SIEMENS 3RT20261BB40

Product data sheet
3RT2026-1BB40
CONTACTOR, AC-3, 11KW/400V, 1NO+1NC,
DC 24V, 3-POLE, SZ S0 SCREW TERMINAL
General technical data:
product brand name
SIRIUS
Size of the contactor
S0
Product extension / auxiliary switch
Yes
Protection class IP / on the front
IP20
Protection against electrical shock
finger-safe
Degree of pollution
3
Installation altitude / at a height over sea level / maximum
m
2,000
• during storage
°C
-55 … +80
• during operating
°C
-25 … +60
Ambient temperature
Shock resistance
• at rectangular impulse
• at DC
10g / 5 ms, 7,5g / 10 ms
• at sine pulse
• at DC
15g / 5 ms, 10g / 10 ms
Impulse voltage resistance / rated value
kV
6
Insulation voltage / rated value
V
690
Mechanical operating cycles as operating time
• of the contactor / typical
3RT2026-1BB40
Page 1/ 7
10,000,000
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
• of the contactor with added auxiliary switch block / typical
10,000,000
• of the contactor with added electronics-compatible auxiliary
switch block / typical
5,000,000
Main circuit:
Number of NC contacts / for main contacts
0
Number of NO contacts / for main contacts
3
Operating current
• at AC-1 / at 400 V
• at 40 °C ambient temperature / rated value
A
40
• at 60 °C ambient temperature / rated value
A
35
• at AC-2 / at 400 V / rated value
A
25
• at AC-3 / at 400 V / rated value
A
25
• at AC-4 / at 400 V / rated value
A
15.5
• at 24 V / rated value
A
35
• at 110 V / rated value
A
4.5
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at 24 V / rated value
A
20
• at 110 V / rated value
A
2.5
• at 24 V / rated value
A
35
• at 110 V / rated value
A
15
• at 24 V / rated value
A
35
• at 110 V / rated value
A
35
• at AC-2 / at 400 V / rated value
kW
11
• at AC-3 / at 400 V / rated value
kW
11
• at AC-4 / at 400 V / rated value
kW
7.5
W
1.6
1/h
5,000
Operating current
• with 1 current path / at DC-1
• with 2 current paths in series / at DC-1
• with 3 current paths in series / at DC-1
• with 1 current path / at DC-3 / at DC-5
• with 2 current paths in series / at DC-3 / at DC-5
• with 3 current paths in series / at DC-3 / at DC-5
Service power
Active power loss / per conductor / typical
Off-load operating frequency
• at AC
3RT2026-1BB40
Page 2/ 7
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
• at DC
1/h
1,500
Frequency of operation / at AC-1 / according to IEC 60947-6-2
1/h
1,000
Frequency of operation / at AC-2 / according to IEC 60947-6-2
1/h
750
Frequency of operation / at AC-3 / according to IEC 60947-6-2
1/h
750
Frequency of operation / at AC-4 / according to IEC 60947-6-2
1/h
250
Control circuit:
Type of voltage / of the controlled supply voltage
DC
Control supply voltage / 1
• for DC / rated value
V
24
Operating range factor control supply voltage rated value / of
the magnet coil
• for DC
0.8 … 1.1
Pull-in power / of the solenoid / for DC
W
5.9
Holding power / of the solenoid / for DC
W
5.9
ms
50 … 170
• at DC
ms
15 … 17.5
Arcing time
ms
10 … 10
Closing delay
• at DC
Opening delay
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts / instantaneous
switching
1
Number of NO contacts / for auxiliary contacts / instantaneous
switching
1
Operating current / of the auxiliary contacts
• at AC-12 / maximum
A
10
• at 230 V
A
10
• at 400 V
A
3
• at 48 V
A
6
• at 60 V
A
6
• at 110 V
A
3
• at 220 V
A
1
• at 24 V
A
10
• at 48 V
A
2
• at 60 V
A
2
• at AC-15
• at DC-12
• at DC-13
3RT2026-1BB40
Page 3/ 7
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
• at 110 V
A
1
• at 220 V
A
0.3
Short-circuit:
Design of the fuse link
• for short-circuit protection of the auxiliary switch / required
fuse gL/gG: 10 A
• for short-circuit protection of the main circuit
• with type of assignment 1 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
100 A
• at type of coordination 2 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
35A
Installation/mounting/dimensions:
mounting position
+/-180° rotation possible on vertical mounting surface;
can be tilted forward and backward by +/- 22.5° on
vertical mounting surface
Type of mounting
screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
Type of fixing/fixation / series installation
Yes
Width
mm
45
Height
mm
85
Depth
mm
107
Distance, to be maintained, to the ranks assembly / sidewards
mm
0
Distance, to be maintained, to earthed part / sidewards
mm
6
Connections:
Design of the electrical connection
• for main current circuit
screw-type terminals
• for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• solid
2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
• finely stranded
• with conductor end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
• for AWG conductors / for main contacts
2x (16 ... 12), 2x (14 ... 8)
• for auxiliary contacts
• solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• finely stranded
• with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
Certificates/approvals:
3RT2026-1BB40
Page 4/ 7
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
General Product Approval
Declaration of Conformity
Test Certificates
other
Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
Shipping Approval
other
Confirmation
UL/CSA ratings:
yielded mechanical performance (hp)
• for single-phase squirrel cage motors
• at 110/120 V / rated value
hp
2
• at 230 V / rated value
hp
3
• at 200/208 V / rated value
hp
5
• at 220/230 V / rated value
hp
7.5
• at 460/480 V / rated value
hp
15
• at 575/600 V / rated value
hp
20
• at 480 V / rated value
A
21
• at 600 V / rated value
A
22
• for three-phase squirrel cage motors
Operating current (FLA) / for three-phase squirrel cage motors
Contact rating designation / for auxiliary contacts / according to
UL
A600 / Q600
Sicherheitsrelevante Kenngrößen:
B10 value / with high demand rate
• according to SN 31920
1,000,000
T1 value / for proof test interval or service life
• according to IEC 61508
a
20
• with low demand rate / according to SN 31920
%
40
• with high demand rate / according to SN 31920
%
73
Proportion of dangerous failures
Failure rate (FIT value) / with low demand rate
3RT2026-1BB40
Page 5/ 7
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
• according to SN 31920
FIT
100
Product function
• mirror contact to IEC 60947-4-1
Yes
• positively driven operation to IEC 60947-5-1
No
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator:
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RT2026-1BB40/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT2026-1BB40
3RT2026-1BB40
Page 6/ 7
07/27/2012
subject to modifications
© Copyright Siemens AG 2012
last change:
3RT2026-1BB40
Page 7/ 7
Jul 26, 2012
07/27/2012
subject to modifications
© Copyright Siemens AG 2012