ETC 227164-

Voltmeter (moving iron) with switch
Dimensions - see table below
A range of moving iron AC Voltmeters with integral selection switch in 72 or 96mm square DIN format for use
on AC supplies. Two versions are available namely: FNlll for phase to phase selection and FNlll+N for phase
to phase and phase to neutral voltage selection.
Application
Dimensions
The EC72/96 FN Voltmeter with integral manual
changeover switch is specifically designed to
measure the voltages between phases and between
each phase and neutral of a three phase AC
system.
The switch on the FNlll has three positions :L1 phase to L2 phase
L2 phase to L3 phase
L3 phase to L1 phase
On the FNlll+N it has six positions :L1 phase to L2 phase
L2 phase to L3 phase
L3 phase to L1 phase
L1 phase to Neutral
L2 phase to Neutral
L3 phase to Neutral
Each phase connection to the Voltmeter should be
protected by a fuse.
The scale has a 90 degree movement with zeroing
adjustment.
Type
Code
Voltage
EC72FNlll
EC72FNlll
EC72FNlll+N
EC72FNlll+N
227 144
227 145
227 164
227 165
500V
600V
500V
600V
EC96FNlll
EC96FNlll
EC96FNlll+N
EC96FNlll+N
227 154
227 155
227 174
227 175
500V
600V
500V
600V
Models are also available for 250V, 300V and
400V systems.
a
b
c
d
EC72FN
72
67.2
43.5
5.7
68sq
EC96FN
96
91
43.5
5.7
92sq
Movement
Scale
Class
Consumption
900
0 … 600V
1.5
1.8 VA (250V)
3.3 VA (500V)
Overload
1.5 Un permanent
2 In for 5 seconds
Frequency ref.
Range
50Hz
20 - 100Hz
Isolating voltage
2000V for 1 minute
Temperature
Ambient range
-250C…+400C
Protection
Case
Terminals
IP52
IP20 (with cover)
Weight
0.275 Kg
Standards
IEC51, VDE410, DIN43 780, BS89, UL94,
EN60051.
Options
Tropicalisation
IP54 or IP55 protection
Anti-reflection glass
Makrolon glass
Grey frame RAL 7037
Starkstrom 256 Field End Rd Eastcote Ruislip Middx HA4 9UW Tel. 020 8868 3732
VISIT OUR WEBSITE AT WWW.STARKSTROM.COM
DS97212.DOC - Page 1 of 1 - Issue 3 - 24.6.98
Cutout