Type 2 Co-ordination acc. UL 60947-4-1 Manual Mtr. Ctrl. Cat.No. 3RT2.1 3RT2025-1.... 3RT2026-1.... 3RT2026-4.... 3RT2026-2.... 3RT2026 3RT2027 3RT2027-1.... 3RT2027-2.... 3RT2028 3RT2028-1.... 3RT2028-1.... Comb. Mtr. Ctrl. C.B. / Thermal Magnetic Bkr TM Bkr TM 3RV1742 3RV27, 3RV28 2A 2A 3.2 A 8A 8A - 3RV2.23 - 3RV2025) 2 A 6) 2 A 6) 3.2 A 8A 6.3 A - 6.3 A 5A - 6.3 A - 25 A2) 4) 40 A1) 3) 25 A2) 4) 40 A1) 3) - 12.5 A 32 A 25 A 12.5 A 32 A 25 A - 20 A 20 A - 15 A 12.5 A 22 A 15 A 12.5 A 22 A 15 A - 1) Branch Circuit Protective Device: The appropriate BCPD need to be determined in accordance with the National Electrical Co Fuses: Classes RK1, RK5, J, G, T, CC or Circuit breakers: Listed Siemens type, with a marked short-circuit rating equal or higher than the available short-circuit current ra These devices were tested for group installation use at the above levels without any upstream branch circuit device. 2) Siemens Listed Manual Motor Controller type 3RV2.23 3) Siemens Listed Manual Motor Controller type 3RV2.21 4) Branch Circuit Protective Device: Max. Fuse Size 100 A, Class J These devices were tested for group installation use at the above levels with Branch Circuit Protective Device Class J Fuses Ra 5) The 3RV2.1 or 3RV2.2 in combination with contactors 3RT2 are also evaluated as Combination Motor Controllers Type F 6) 3RV20.1 can be applied too. 7) Class J or Class CC fuses only Fuses RK1, RK5, J, G, T, CC 15 A 7) 35 A 25 A 50 A 40 A 50 A 40 A SCCR 100 kA 10 kA 30 kA 65 kA 65 kA 10 kA 10 kA 65 kA 30 kA 100 kA 10 kA 65 kA 30 kA 100 kA 65 kA 10 kA 30 kA 50 kA 65 kA 12 kA 100 kA 100 kA 10 kA 30 kA 50 kA 65 kA 12 kA 100 kA 100 kA Voltage 600 V 600 V 600 V 480 V 480 V 600 V 600 V 480 V 600 V 600 V 600 V 480 V 600 V 600 V 480 V 600 V 600 V 480 V 480 V 480 V 600 V 600 V 600 V 600 V 480 V 480 V 480 V 600 V 600 V ccordance with the National Electrical Code, Article 430-53 and the application. The following devices are permitted: than the available short-circuit current rating stream branch circuit device. rcuit Protective Device Class J Fuses Rated Max. 100 A. ombination Motor Controllers Type F Type 2 Co-ordination acc. UL 60947-4-1 Contactor Overload relay 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1015 3RT1016 3RT1016 3RT1016 3RT1024 3RT1025 3RT1025 3RT1026 3RT1026 3RT1026 3RT1026 3RT1026 3RT1033 3RT1034 3RT1035 3RT1044 3RT1044 3RT1045 3RT1046 3RT1054 3RT1054 3RT1055 3RT1055 3RT1056 3RT1056 3RT1065 3RT1066 3RT1076 3RT1076 3RU1116-0F 3RU1116-0G 3RU1116-0H 3RU1116-0J 3RU1116-0K 3RU1116-1A 3RU1116-1B 3RU1116-1C 3RU1116-1D 3RU1116-1E 3RU1116-1F 3RU1116-1G 3RU1116-1H 3RU1116-1H 3RU1116-1J 3RU1116-1J 3RU1126-1K 3RU1126-4A 3RU1126-4B 3RU1126-4C 3RU1126-4C 3RU1126-4D 3RU1126-4D 3RU1126-4D 3RU1136-4E 3RU1136-4F 3RU1136-4G 3RU1146-4J 3RU1146-4K 3RU1146-4L 3RU1146-4M 3RB1056-1FW0 3RB1056-1FG0 3RB1056-1FW0 3RB1056-1FG0 3RB1056-1FW0 3RB1056-1FG0 3RB1066-1G 3RB1066-1K 3RB1066-1K 3RB1066-1K Fuse Class J [A] SCCR 1 1 1 2 2 2 3 3 6 6 8 10 15 15 15 15 20 25 30 40 40 30 50 50 60 60 70 90 125 175 200 250 250 300 300 300 300 400 400 500 500 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 65 kA 100 kA 100 kA 65 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA 100 kA Voltage 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 480 600 600 480 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 Type 2 Co-ordination acc. UL 60947-4-1 Circuit Breaker (TM) Size Current range SCCR Voltage 3RV27,3RV28 S00 1.6 – 16 A (3RR2..1) S0 (3RR2..2) 4 – 40 A 22 A 50 kA 480 V 15 A 12.5 A 65 kA 10 kA 480 V 600 V 15 A 65 kA 480 V 22 A 50 kA 480 V 12.5 A 10 kA 600 V Type 2 Co-ordination acc. UL 60947-4-1A High Capacity Short Circuit Ratings with Fuses, Type 2 co-ordination according UL 60947-4-1A Current range Max. Fuse Fuse Classes 3 – 12 A 4 – 16 A 6 – 25 A 10 – 40 A 45 A 60 A 100 A 160 A J J J J 4 – 16 A 6 – 25 A 10 – 40 A 60 A 90 A 90 A J J J Size S0 (3RB3.2) S00 (3RB3.1) Setting Ranges and Short Circuit ratings Circuit Breaker, Type 2 co-ordination according UL 60947-4-1A Current range Circuit Breaker Short Voltage 5SJ…1) Circuit 1–4A 15 A 5 kA 480 V 3 – 12 A 40 A 5 kA 480 V 4 – 16 A 40 A 5 kA 480 V 6 – 25 A 40 A 5 kA 480 V 10 – 40 A 40 A 5 kA 480 V 1) Siemens listed Circuit Breaker Type 5SJ43…-7HG42 (max. 40A) High Capacity Short Circuit Ratings Type 2 co-ordination according UL 60947-4-1A Current range 0.1 – 0.4 A 0.32 – 1.25 A Circuit Breaker (TM) 3RV27, 3RV28 Short Circuit Voltage - - - 3.2 A 65 kA 480 V 3.2 A 10 kA 30 kA 65 kA 10 kA 50 kA 65 kA 600 V 600 V 480 V 600 V 480 V 480 V 1–4A 15 A 12.5 A 3 – 12 A 22 A 15 A 12.5 A 4 – 16 A 22 A 15 A 12.5 A 6 – 25 A 22 A 15 A 12.5 A 10 – 40A 15 A 22 A 12.5 A 10 kA 50 kA 65 kA 10 kA 50 kA 65 kA 10 kA 65 kA 50 kA 10 kA 600 V 480 V 480 V 600 V 480 V 480 V 600 V 480 V 480 V 600 V ination according UL 60947-4-1A SCCR Voltage 100 kA 100 kA 100 kA 100 kA 600 V 600 V 600 V 600 V 100 kA 100 kA 100 kA 600 V 600 V 600 V dination according UL 60947-4-1A