ETC PUB01

Monitoring Relays
1-Phase True RMS AC/DC Over or Under Voltage
Types DUB01, PUB01
DUB01
• TRMS AC/DC over or under voltage
monitoring relays
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 to 500 V AC/DC
• Adjustable voltage on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DUB01) or plug-in module (PUB01)
• 22.5 mm Euronorm housing (DUB01)
or 36 mm plug-in module (PUB01)
• LED indication for relay, alarm and power supply ON
PUB01
Product Description
DUB01 and PUB01 are precise TRMS AC/DC over or
under voltage (selectable by
DIP-switch) monitoring relays.
Owing to the built-in latch
function, the ON-position of
the relay output can be
Ordering Key
maintained. Inhibit function
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay.
DUB 01 C B23 10V
Housing
Function
Type
Item number
Output
Power supply
Range
Type Selection
Mounting
Output
DIN-rail
SPDT
Plug-in
SPDT
Measuring range
0.1 to 10 V AC/DC
2 to 500 V AC/DC
0.1 to 10 V AC/DC
2 to 500 V AC/DC
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DUB 01 C 724 10V
DUB 01 C 724 500V
PUB 01 C 724 10V
PUB 01 C 724 500V
DUB 01 C B48 10V
DUB 01 C B48 500V
PUB 01 C B48 10V
PUB 01 C B48 500V
DUB 01 C B23 10V
DUB 01 C B23 500V
PUB 01 C B23 10V
PUB 01 C B23 500V
Input Specifications
Output Specifications
Input
Voltage level
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
DUB01: Terminals Y1, Y2
PUB01: Terminals 5, 7
Measuring ranges
..10V:
0.1 to 1 V AC/DC
0.2 to 2 V AC/DC
0.5 to 5 V AC/DC
1 to 10 V AC/DC
Max. voltage for 1 s
..500V:
2 to 20 V AC/DC
5 to 50 V AC/DC
20 to 200 V AC/DC
50 to 500 V AC/DC
Max. voltage for 1 s
Note:
The input voltage cannot
raise over 300 VAC/DC
with respect to ground
(PUB01 only)
Contact input
DUB01
PUB01
Disabled
Enabled
Latch disable
Internal resist.
>200 kΩ
>200 kΩ
>200 kΩ
>200 kΩ
>500 kΩ
>500 kΩ
>500 kΩ
>500 kΩ
Max. volt.
100 V
100 V
100 V
100 V
200 V
350 V
350 V
600 V
600 V
1000 V
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
Specifications are subject to change without notice (21.10.00)
1
DUB01, PUB01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DUB01)
2, 10 or 11, 10
(PUB01)
724:
B48:
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
AC supply
2 kV
4 kV
4 kV
4 kV
4 kV
4 kV
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
4 VA
3W
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 100 ms
< 100 ms
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
IP 20
3 (DUB01), 2 (PUB01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 150 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
DUB01 and PUB01 monitor
both AC and DC over or
under voltage.
set level (see hysteresis setting), or when power supply
is interrupted.
Example 1
(no connection between terminals Z1, Y1 or 8, 9 - latch
function disabled)
Example 2
(connection between terminals Z1, Y1 or 8, 9 - latch
function enabled)
The relay operates when the
measured value exceeds (or
drops below) the set level for
more than the set delay time.
It releases when the voltage
drops below (or exceeds) the
The relay operates and latches in operating position
when the measured value
exceeds (or drops below) the
set level for more than the
set delay time.
2
Provided that the voltage
has dropped below (or has
exceeded) the set point (see
hysteresis setting) the relay
releases when the interconnection between terminals
Z1, Y1 or 8, 9 is interrupted,
or power supply is interrupted as well.
The yellow LED flashes until
the delay time has expired or
the measured value has
dropped below the set point
(see hysteresis setting).
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
Specifications are subject to change without notice (21.10.00)
DUB01, PUB01
Function/Range/Level and Time Delay Setting
Selection of measuring range:
DIP-switch selector (1 to 2)
Selection of function:
DIP-switch selector (3 to 5)
Selection of function:
DIP-switch selector (6)
Selection of level and time
delay:
..10V
12
3
6
Upper knob:
Setting of hysteresis on relative scale: 0 to 30% on set
value.
ON
Relay de-energized in
normal condition.
Input range:
0.1 to 1 V
0.2 to 2 V
0.5 to 5 V
1 to 10 V
Relay energized in normal
condition.
4
..500V
12
ON
Power ON delay 6 ± 0.5 s
Input range:
2 to 20 V
5 to 50 V
20 to 200 V
50 to 500 V
Power ON delay 1 ± 0.5 s
Over current monitoring
relay. The alarm condition
occurs when the current input
is over the set point value.
Under current monitoring
relay. The alarm condition
occurs when the current input
is under the set point value.
Centre knob:
Current level setting on relative scale: 10 to 110% on full
scale.
Lower knob:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
5
Contact input as latch function enable. When the contact
is closed, the latch function is
activated. Reset of the latch
condition occurs when the contact is open or by power down.
Contact input as inhibit of
alarm enable. When the contact is closed the relay remains
in normal position even if the
alarm condition occurs.
Wiring Diagrams
Example 1
Example 1
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
PE
Y1
A1
24 VDC (+)
48/230 VAC 24/115 VAC
µ
A3
16
L
18
9
U
PE
Y2
A2
15
7
8
2
µ
11
4
3
U
5
10
1
N(-)
N(-)
Example 2
Example 2
Latch/inhibit
enable
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
PE
Y1
Y2
A1
24 VDC (+)
48/230 VAC 24/115 VAC
Latch/inhibit
enable
L
µ
A3
16
18
9
U
8
2
µ
11
4
3
U
PE
7
A2
15
5
N(-)
DUB01
Specifications are subject to change without notice (21.10.00)
10
1
N(-)
PUB01
3
DUB01, PUB01
Operation Diagrams
Over voltage
Under voltage - Latch function
Power supply
Power supply
Latch ON
Set Level
Hysteresis
Hysteresis
Set Level
1 or 6 s
Relay ON
Red LED ON
1 or 6 s
Relay ON
Red LED ON
Under voltage
Over voltage - Inhibit function
Power supply
Power supply
Inhibit ON
Set Level
Hysteresis
Set Level
Hysteresis
Relay ON
Red LED ON
1 or 6 s
1 or 6 s
Relay ON
Red LED ON
4