ETC PAT4DVF

AVO INTERNATIONAL
MEGGER PAT4
PORTABLE APPLIANCE TESTERS
• Fast Testing
• Tests 110V, 230V and I.T. equipment
• Full Test capabilities (Flash Test on PAT4DVF only)
• Extension Lead Testing
• QWERTY keyboard
• 10-Year Real TIme Clock
• Integral Database
• Parallel Printer Port
• RS232 Communication
• Lightweight, Small and Compact
PAT4DV & DVF
DESCRIPTION
PAT4DV & PAT4DVF speed testing by
working the way you work. PAT4 is
quicker to start, test, download and
upload. Full Appliance and Client
details are stored along with test
results.
New Appliances may be
added as and where you find them.
The combination of Quick Boot, Auto
Restart, Real Time Clock, Group Test
Codes, Quick Check and Instant
Certification will save you up to 50%
of your time, resulting in increased
efficiency, improved productivity and
increased profits for your company
compared to other testers.
PAT4 is engineered to maintain data
integrity and traceability with storage
for up to 1000 assets, 1000 sets of
current test results, 1000 sets of
historical test results, 10 clients, 20
locations and 50 group test codes at
the same time.
PAT4 is designed to minimise the time
taken to test electrical appliances.
We believe that PAT4 is the fastest
downloading
portable
appliance
tester available on the market today.
Each test is time and date stamped to
provide traceability.
users. Each user can be allocated
their own name and password.
Plain & Simple Operation!
The PAT4 has a full QWERTY
keyboard for rapid data entry.
Repair Codes.
PAT4 can reference up to 99 repair
codes allowing you to quickly record
repair details against appliance tests.
When used with PowerSuite, this
information will allow charges to be
made for appliance repairs.
No complicated test codes!
Many pats use complicated codes to
control test routines. PAT4 uses
group test codes in plain English that
define test routines, test duration and
pass bands.
Direct entry of new details!
PAT4 allows you to enter new
appliance and repair details directly
into memory, complete with location,
description, voltage and group test
code. All details may be downloaded
to AVO PowerSuite for Windows or
other suitable software. No more
work is needed.
Built in Fuse Check!
If you suspect a blown fuse you no
longer need a multimeter. PAT4 has a
built in fuse check.
Boots up in 5 seconds!
Some pats take 30 seconds or more to
start up, time that could be used
carrying out tests. PAT4 quick boots
in only 5 seconds.
Quick check.
When repairs have been completed,
PAT4 will carry out a single test to
check the effectiveness of the repair.
There is no need to complete a full
test routine when only a quick check
is required.
Auto restart facility!
You need to move your pat as you
test appliances. PAT4 auto restart
returns you to the point you were at
when you switched off, in only 5s.
User selectable test duration.
To prevent test results varying
because of different test durations,
you can set the test duration for each
test.
Clock set for 10 years!
No need to set the clock every time
you restart PAT4. PAT4’s real-time
clock stays correct for ten years.
Optional user defined access.
PAT4 gives you options to restrict
access to the operation of the
instrument for up to 10 authorised
Degradation Warning.
PAT4 incorporates a historic data
facility, which enables previous test
results, uploaded from PowerSuite, to
be viewed at the time of testing. This
enables you to identify degradation in
the appliance since its last test.
Auto or Manual mode.
Pass / Fail decisions can be made
manually or you can set limits for
each test and let PAT4 make the
decision based on the measurement.
Search Routines.
Powerful in-built search routines
allow you to search PAT4’s database
by Asset ID, Retest due date, Test
Group Code, by Room within Location
and by Location within Client.
Clients and Locations.
PAT4 uniquely holds details of Clients
and Locations. Unique Appliance IDs
and details are held separately for each
client. Thus, appliances may be tracked
easily if they move between locations.
On Site Certification.
Parallel printers, bar code readers
and PC downloads are all supported
by PAT4. Test data may be
downloaded to PCs for certification,
or printed on site immediately after
testing for instant certification. All
reports can be personalised to show
your company details.
MEGGER® PAT4 Portable Appliance Testers
SPECIFICATIONS
Circuit Test
Open Circuit Voltage:
Short Circuit Current:
Fuse Test
15 V. a.c. typical
100 mA. a.c. typical
Open Circuit Voltage:
Test Current:
Indication :
Insulation Test
Range:
Accuracy:
Compliance:
Pass Band Options:
0 - 50 MΩ
5.0% ± 100 kΩ (≤20MΩ)
500 V. d.c. at 0.5 MΩ
0.5, 1, 2, 5, 7, 10, 20, 50 MΩ
5 V. d.c. typical
500 mA. short circuit typical
Audible using internal buzzer
Extension Lead Test
Bond test (10 or 25 A)
Insulation test
Polarity test indicates:
Correct polarity
Crossed connections L/N
Short circuit L/N
Open circuit L/N
Earth Bond Test
Range:
0 mΩ - 999 mΩ
1000 mΩ - 1999 mΩ
Accuracy:
0 mΩ <R> 499 mΩ
500 mΩ <R> 1999 mΩ
Open Circuit Voltage:
Test Current:
Pass Band Options:
.
Resolution 1 mΩ
Resolution 10 mΩ
On Board Database Specifications
5.0% ± 5 mΩ
5.0% ± 50 mΩ
10 V. a.c. typical
10 A. or 25 A. into 0.1 Ω typical
50, 100, 200, 500, 750 mΩ, 1.0, 1.5, 2.0 Ω
Clients:
Locations:
Test Groups:
Users:
Appliances:
10
20
50
10
1000 with the following data fields;
ID, description, group, serial no, room, VA
rating, last and next test dates, retest
frequency and fuse rating
Earth Continuity Test
Range:
0 mΩ - 999 mΩ
1.00 Ω - 9.99 Ω
Accuracy:
0 mΩ <R> 999 mΩ
1.00 Ω <R> 9.99 Ω
Open Circuit Voltage:
Test Current:
Pass Band Options:
Resolution 1 mΩ
Resolution 10 mΩ
Supply Voltage
5.0% ± 5 mΩ
5.0% ± 10 mΩ
4 V. d.c. typical
200 mA. typical constant current (R≤1 Ω)
100, 500, 750 mΩ, 1.0, 1.5, 2.0, 5, 10 Ω
Communications
Mains supply:
99 - 121, 207 - 253 V. 50Hz
Interface to PC and optional Bar Code Scanner
Connection to parallel printer
9 way male ‘D’ RS232 connector:
25 way female ‘D’ connector:
Safety Specifications
Operation Test (Energised from 230 V. supply)
The PAT4 complies with BSEN 61010-1:1990
Range:
Accuracy:
Electromagnetic Compatibility
Reference:
Pass Band Options:
0 - 3.0 kVA
0 <VA.> 99 VA
5.0% ± 5 VA
100 <VA.> 999 VA
5.0% ± 10 VA
1.0 <kVA.> 3.0 kVA
5.0% ±100 VA
Reading corrected to 230 V
50, 200, 500, 1000, 1500, 2000, 2500, 3000 VA
The PAT4 complies with BSEN 50081-1-1992 (Light Industrial Category), BSEN
50082-1-1992
Physical Specifications
Operation Test (Energised from 110 V. supply)
Weight (unpackaged inc. std. accessories):
Range:
Accuracy:
Width (Including Handle and Lid):
Depth:
Height:
Reference:
Pass Band Options:
0 - 1.6 kVA (3 kVA. short term)
0 <VA.> 99 VA
5.0% ± 5 VA
100 <VA.> 999 VA
5.0% ± 10 VA
1.0 <VA.> 1.6 kVA
5.0% ± 100 VA
Reading corrected to 110 V
50, 200, 500, 1000, 1500, 2000, 2500, 3000 VA
6.0 kg
6.9 kg
375 mm
330 mm
200 mm
(PAT4DV)
(PAT4DVF)
Earth Leakage Test
Range:
Accuracy:
Reference:
Pass Band Options:
0 - 15 mA
5.0% ± 100µA
Reading corrected to 253/121V.
(As if 10% High Supply)
0.5, 1.0, 2.0, 3.5, 5.0, 7.5, 10, 15 mA
Flash Test
Range:
Accuracy:
Output Voltage:
Output Current:
Pass Band Options:
0 - 3 mA
5.0% ± 100 µA
Class 1
1500 V. a.c. (typical)
Class 2
3000 V. a.c. (typical)
< 3.5 mA. @ 253/121 V
0.2, 0.5, 0.75, 1.0, 1.5, 2.0, 2.5, 3.0 mA
The Company reserves the right to change the specification or design without prior notice. AVO and MEGGER are the Registered Trade
Marks of AVO INTERNATIONAL LIMITED.
ORDERING INFORMATION
Item
Cat.No.
Portable Appliance Tester
PAT4DV
Portable Appliance Tester with Flash Test
PAT4DVF
Included Accessories
User Guide
Earth Bond Test Lead
Mains Lead (230 V. 16 A.)
Flash Test Probe (DVF only)
Serial PC Download Lead
UNITED KINGDOM
ARCHCLIFFE ROAD, DOVER, KENT CT17 9EN
ENGLAND
PHONE: +44 (0)1304-502100/202620
FAX: +44 (0)1304-502300/207342
EMAIL: avosales.dover @avointl.com
6172-216
6280-315
6121-282
5310-401
25955-025
UNITED STATES
4651 S. WEST MORELAND ROAD
DALLAS, TX 75237-1017 USA
PHONE: (214) 330-3255
FAX: (214) 333-3533
EXPORT FAX: (214) 337-3038
Optional Accessories
Cat.No.
Bar Code Scanner 72mm
PAT Testing Labels
Earth Bond Probe
“Safe Block” Adaptor Lead
Adaptor for 110 V plug to 110 V socket Ext. Lead
Adaptor for 13A plug to 13A socket Ext. Lead
110 V., 16 A. IEC supply Lead
Parallel Printer Lead
“Electricity in the Workplace” Video
“PAT Testing “ Video (ii)
“PowerSuite” Software
Results Printer
Continuous Label Roll for 25995-017
Test labels (roll of 500)
1200 clear adhesive label covers (2”x1”)
6231-623
6171-418
6320-225
6331-230
6231-547
6220-632
6220-631
25970-024
6131-883
6131-999
Various
25995-017
25995-016
6171-418
6220-610
AVO INTERNATIONAL