ETC DPA01CM44

Monitoring Relays
3-Phase Sequence and Phase Loss
Types DPA01, PPA01
• 3-phase monitoring relays for phase
sequence and phase loss
• Detect when all 3 phases are present and have the
correct sequence
• Measure on own power supply
• Power supply range: 208 to 480 VAC (±15%)
• Output: 8 A SPDT relay or 8 A DPDT normally energized
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DPA01) or plug-in module (PPA01)
• 22.5 mm Euronorm housing (DPA01) or 36 mm plug-in
module (PPA01)
• LED indication for relay and power supply ON
DPA01D
PPA01
Product Description
3-phase relay for detection of
incorrect phase sequence,
total and partial phase loss.
Supply range from 208 to 480
VAC covered by one multivoltage relay (or by two multivoltage relays for DPA01D
Ordering Key
DPA 01 C M44
models). For mounting on
DIN-rail or plug-in module.
The device detects regenerated voltages up to 70% of
the mains nominal voltage
(phase-neutral).
Housing
Function
Type
Item number
Output
Power supply
Supply: 208-240 VAC
Supply: 380-480 VAC
DPA 01 D M23
DPA 01 D M48
Type Selection
Mounting
Output
Supply: 208-480 VAC
DIN-rail
DIN-rail
Plug-in
SPDT
DPDT
SPDT
DPA 01 C M44
PPA 01 C M44
Input Specifications
Input
L1, L2, L3
Measuring ranges
208 to 480 VAC (DPA01C)
208 to 415 VAC (PPA01C)
208 to 240 VAC (DPA01D)
380 to 480 VAC (DPA01D)
ON-level
Output Specifications
DPA01: Terminals L1, L2, L3
PPA01: Terminals 5, 6, 7
Measures on own supply
177 to 550 VAC
177 to 475 VAC
177 to 275 VAC
323 to 550 VAC
> 70% of the mains phaseneutral voltage
Output
Rated insulation voltage
Contact ratings (AgSnO2)
DPA01C, PPA01 (SPDT):
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
DPA01D (DPDT):
Resistive loads
AC 1
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
SPDT or DPDT relay, N.E.
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
8 A @ 250 VAC
3 A @ 250 VAC
2 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Specifications are subject to change without notice (21.10.00)
1
DPA01, PPA01
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
L1, L2, L3
(DPA01)
5, 6, 7
(PPA01)
DPA01CM44
Reaction time
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Repeatability
Indication for
Power supply ON
Relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
PPA01CM44
DPA01DM23
DPA01DM48
Rated operational power
Overvoltage cat. III
(IEC 60664, IEC 60038)
208 to 480 VAC ± 15%,
45 to 65 Hz
208 to 415 VAC ± 15%,
45 to 65 Hz
208 to 240 VAC ± 15%,
45 to 65 Hz
380 to 480 VAC ± 15%,
45 to 65 Hz
13 VA @ 400 VAC, 50 Hz
13 VA @ 230 VAC, 50 Hz
(DPA01DM23 only)
Supplied by L2 and L3
Storage temperature
Housing dimensions
DIN-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
< 100 ms
< 300 ms
(15 min warm-up time)
± 1000 ppm/°C
± 0.5% on full scale
LED, green
LED, yellow
(EN 60529)
IP 20
3 (DPA01), 2 (PPA01)
-20 to 60°C, R.H. < 95%
@ 475 VAC, 65 Hz
-20 to 50°C, R.H. < 95%
@ 550 VAC, 65 Hz
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 100 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Mode of Operation
DPA01 and PPA01 monitor
their own 3-phase power
supply. The relay operates
when all the phases are present
and
the
phase
sequence is correct. The
relay releases when one
phase-neutral voltage drops
below 70% of the other
phase-neutral voltages.
Example 1
The relay monitors that the
power supply has the correct
phase sequence and that all
phase voltages are present.
Example 2
The relay releases in case of
interruption of one or more
phases, provided that the
regenerated voltage does
not exceed 70% of the
mains phase-neutral voltage.
Operation Diagram
L1
L1
L2
L3
L1
L2
L2
L1
L2
L2
L3
L3
L3
L1
L3
Relay ON
2
Specifications are subject to change without notice (21.10.00)
DPA01, PPA01
Wiring Diagrams
Example 1
Example 1
L3
L2
L1
L3
L2
L1
µ
m<3
L1 L2 L3
12
µ
µ
14 22
24
m<3
L2
6
5
7
4
3
L2
L3
11
DPA01C...
DPA01D...
L3
21
1
DPA01D
Example 2
Example 2
L3
L2
L1
L3
L2
L1
µ
m<3
L1 L2 L3
12
µ
14 22
µ
24
m<3
L2
5
6
7
4
3
L2
L3
11
DPA01C...
DPA01D...
L3
21
1
DPA01D
DPA01
Specifications are subject to change without notice (21.10.00)
PPA01
3