ETC JJN-35

Bussmann®
T-Tron® Very Fast Acting Fuses
JJN
Class T
300 Volts, 1-1200 Amps
Dimensional Data
.88"
(± 0.02)
3.06"
(± 0.04)
.41" Dia.
(± 0.02)
1A to 30A
.88"
(± 0.02)
2.03"
.88"
1.25"
(± 0.04)
.56" Dia.
(± 0.02)
450A to 600A
35A to 60A
.284"
(Typ. 2)
2.16"
(± 0.02)
3.38"
(± 0.04)
1.56"
.84"
2.22"
.92"
.484"
(Typ. 2)
.75"
(± 0.02)
1.75"
(± 0.04)
70A to100A
Catalog Symbol: JJN
Current Limiting
Very Fast Acting
Ampere Rating: 1 to1200 Amperes
Voltage Rating: 300 Volts AC (or less)*
Interrupting Rating: 200,000A RMS Sym.
Agency Approval:
UL Listed, Std. 248-15, Class T, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.15, Class 1422-02, File 53787
Catalog Numbers
JJN-1
JJN-50
JJN-250
JJN-2
JJN-60
JJN-300
JJN-3
JJN-70
JJN-350
JJN-6
JJN-80
JJN-400
JJN-10
JJN-90
JJN-450
JJN-15
JJN-100
JJN-500
JJN-20
JJN-110
JJN-600
JJN-25
JJN-125
JJN-700
JJN-30
JJN-150
JJN-800
JJN-35
JJN-175
JJN-1000
JJN-40
JJN-200
JJN-1200
JJN-45
JJN-225
—
.344"
(Typ. 2)
4"
(± 0.04)
2.53"
1.08"
110A to 200A
.406"
(Typ. 2)
.562"
(Typ. 2)
601A to 800A
.88"
(± 0.02)
2.75"
(± 0.04)
1.84"
.86"
2"
(± 0.04)
1"
(± 0.04)
.609"
(Typ. 2)
801A to 1200A
225A to 400A
• Small, space-saving fuses provide a high degree of current
limitation on short-circuits for excellent component protection.
• Commonly applied in electric heat circuits, load center,
disconnect switches, and meters.
• The small size of the T-Tron fuses permits installation in
panelboards and control centers for system upgrading when
existing circuit breakers cannot safely interrupt larger available
short-circuit currents.
• High speed of response for semiconductor protection.
Standard T Fuseblocks (300V) Catalog Data
Catalog Numbers
Amps
Carton Quantity and Weight–JJN-T-TRON (300 Volts AC)
2.44"
(± 0.02)
1.69"
.84"
Poles
Screw
Box Lug
⁄Ω™
2
T30030-2SR
T30030-2CR
Carton
Qty.
to
3
T30030-3SR
T30030-3CR
Lbs.
Kg.
30
4
T30030-4SR
T30030-4CR
1–30
10
0.12
0.054
31
2
T30060-2SR
T30060-2CR
35–60
10
0.23
0.104
to
3
T30060-3SR
T30060-3CR
70–100
5
0.36
0.163
60
4
T30060-4SR
T30060-4CR
110–200
1
0.14
0.063
61
1
–
T30100-1CR
225–400
1
0.25
0.113
to
2
–
T30100-2CR
450–600
1
0.44
0.200
100
3
–
T30100-3CR
700–800
1
0.80
0.363
101 to
1
–
T30200-1C
200
3
–
1B0083
201 to 400
1
–
T30400-1C
401 to 600
1
–
T30600-1C
Catalog
Number
Weight**
1000–1200
1
1.45
0.658
*15-100A rated 300 VDC, 101-600A rated 160 VDC, 801-1200A rated 170 VDC
and 10 KAIC.
**Weight per carton.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 VAC, 75-1500 VDC). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
11-27-00
A00178
Form No. JJN
Page 1 of 2
BIF Doc #1025
Bussmann®
T-Tron® Very Fast Acting Fuses
JJN
Class T
300 Volts, 1-1200 Amps
1200
800
600
1000A
1200A
800A
600A
400A
200A
60A
30A
AMPERE
RATING
100,000
300
15A
B
100A
Time-Current Characteristic Curves–Average Melt
400,000
AMPERE
RATING
100
400
200
100
60
30
15
10,000
10
RMS SYMMETRICAL CURRENTS IN AMPERES
A-B = ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS)
TIME IN SECONDS
200,000
100,000
1,000
A
200
10,000
1,000
100
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
Current Limitation Curves
1
Custom Designs
• Printed circuit board variations available.
1.743" (± .020)
.1
1.395" (± .015)
.875" (± .015)
CL
A
Fuse
JJN-(1-30)L
JJN-(35-60)L
1,000
20
.01
10,000
.500"
100
1.90" MIN.
RMS SYMMETRICAL CURRENT IN AMPERES
A
0.406
0.563
The JJN-XXL products are UL Component Recognized under File E-56412
.125"
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
11-27-00
A00178
Form No. JJN
Page 2 of 2
BIF Doc #1025