KTS-R Data Sheet 1-18-11

Limitron®
KTS-R
Fast-Acting Fuses
600 Volt
1-600A
Dimensional Data
5"
(± 0.31)
.81" (± 0.008)
1/10A to 30A
5.5"
(± 0.31)
1.06" (± 0.008)
35A to 60A
7.88"
(±0.062)
1.000" (± 0.008)
70A to 100A
9.63"
(± 0.062)
1.500" (± 0.008)
110A to 200A
Catalog Symbol: KTS-R
Fast-Acting
Current-Limiting
Ampere Rating: 1 to 600A
Voltage Rating: 600Vac (or less)*
Interrupting Rating: 200,000A RMS Sym.
Tube Material: Glass Melamine
End Caps: 70/30 Brass
Operating Temp.: –40°C to +85°C
Storage Temp.: –55°C to +85°C
Agency Information:
CE, UL Listed, Std. 248-12, Class RK1, Guide JDDZ, File
E54273 CSA Certified, C22.2 No. 248.12, Class 1422-02,
File 53787
Catalog Numbers
11.63"
(±0.094)
2.000" (± 0.008)
225A to 400A
13.38"
(± 0.094)
2.500" (± 0.008)
450A to 600A
Carton Quantity and Weight (600Vac)
Weight*
Amps
Carton
Qty.
Lbs.
Kg.
1–30
10
1.45
0.657
40–60
10
2.63
1.262
70–100
1
0.5
0.226
110–200
1
1.4
0.634
KTS-R-1
KTS-R-30
KTS-R-125
225–400
1
2.75
1.246
KTS-R-2
KTS-R-35
KTS-R-150
4.25
1.925
KTS-R-40
KTS-R-175
450–600
*Weight per carton.
1
KTS-R-3
KTS-R-4
KTS-R-45
KTS-R-200
KTS-R-5
KTS-R-50
KTS-R-225
KTS-R-6
KTS-R-60
KTS-R-250
KTS-R-8
KTS-R-70
KTS-R-300
KTS-R-10
KTS-R-75
KTS-R-350
KTS-R-12
KTS-R-80
KTS-R-400
KTS-R-15
KTS-R-90
KTS-R-450
KTS-R-20
KTS-R-100
KTS-R-500
KTS-R-25
KTS-R-110
KTS-R-600
1002
SB02295
General Information:
• Single-element, fast-acting fuses with minimal time-delay.
• Provides a high degree of short-circuit current-limitation
(component protection).
• Particularly suited for circuits and loads with no heavy surge
currents of motors, transformers, solenoids, and welders.
• LIMITRON fuses are commonly used to protect circuit
breakers with lower interrupting ratings.
• If used in circuits with surge currents (motors, etc.) must be
sized to prevent unwanted opening and thus only provide
short-circuit protection.
• Incorporate Class R rejection feature. Can be inserted in nonrejection type fuseholders. Thus, can physically and electrically replace fast-acting Class H, K1, K5, RK5, and other
fast-acting fuses.
Page 1 of 2
Data Sheet 1044
600A
400A
200A
100A
30A
400,000
60A
Time-Current Characteristic Curves–Average Melt
B
AMPERE
RATING
AMPERE
RATING
300
100,000
100
600
400
200
100
10,000
60
10
200,000
100,000
1,000
10,000
A
TIME IN SECONDS
30
1,000
INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS
Current-Limitation Curves
1
RMS SYMMETRICAL CURRENTS IN AMPERES
A–B=ASYMMETRICAL AVAILABLE PEAK (2.3 x SYMM RMS AMPS)
Recommended fuseblocks for
Class R 600V fuses
See Data Sheet: 1111
.1
10,000
1,000
40
100
.01
RMS SYMMETRICAL CURRENT IN AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2010 Cooper Bussmann
www.cooperbussmann.com
1002
SB02295
Page 2 of 2
Data Sheet 1044