ETC DPB01CM23

Monitoring Relays
3-Phase, 3-Phase+N, Multi-function
Types DPB01, PPB01
DPB01
PPB01
• 3-phase over and under voltage,
phase sequence and phase loss monitoring relays
• Detect when all 3 phases are present and have the
correct phase sequence
• Detect if all the 3-phase-phase or phase-neutral voltages are within the set limits
• Upper and lower limits separately adjustable
• Measure on own power supply
• Selection of measuring range by DIP-switches
• Adjustable voltage on relative scale
• Adjustable delay function (0.1 to 30 s)
• Output: 8 A SPDT relay N.E.
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DPB01) or plug-in module (PPB01)
• 22.5 mm Euronorm housing (DPB01)
or 36 mm plug-in module (PPB01)
• LED indication for relay, alarm and power supply ON
Product Description
Ordering Key
3-phase or 3-phase+neutral
line voltage monitoring relay
for phase sequence, phase
loss, over and under voltage
(separately adjustable set
points) with built-in time
delay function.
Supply ranges from 208 to
480 VAC covered by two
multivoltage relays.
Housing
Function
Type
Item number
Output
Power supply
Mounting
Output
Supply: 208 to 240 VAC
Supply: 380 to 480 VAC
DIN-rail
Plug-in
SPDT
SPDT
DPB 01 C M23
PPB 01 C M23
DPB 01 C M48
PPB 01 C M48
DPB 01 C M23
Type Selection
Input Specifications
Output Specifications
Input
L1, L2, L3, N
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Measuring ranges
208 to 240 VAC
380 to 480 VAC (DPB01CM48)
380 to 415 VAC (PPB01CM48)
Ranges
Upper level
Lower level
DPB01: Terminals L1, L2, L3, N
PPB01: Terminals 5, 6, 7, 11
Measure on own supply
177 to 275 VAC
323 to 550 VAC
323 to 475 VAC
+2 to +22%
of the nominal voltage
-22 to -2%
of the nominal voltage
Specifications are subject to change without notice (06.11.00)
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
Dielectric voltage
2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
1
DPB01, PPB01
Supply Specifications
General Specifications (cont.)
Power supply
Rated operational voltage
through terminals:
L1, L2, L3, N
(DPB01)
5, 6, 7, 11
(PPB01)
M23:
Indication for
Power supply ON
Alarm ON
M48:
Rated operational power
DPB01CM23, PPB01CM23
DPB01CM48, PPB01CM48
Overvoltage cat. III
(IEC 60664, IEC 60038)
208 to 240 VAC ± 15%
45 to 65 Hz
380 to 480 VAC ± 15%
45 to 65 Hz
13 VA @ 230 VAC, 50 Hz
13 VA @ 400 VAC, 50 Hz
Supplied by L2 and L3
General Specifications
Power ON delay
Reaction time
Incorrect phase sequence or
total phase loss
Voltage level
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
1 s ± 0.5 s or 6 s ± 0.5 s
< 200 ms
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 200 ms (delay < 0.1 s)
< 200 ms (delay < 0.1 s)
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-marking
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
IP 20
3 (DPB01), 2 (PPB01)
-20 to 60°C, R.H. < 95%
@ 475 VAC, 65 Hz
-20 to 50°C, R.H. < 95%
@ 550 VAC, 65 Hz
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 120 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
Connected to the 3 phases
(and neutral) DPB01 and
PPB01 operate when all 3
phases are present at the
same time, the phase
sequence is correct and the
phase-phase (or phase-neutral) voltage levels are within
set limits.
If one or more phase-phase
or phase-neutral voltages
exceeds the upper set level
or drops below the lower set
level, the red LED starts
flashing 2 Hz and the output
relay releases after the set
time period. In any case if
phase-neutral measurement
is selected both phasephase and phase-neutral
voltages are monitored. If the
phase sequence is wrong or
one phase is lost, the output
relay releases immediately.
Only 200 ms delay occurs.
The failure is indicated by the
red LED flashing 5 Hz during
the alarm condition.
Example 1
(mains network monitoring)
Example 2
(load monitoring)
The relay releases in case of
interruption of one or more
phases, when one or more
voltages drop below the lower set level or exceed the
upper set level.
The relay monitors over and
under voltage, phase loss
and correct phase sequence.
Function/Range/Level and Time Delay Setting
Selection of function:
DIP-switch selector (1 to 2)
Selection of measuring range:
DIP-switch selector (3 to 4)
34
1
ON
Power ON delay 6 ± 0.5 s
Power ON delay 1 ± 0.5 s
2
Phase-neutral voltage
Phase-phase voltage
2
ON
3 x 240 ∆ VAC (M23)
3 x 480 ∆ VAC
(DPB01CM48)
3 x 208 ∆ VAC (M23)
3 x 380 ∆ VAC (M48)
Selection of level and time
delay:
3 x 220 ∆ VAC (M23)
3 x 400 ∆ VAC (M48)
Upper knob:
Setting of lower level on relative scale.
3 x 230 ∆ VAC (M23)
3 x 415 ∆ VAC (M48)
Centre knob:
Setting of upper level on relative scale.
Lower knob:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
Specifications are subject to change without notice (06.11.00)
DPB01, PPB01
Wiring Diagrams
Example 1
Example 1
N
L3
L2
L1
N
L3
L2
L1
µ
L1 L2 L3
m<3
16
µ
18
5
m<3
6
4
7
3
U
U
L2
L2
L3
N
L3
15
11
1
Example 2
Example 2
N
L3
L2
L1
N
L3
L2
L1
µ
L1 L2 L3
m<3
16
µ
18
5
m<3
6
7
4
3
U
U
L2
L2
L3
N
L3
15
11
1
PPB01
DPB01
Operation Diagrams
L1 or
L1-L2
Upper Level
Hysteresis
L2 or
L2-L3
Hysteresis
Lower Level
L3 or
L1-L3
Relay ON
1 or 6 s
Red LED ON
1 or 6 s
T
T
L1
L1
L2
L1
L2
L3
L1
L2
L3
L2
L3
L3
Relay ON
Red LED ON
1 or 6 s
Specifications are subject to change without notice (06.11.00)
3