ETC DS1672-3

DS1672
Low-Voltage Serial Timekeeping Chip
www.maxim-ic.com
FEATURES
§
§
§
§
§
§
§
PIN ASSIGNMENT
32-bit counter
Two-wire serial interface
Automatic power-fail detect and switch
circuitry
Power-fail reset output
Low-voltage oscillator operation (1.3V min.)
Trickle charge capability
Underwriters Laboratory (UL) recognized
X1
1
8
VCC
X2
2
7
RST
VBACKUP
3
6
SCL
GND
4
5
SDA
Package dimension information can be found at:
ORDERING INFORMATION
http://www.maxim-ic.com/TechSupport/PackInfo.htm
DS1672X-X
2 2.0V Operation
3 3.0V Operation
33 3.3V Operation
blank
S
U
8-Pin DIP
8-Pin SOIC
8-Pin µSOP
PIN DESCRIPTION
VCC, VBACKUP
GND
X1, X2
SCL
SDA
RST
- Power Supply Inputs
- Ground
- 32.768kHz Crystal Pins
- Serial Clock
- Serial Data
- Reset Output
DESCRIPTION
The DS1672 low-voltage serial timekeeping chip incorporates a 32-bit counter and power-monitoring
functions. The 32-bit counter is designed to count seconds and can be used to derive time-of-day, week,
month, month, and year by using a software algorithm. A precision, temperature-compensated reference
and comparator circuit monitors the status of VCC. When an out-of-tolerance condition occurs, an internal
power-fail signal is generated that forces the reset to the active state. When VCC returns to an in-tolerance
condition, the reset signal is kept in the active state for 250ms to allow the power supply and processor to
stabilize.
OPERATION
The block diagram in Figure 1 shows the main elements of the DS1672. As shown, communications to
and from the DS1672 occur serially over a 2-wire, bi-directional bus. The DS1672 operates as a slave
device on the serial bus. Access is obtained by implementing a START condition and providing a device
identification code followed by a register address. Subsequent registers can be accessed sequentially until
a STOP condition is executed.
1 of 12
100101
DS1672
TYPICAL OPERATING CIRCUIT
DS1672 BLOCK DIAGRAM Figure 1
X1
X2
32-BIT
COUNTER
(4 BYTES)
OSCILLATOR
AND DIVIDER
CONTROL
TRICKLE CHARGER
VCC
VBACKUP
GND
POWER
CONTROL
CONTROL
LOGIC
SERIAL BUS
INTERFACE
ADDRESS
REGISTER
RST
SCL
SDA
SIGNAL DESCRIPTIONS
VCC, GND – DC power is provided to the device on these pins.
VBACKUP – Battery input for any standard 3V lithium cell or other energy source. Battery voltage must be
held between 1.3V and 3.6V for proper operation. UL recognized to ensure against reverse charging
current when used in conjunction with a lithium battery.
See “Conditions of Acceptability” at http://www.maxim-ic.com/TechSupport/QA/ntrl.htm.
2 of 12
DS1672
SCL (Serial Clock Input) – SCL is used to synchronize data movement on the serial interface and
requires an external pull-up resistor.
SDA (Serial Data Input/Output) – SDA is the input/output pin for the 2-wire serial interface. The SDA
pin is an open drain output and requires an external pull-up resistor.
RST (Reset Output) – The RST pin functions as a microprocessor reset signal. This pin is an open drain
output and requires an external pull-up resistor.
X1, X2 – These signals are connections for a standard 32.768kHz quartz crystal. The internal oscillator
circuitry is designed for operation with a crystal having a specified load capacitance (CL) of 6pF.
For more information about crystal selection and crystal layout considerations, please consult Application
Note 58, “Crystal Considerations with Dallas Real-Time Clocks.” The DS1672 can also be driven by an
external 32.768kHz oscillator. In this configuration, the X1 pin is connected to the external oscillator
signal and the X2 pin is floated.
RECOMMENDED LAYOUT FOR CRYSTAL
CLOCK ACCURACY
The accuracy of the clock is dependent upon the accuracy of the crystal and the accuracy of the match
between the capacitive load of the oscillator circuit and the capacitive load for which the crystal was
trimmed. Additional error will be added by crystal frequency drift caused by temperature shifts. External
circuit noise coupled into the oscillator circuit may result in the clock running fast. See Application Note
58, “Crystal Considerations with Dallas Real-Time Clocks” for detailed information.
ADDRESS MAP
The counter is accessed by reading or writing the first 4 bytes of the DS1672 (00h–03h). The control
register and trickle charger are accessed by reading or writing the appropriate register bytes as illustrated
in Figure 2. If the master continues to send or request more data after the address pointer has reached
05h, the address pointer will wrap around to location 00h.
3 of 12
DS1672
DS1672 REGISTERS Figure 2
Address
00h
B7
B6
B5
B4
B3
B2
B1
B0
LSB
TCS
TCS
TCS
DS
DS
RS
RS
01h
02h
03h
04h
05h
MSB
EOSC
TCS
Function
Counter
Byte 1
Counter
Byte 2
Counter
Byte 3
Counter
Byte 4
Control
Trickle
Charger
DATA RETENTION MODE
The device is fully accessible and data can be written and ready only when VCC is greater than VPF.
However, when VCC falls below VPF, (point at which write protection occurs) the internal clock registers
are blocked from any access. If VPF is less than VBACKUP, the device power is switched from VCC to
VBACKUP when VCC drops below VPF. If VPF is greater than VBACKUP, the device power is switched from
VCC to VBACKUP when VCC drops below VBACKUP. The registers are maintained from the VBACKUP source
until VCC is returned to nominal levels.
OSCILLATOR CONTROL
The EOSC bit (bit 7 of the control register) controls the oscillator when in back-up mode. This bit when
set to logic 0 will start the oscillator. When this bit is set to a logic 1, the oscillator is stopped and the
DS1672 is placed into a low-power standby mode (IBACKUP) when in back-up mode. When the DS1672 is
powered by VCC, the oscillator is always on regardless of the status of the EOSC bit; however, the counter
is incremented only when EOSC is a logic 0.
MICROPROCESSOR MONITOR
A temperature-compensated comparator circuit monitors the level of VCC. When VCC falls to the powerfail trip point, the RST signal (open drain) is pulled active. When VCC returns to nominal levels, the RST
signal is kept in the active state for 250ms (typically) to allow the power supply and microprocessor to
stabilize. Note, however, that if the EOSC bit is set to a logic 1 (to disable the oscillator during write
protection), the reset signal will be kept in an active state for 250ms plus the start-up time of the
oscillator.
4 of 12
DS1672
TRICKLE CHARGER
The trickle charger is controlled by the trickle charge register. The simplified schematic of Figure 3
shows the basic components of the trickle charger. The trickle charge select (TCS) bit (bits 4–7) controls
the selection of the trickle charger. In order to prevent accidental enabling, only a pattern on 1010 will
enable the trickle charger. All other patterns will disable the trickle charger. The DS1672 powers up
with the trickle charger disabled. The diode select (DS) bits (bits 2–3) select whether or not a diode is
connected between VCC and VBACKUP. If DS is 01, no diode is selected or if DS is 10, a diode is selected.
The RS bits (bits 0–1) select whether a resistor is connected between VCC and VBACKUP and what the value
of the resistor is. The resistor selected by the resistor select (RS) bits and the diode selected by the diode
select (DS) bits are as follows:
TC
S
X
X
X
1
1
1
1
1
1
TCS
TCS
TCS
DS
DS
RS
RS
Function
X
X
X
0
0
0
0
0
0
X
X
X
1
1
1
1
1
1
X
X
X
0
0
0
0
0
0
0
1
X
0
1
0
1
0
1
0
1
X
1
0
1
0
1
0
X
X
0
0
0
1
1
1
1
X
X
0
1
1
0
0
1
1
Disabled
Disabled
Disabled
No diode, 250W resistor
One diode, 250W resistor
No diode, 2kW resistor
One diode, 2kW resistor
No diode, 4kW resistor
One diode, 4kW resistor
Diode and resistor selection is determined by the user according to the maximum current desired for
battery or super cap charging. The maximum charging current can be calculated as illustrated in the
following example. Assume that a system power supply of 3V is applied to VCC and a super cap is
connected to VBACKUP. Also assume that the trickle charger has been enabled with a diode and resistor R2
between VCC and VBACKUP. The maximum current IMAX would, therefore, be calculated as follows:
IMAX = (5.0V - diode drop) / R1 » (5.0V - 0.7V) / 2kW » 2.2mA
As the super cap changes, the voltage drop between VCC and VBACKUP will decrease and, therefore, the
charge current will decrease.
5 of 12
DS1672
DS1672 PROGRAMMABLE TRICKLE CHARGER Figure 3
R1
VCC
250W
VBACKUP
R2
2kW
R3
4kW
1 OF 16 SELECT
1 OF 2
SELECT
NOTE: ONLY 1010 ENABLES
TCS
BIT 7
TCS
BIT 6
TCS
BIT 5
TCS
BIT 4
DS
BIT 3
DS
BIT 2
1 OF 3
SELECT
RS
BIT 1
RS
BIT 0
TCS = TRICKLE CHARGER SELECT
DS = DIODE SELECT
RS = RESISTOR SELECT
TRICKLE CHARGE REGISTER
2-WIRE SERIAL DATA BUS
The DS1672 supports a bi-directional 2-wire bus and data transmission protocol. A device that sends
data onto the bus is defined as a transmitter and a device receiving data as a receiver. The device that
controls the message is called a “master.” The devices that are controlled by the master are “slaves.” The
bus must be controlled by a master device that generates the serial clock (SCL), controls the bus access,
and generates the START and STOP conditions. The DS1672 operates as a slave on the 2-wire bus.
Connections to the bus are made via the open-drain I/O lines SDA and SCL.
The following bus protocol has been defined (See Figure 4):
§
§
Data transfer may be initiated only when the bus is not busy.
During data transfer, the data line must remain stable whenever the clock line is HIGH. Changes in
the data line while the clock line is high will be interpreted as control signals.
Accordingly, the following bus conditions have been defined:
Bus not busy: Both data and clock lines remain HIGH.
Start data transfer: A change in the state of the data line from high to low, while the clock line is high,
defines a START condition.
Stop data transfer: A change in the state of the data line from low to high, while the clock line is high,
defines a STOP condition.
6 of 12
DS1672
Data valid: The state of the data line represents valid data when, after a START condition, the data line
is stable for the duration of the high period of the clock signal. The data on the line must be changed
during the low period of the clock signal. There is one clock pulse per bit of data.
Each data transfer is initiated with a START condition and terminated with a STOP condition. The
number of data bytes transferred between the START and the STOP conditions is not limited, and is
determined by the master device. The information is transferred byte-wise and each receiver
acknowledges with a ninth bit.
Acknowledge: Each receiving device, when addressed, is obliged to generate an acknowledge after the
reception of each byte. The master device must generate an extra clock pulse which is associated with
this acknowledge bit.
A device that acknowledges must pull down the SDA line during the acknowledge clock pulse in such a
way that the SDA line is stable LOW during the HIGH period of the acknowledge related clock pulse. Of
course, setup and hold times must be taken into account. A master must signal an end of data to the slave
by not generating an acknowledge bit on the last byte that has been clocked out of the slave. In this case,
the slave must leave the data line HIGH to enable the master to generate the STOP condition.
DATA TRANSFER ON 2-WIRE SERIAL BUS Figure 4
SDA
MSB
slave address
R/W
direction
bit
acknowledgement
signal from receiver
acknowledgement
signal from receiver
SCL
1
START
CONDITION
2
6
7
8
9
1
2
3-8
ACK
8
9
ACK
repeated if more bytes
are transferred
STOP CONDITION
OR
REPEATED
START CONDITION
Figures 5 and 6 detail how data transfer is accomplished on the 2-wire bus. Depending upon the state of
the R/ W bit, two types of data transfer are possible:
1. Data transfer from a master transmitter to a slave receiver. The first byte transmitted by the
master is the slave address. Next follows a number of data bytes. The slave returns an acknowledge
bit after each received byte.
2. Data transfer from a slave transmitter to a master receiver. The first byte (the slave address) is
transmitted by the master. The slave then returns an acknowledge bit. Next follows a number of data
bytes transmitted by the slave to the master. The master returns an acknowledge bit after all received
bytes other than the last byte. At the end of the last received byte, a “not acknowledge” is returned.
The master device generates all of the serial clock pulses and the START and STOP conditions. A
transfer is ended with a STOP condition or with a repeated START condition. Since a repeated START
condition is also the beginning of the next serial transfer, the bus will not be released.
7 of 12
DS1672
The DS1672 may operate in the following two modes:
1. Slave receiver mode (DS1672 write mode): Serial data and clock are received through SDA and
SCL. After each byte is received, an acknowledge bit is transmitted. START and STOP conditions
are recognized as the beginning and end of a serial transfer. Address recognition is performed by
hardware after reception of the slave address and direction bit. The slave address byte is the first byte
received after the START condition is generated by the master. The slave address byte contains the
7-bit DS1672 address, which is 1101000, followed by the direction bit (R/ W ), which for a write is a
0. After receiving and decoding the slave address byte the DS1672 outputs an acknowledge on the
SDA line. After the DS1672 acknowledges the slave address + write bit, the master transmits a
register address to the DS1672. This will set the register pointer on the DS1672. The master will
then begin transmitting each byte of data with the DS1672 acknowledging each byte received. The
master will generate a STOP condition to terminate the data write.
2. Slave transmitter mode (DS1672 read mode): The first byte is received and handled as in the slave
receiver mode. However, in this mode, the direction bit will indicate that the transfer direction is
reversed. Serial data is transmitted on SDA by the DS1672 while the serial clock is input on SCL.
START and STOP conditions are recognized as the beginning and end of a serial transfer. Address
recognition is performed by hardware after reception of the slave address and direction bit. The slave
address byte is the first byte received after the START condition is generated by the master. The
slave address byte contains the 7-bit DS1672 address, which is 1101000, followed by the direction bit
(R/ W ), which for a read is a 1. After receiving and decoding the slave address byte the DS1672
outputs an acknowledge on the SDA line. The DS1672 then begins to transmit data starting with the
register address pointed to by the register pointer. If the register pointer is not written to before the
initiation of a read mode the first address that is read is the last one stored in the register pointer. The
DS1672 must receive a “not acknowledge” to end a read.
DATA WRITE – SLAVE RECEIVER MODE Figure 5
DATA READ – SLAVE TRANSMITTER MODE Figure 6
8 of 12
DS1672
ABSOLUTE MAXIMUM RATINGS*
Voltage on Any Pin Relative to Ground
Operating Temperature
Storage Temperature
Soldering Temperature
-0.5V to +6.0V
-40°C to +85°C
-55°C to +125°C
See J-STD-020A specification
* This is a stress rating only and functional operation of the device at these or any other conditions above
those indicated in the operation sections of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods of time may affect reliability.
RECOMMENDED DC OPERATING CONDITIONS
PARAMETER
Supply Voltage (DS1672-33)
(DS1672-3)
(DS1672-2)
Logic 1
Logic 0
Backup Supply Voltage
SYMBOL
VCC
VCC
VCC
VIH
VIL
VBACKUP
MIN
2.97
2.7
1.8
0.7VCC
-0.5
1.3
DC ELECTRICAL CHARACTERISTICS
DS1672-33
PARAMETER
Active Supply Current
Standby Current
Power-Fail Voltage
Logic 0 Output (VOL = 0.4V)
SYMBOL
ICCA
ICCS
VPF
IOL
SYMBOL
ICCA
ICCS
VPF
IOL
TYP
2.80
2.88
SYMBOL
ICCA
ICCS
VPF
IOL
UNITS
V
V
V
V
V
V
NOTES
MAX
600
500
2.97
3
UNITS
mA
mA
V
mA
NOTES
6
7
13
(-40°C to +85°C; VCC = 2.7 to 3.3V)
MIN
TYP
2.5
2.6
DC ELECTRICAL CHARACTERISTICS
DS1672-2
PARAMETER
Active Supply Current
Standby Current
Power-Fail Voltage
Logic 0 Output
(VCC > 2 V; VOL = 0.4V)
(VCC < 2 V; VOL = .2VCC)
(-40°C to +85°C)
MAX
3.63
3.3
2.2
VCC + 0.5
0.3VCC
3.6
(-40°C to +85°C; VCC = 2.97 to 3.63V)
MIN
DC ELECTRICAL CHARACTERISTICS
DS1672-3
PARAMETER
Active Supply Current
Standby Current
Power-Fail Voltage
Logic 0 Output (VOL = 0.4V)
TYP
3.3
3.0
2.0
MAX
600
500
2.7
3
UNITS
mA
mA
V
mA
NOTES
6
8
13
(-40°C to +85°C; VCC = 1.8 to 2.2V)
MIN
TYP
1.6
1.7
9 of 12
MAX
600
500
1.8
UNITS
mA
mA
V
NOTES
6
9
3
3
mA
13
DS1672
DC ELECTRICAL CHARACTERISTICS
PARAMETER
Timekeeping Current
Backup Standby Current
(Oscillator Off)
SYMBOL
IOSC
IBACKUP
(-40°C to +85°C; VCC < VPF)
MIN
TYP
AC ELECTRICAL CHARACTERISTICS
PARAMETER
SCL Clock
Frequency
SYMBOL
fSCL
tBUF
tHD:DAT
Data Set-up Time
tSU:DAT
tHD:STA
tLOW
tHIGH
tSU:STA
tR
tF
MIN
100
TYP
1.3
MAX
400
Standard Mode
4.7
Fast Mode
0.6
Standard Mode
4.0
Fast Mode
Standard Mode
Fast Mode
Standard Mode
Fast Mode
1.3
4.7
0.6
4.0
0.6
Standard Mode
4.7
ms
NOTES
1
ms
ms
ms
Fast Mode
0
Standard Mode
0
Fast Mode
100
Standard Mode
250
Fast Mode
20 + 0.1CB
300
Standard Mode
1000
Fast Mode
Standard Mode
UNITS
kHz
ms
0.9
20 + 0.1CB
300
Standard Mode
tSU:STO
NOTES
11
12
100
Fast Mode
Fast Mode
UNITS
mA
nA
(-40°C to +85°C; VCC > VPF)
Standard Mode
Bus Free Time
Between a STOP
and START
Condition
Hold Time
(Repeated) START
Condition
LOW Period of
SCL Clock
HIGH Period of
SCL Clock
Set-up Time for a
Repeated START
Condition
Data Hold Time
Rise Time of Both
SDA and SCL
Signals
Fall Time of Both
SDA and SCL
Signals
Set-up Time for
STOP Condition
Capacitive Load for
each Bus Line
I/O Capacitance
CONDITION
Fast Mode
MAX
1
200
ms
2,3
ms
10
ns
4
ns
4
300
0.6
4.0
ms
CB
400
CI/O
10
10 of 12
pF
pF
4
DS1672
TIMING DIAGRAM Figure 7
SDA
tBUF
tLOW
tF
tHD:STA
SCL
tHD:STA
tSU:STA
tHD:DAT
STOP
tHIGH
tSU:DAT
START
tSU:STO
REPEATED
START
POWER-UP/POWER-DOWN TIMING Figure 8
V CC
V PF(max)
V PF(min)
tF
tR
tPD
tRPU
tRPD
RST
INPUTS
OUTPUTS
DON'T CARE
RECOGNIZED
RECOGNIZED
HIGH-Z
VALID
VALID
POWER-UP/POWER-DOWN CHARACTERISTICS
PARAMETER
VCC Detect to RST (VCC Falling)
VCC Detect to RST (VCC Rising)
VCC Fall Time; VPF(MAX) to VPF(MIN)
VCC Rise Time; VPF(MIN) to VPF(MAX)
SYMBOL
tRPD
tRPU
tF
tR
MIN
(-40°C to +85°C)
TYP
250
300
0
MAX
10
UNITS
µs
ms
NOTES
6
ms
ms
WARNING:
Under no circumstances are negative undershoots, of any amplitude, allowed when device is in write
protection.
11 of 12
DS1672
NOTES:
1. After this period, the first clock pulse is generated.
2. A device must internally provide a hold time of at least 300ns for the SDA signal (referenced to the
VIHMIN of the SCL signal) in order to bridge the undefined region of the falling edge of SCL.
3. The maximum tHD:DAT has only to be met if the device does not stretch the LOW period (tLOW) of the
SCL signal.
4. CB – Total capacitance of one bus line in pF.
5. If the EOSC bit in the control register is set to logic 1, tRPU is equal to 250ms plus the start-up time of
the crystal oscillator.
6. ICCA specified with SCL clocking at max frequency (400kHz).
7. ICCS specified with VCC = 3.3V and SDA, SCL = 3.3V.
8. ICCS specified with VCC = 3.0V and SDA, SCL = 3.0V.
9. ICCS specified with VCC = 2.0V and SDA, SCL = 2.0V.
10. A fast mode device can be used in a standard mode system, but the requirement tSU:DAT >= to 250ns
must then be met. This will automatically be the case if the device does not stretch the LOW period
of the SCL signal. If such a device does stretch the LOW period of the SCL signal, it must output the
next data bit to the SDA line tR max + tSU:DAT = 1000 + 250 = 1250ns before the SCL line is released.
11. IOSC specified with VCC = 0V, VBACKUP = 3.6V and oscillator enabled.
12. IBACKUP specified with VCC = 0V, VBACKUP = 3.6V and oscillator disabled.
13. SDA and RST .
12 of 12