ETC H470156400

Current and Voltage Controls
3-Phase Voltage Sequence Control
Type H 470
• 3-phase monitoring relay for phase
sequence/phase loss
• Measures when all 3 phases are present and
have the correct phase sequence
• Output: 10 A SPDT relay
• For mounting on DIN-rail in accordance with
DIN/EN 50 022
• H4-housing
• LED-indication for power supply and output ON
• Power supply is the 3-phase measuring voltage
Product Description
Ordering Key
H 470 156 400
right phase sequence when
connecting a load to a 3phase electrical system.
Housing
Type
Output
Power supply
Plug
Output
Supply: 230 VAC
Supply: 400 VAC
Screw
terminals
SPDT
H 470 156 230
H 470 156 400
3-phase monitoring and
phase sequence/phase loss
relay for DIN-rail mounting.
Frequently used to secure the
Type Selection
Input Specifications
Output Specifications
Input
Terminal 21
Terminal 22
Terminal 23
Terminal 24
Output
Rated insulation voltage
Neutral (optional connection)
Phase L1
Phase L2
Phase L3
measures on own supply
Supply Specifications
Power supply AC types
Rated operational voltage
Through term. 21, 22, 230
23 & 24
400
Overvoltage cat. III (IEC 60664)
(IEC 60038)
3 x 230 VAC ± 15%,
45 to 65 Hz
3 x 400 VAC ± 15%,
45 to 65 Hz
Voltage interruption
≤ 40 ms
Dielectric voltage
None (supply/elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral,
line/line), direct connection
to electronics
Rated operational power
2.5 VA
Specifications are subject to change without notice (26.10.99)
Contact ratings (AgCdO)
Resistive loads
AC 1
DC 1
or
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
AC 1
Operating frequency
Dielectric strength
Dielectric voltage
Rated impulse withstand volt.
SPDT relay
250 VAC (rms)
(cont./elect.)
µ (micro gap)
10 A/250 VAC (2500 VA)
1 A/250 VDC (250 W)
10 A/25 VDC (250 W)
2.5 A/230 VAC
5 A/24 VDC
≥ 30 x 106 operations
≥ 2.5 x 105 operations
(at max. load)
≤ 7200 operations/h
≥ 2 kVAC (rms) (cont./elect.)
4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
1
H 470
General Specifications
Reaction time
Indication for
Power supply ON
Output ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Weight
Mode of Operation
τ = 0.5 s, worst case reaction
time may be up to 5 x τ
LED, green
LED, red
(IEC 60947-1)
IP 20 B/front IP 40 D (IEC 60529)
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
300 g
The relay measures on its own
3-phased power supply and
operates when all phases are
present and the phase sequence is correct.
Example 1
Own power supply
monitoring
The relay is for monitoring
that the power supply has
correct phase sequence and
that all phase voltages are
present. The relay shall be
mounted in front of the fuses
of each load.
Example 2
Load monitoring
The relay releases in case of
interruption of one of the
phases, provided that the
voltage regenerated by electric motors on the interrupted
phase does not exceed 70%
of the nominal voltage. If it
exceeds this value the connection cannot be recommended (see description ex. 3).
Example 3
If the value of the regenerated voltage is slightly higher
than 70% of the nominal voltage, the relay releases when
neutral is connected to terminal 21 as sensitivity is improved.
Wiring Diagrams
Example 1
Example 2
Example 3
µ
H 470
µ
µ
H 470
H 470
Operation Diagram
Phase L1, terminal 22
Phase L2, terminal 23
Phase L3, terminal 24
Relay ON
2