UL60947-4-1 Type 2 Coordination Technical Ratings

Type 2 Co-ordination acc. UL 60947-4-1
Manual Mtr. Ctrl.
Cat.No.
3RT2.1
3RT2025-1....
3RT2026-1....
3RT2026-4....
3RT2026-2....
3RT2026
3RT2027
3RT2027-1....
3RT2027-2....
3RT2028
3RT2028-1....
3RT2028-1....
Comb. Mtr. Ctrl.
C.B. /
Thermal Magnetic
Bkr TM
Bkr TM
3RV1742
3RV27, 3RV28
2A
2A
3.2 A
8A
8A
-
3RV2.23
-
3RV2025)
2 A 6)
2 A 6)
3.2 A
8A
6.3 A
-
6.3 A
5A
-
6.3 A
-
25 A2) 4)
40 A1) 3)
25 A2) 4)
40 A1) 3)
-
12.5 A
32 A
25 A
12.5 A
32 A
25 A
-
20 A
20 A
-
15 A
12.5 A
22 A
15 A
12.5 A
22 A
15 A
-
1) Branch Circuit Protective Device: The appropriate BCPD need to be determined in accordance with the National Electrical Co
Fuses: Classes RK1, RK5, J, G, T, CC or
Circuit breakers: Listed Siemens type, with a marked short-circuit rating equal or higher than the available short-circuit current ra
These devices were tested for group installation use at the above levels without any upstream branch circuit device.
2) Siemens Listed Manual Motor Controller type 3RV2.23
3) Siemens Listed Manual Motor Controller type 3RV2.21
4) Branch Circuit Protective Device: Max. Fuse Size 100 A, Class J
These devices were tested for group installation use at the above levels with Branch Circuit Protective Device Class J Fuses Ra
5) The 3RV2.1 or 3RV2.2 in combination with contactors 3RT2 are also evaluated as Combination Motor Controllers Type F
6) 3RV20.1 can be applied too.
7) Class J or Class CC fuses only
Fuses
RK1, RK5, J, G, T,
CC
15 A 7)
35 A
25 A
50 A
40 A
50 A
40 A
SCCR
100 kA
10 kA
30 kA
65 kA
65 kA
10 kA
10 kA
65 kA
30 kA
100 kA
10 kA
65 kA
30 kA
100 kA
65 kA
10 kA
30 kA
50 kA
65 kA
12 kA
100 kA
100 kA
10 kA
30 kA
50 kA
65 kA
12 kA
100 kA
100 kA
Voltage
600 V
600 V
600 V
480 V
480 V
600 V
600 V
480 V
600 V
600 V
600 V
480 V
600 V
600 V
480 V
600 V
600 V
480 V
480 V
480 V
600 V
600 V
600 V
600 V
480 V
480 V
480 V
600 V
600 V
ccordance with the National Electrical Code, Article 430-53 and the application. The following devices are permitted:
than the available short-circuit current rating
stream branch circuit device.
rcuit Protective Device Class J Fuses Rated Max. 100 A.
ombination Motor Controllers Type F
Type 2 Co-ordination acc. UL 60947-4-1
Contactor
Overload relay
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1015
3RT1016
3RT1016
3RT1016
3RT1024
3RT1025
3RT1025
3RT1026
3RT1026
3RT1026
3RT1026
3RT1026
3RT1033
3RT1034
3RT1035
3RT1044
3RT1044
3RT1045
3RT1046
3RT1054
3RT1054
3RT1055
3RT1055
3RT1056
3RT1056
3RT1065
3RT1066
3RT1076
3RT1076
3RU1116-0F
3RU1116-0G
3RU1116-0H
3RU1116-0J
3RU1116-0K
3RU1116-1A
3RU1116-1B
3RU1116-1C
3RU1116-1D
3RU1116-1E
3RU1116-1F
3RU1116-1G
3RU1116-1H
3RU1116-1H
3RU1116-1J
3RU1116-1J
3RU1126-1K
3RU1126-4A
3RU1126-4B
3RU1126-4C
3RU1126-4C
3RU1126-4D
3RU1126-4D
3RU1126-4D
3RU1136-4E
3RU1136-4F
3RU1136-4G
3RU1146-4J
3RU1146-4K
3RU1146-4L
3RU1146-4M
3RB1056-1FW0
3RB1056-1FG0
3RB1056-1FW0
3RB1056-1FG0
3RB1056-1FW0
3RB1056-1FG0
3RB1066-1G
3RB1066-1K
3RB1066-1K
3RB1066-1K
Fuse
Class J [A]
SCCR
1
1
1
2
2
2
3
3
6
6
8
10
15
15
15
15
20
25
30
40
40
30
50
50
60
60
70
90
125
175
200
250
250
300
300
300
300
400
400
500
500
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
65 kA
100 kA
100 kA
65 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
Voltage
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
480
600
600
480
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
Type 2 Co-ordination acc. UL 60947-4-1
Circuit Breaker (TM)
Size
Current
range
SCCR
Voltage
3RV27,3RV28
S00
1.6 – 16 A
(3RR2..1)
S0
(3RR2..2)
4 – 40 A
22 A
50 kA
480 V
15 A
12.5 A
65 kA
10 kA
480 V
600 V
15 A
65 kA
480 V
22 A
50 kA
480 V
12.5 A
10 kA
600 V
Type 2 Co-ordination acc. UL 60947-4-1A
High Capacity Short Circuit Ratings with Fuses, Type 2 co-ordination according UL 60947-4-1A
Current range
Max. Fuse
Fuse Classes
3 – 12 A
4 – 16 A
6 – 25 A
10 – 40 A
45 A
60 A
100 A
160 A
J
J
J
J
4 – 16 A
6 – 25 A
10 – 40 A
60 A
90 A
90 A
J
J
J
Size
S0 (3RB3.2)
S00 (3RB3.1)
Setting Ranges and Short Circuit ratings Circuit Breaker, Type 2 co-ordination according UL 60947-4-1A
Current range
Circuit Breaker Short
Voltage
5SJ…1)
Circuit
1–4A
15 A
5 kA
480 V
3 – 12 A
40 A
5 kA
480 V
4 – 16 A
40 A
5 kA
480 V
6 – 25 A
40 A
5 kA
480 V
10 – 40 A
40 A
5 kA
480 V
1) Siemens listed Circuit Breaker Type 5SJ43…-7HG42 (max. 40A)
High Capacity Short Circuit Ratings Type 2 co-ordination according UL 60947-4-1A
Current range
0.1 – 0.4 A
0.32 –
1.25 A
Circuit
Breaker
(TM)
3RV27,
3RV28
Short
Circuit
Voltage
-
-
-
3.2 A
65 kA
480 V
3.2 A
10 kA
30 kA
65 kA
10 kA
50 kA
65 kA
600 V
600 V
480 V
600 V
480 V
480 V
1–4A
15 A
12.5 A
3 – 12 A
22 A
15 A
12.5 A
4 – 16 A
22 A
15 A
12.5 A
6 – 25 A
22 A
15 A
12.5 A
10 – 40A
15 A
22 A
12.5 A
10 kA
50 kA
65 kA
10 kA
50 kA
65 kA
10 kA
65 kA
50 kA
10 kA
600 V
480 V
480 V
600 V
480 V
480 V
600 V
480 V
480 V
600 V
ination according UL 60947-4-1A
SCCR
Voltage
100 kA
100 kA
100 kA
100 kA
600 V
600 V
600 V
600 V
100 kA
100 kA
100 kA
600 V
600 V
600 V
dination according UL 60947-4-1A