the use of this document. C. Approvals: R E V DATE UL –CMP ; C(UL) CMP CHANGE DETAIL General Cable 20 Forge Park, Franklin, Ma 02038 Phone: 508-541-7100 Fax: 508-541-8122 Title: C8131 Description: 3 PR 22 AWG Shielded Plenum Cable Created By: A 05/19/09 Initial Release -VM Final Approval: VM 5/19/09 PAGE 2 of 1 General Cable reserves the right to modify this information without prior notification and does not make a warranty or representation of any kind, whether implied or expressed with respect to the information contained herein. General Cable assumes no risks, and will not be liable for direct or indirect, special; incidental or consequential damages, any defect or personal injury resulting from the use of this document.