AD ADM1033ARQZ-REEL

Thermal Monitor and
Fan Speed (RPM) Controller
ADM1033
Look-up table for temperature-to-fan-speed control
Linear and discrete options for look-up table
FAN_FAULT output
THERM input, used to time PROCHOT assertions
REF input, used as reference for THERM (PROCHOT)
3 V to 5.5 V supply
Small 16-lead QSOP package
FEATURES
1 local and 1 remote temperature channel
±1.5°C accuracy on local and remote channels
Automatic series resistance cancellation on remote
Temperature channels > 1 kΩ
Fast (up to 64 measurements per second)
SMBus 2.0, 1.1, and 1.0 compliant
SMBus address input/LOCATION input to UDID
Programmable over-/undertemperature limits
Programmable fault queue
SMBusALERT output
Fail-safe overtemperature comparator output
Fan speed (RPM) controller
APPLICATIONS
Desktop and notebook PCs
Embedded systems
Telecommunications equipment
LCD projectors
FUNCTIONAL BLOCK DIAGRAM
VCC
6
ADM1033
SMBUS
ADDRESS
SERIAL BUS
INTERFACE
MANUAL FAN
SPEED CONTROL
REGISTERS
ADDRESS
POINTER
REGISTER
TEMPERATURE-TOFAN-SPEED
LOOK-UP TABLE
DRIVE 1
TACH 2
NC 4
FAN SPEED
CONTROLLER
ALERT
STATUS
REGISTER
FAN RESPONSE
TACH SIGNAL
CONDITIONING
THERM
FAULT
QUEUE
SCL
15
SDA
8
FAN_FAULT
3
ALERT Comp
14
SMBusALERT
7
THERM
LIMIT
COMPARATOR
VALUE AND
LIMIT
REGISTERS
FAN
SPEED
COUNTER
THERM PERCENT
TIMER
FAULT
QUEUE
REF 8
HYSTERESIS
REGISTERS
LOCATION 13
9
D+ 10
NC 11
ANALOG
MULTIPLEXER
ADC
OFFSET
REGISTERS
SRC
BLOCK
CONVERSION
RATE REGISTER
BAND GAP
REFERENCE
NC 12
BAND GAP
TEMPERATURE
SENSOR
CONFIGURATION
REGISTERS
5
NC = NO CONNECT
04937-0-001
D–
MASK
REGISTERS
16
GND
Figure 1.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective owners.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
www.analog.com
Fax: 781.326.8703
© 2004 Analog Devices, Inc. All rights reserved.
ADM1033
TABLE OF CONTENTS
General Description ......................................................................... 3
Handling SMBusALERT Interrupts......................................... 22
Specifications..................................................................................... 4
Interrupt Masking Register ....................................................... 22
Absolute Maximum Ratings............................................................ 6
FAN_FAULT Output ................................................................. 23
Thermal Characteristics .............................................................. 6
Fault Queue ................................................................................. 23
ESD Caution.................................................................................. 6
Conversion Rate Register .......................................................... 23
Pin Configuration and Function Descriptions............................. 7
THERM I/O Timer and Limits ................................................ 23
Typical Performance Characteristics ............................................. 8
THERM % Limit Register ......................................................... 24
Functional Description .................................................................. 10
Internal Registers........................................................................ 10
Fan Drive Signal ......................................................................... 25
Synchronous Speed Control ..................................................... 25
Serial Bus Interface..................................................................... 10
Fan Inputs.................................................................................... 26
LOCATION Input ...................................................................... 10
Fan Speed Measurement ........................................................... 26
SMBus 2.0 ARP-Capable Mode ................................................ 10
Fan Speed Measurement Registers........................................... 27
SMBus 2.0 Fixed-and-Discoverable Mode.............................. 12
Reading Fan Speed ..................................................................... 27
SMBus 2.0 Read and Write Operations ................................... 12
Calculating Fan Speed ............................................................... 27
Register Addresses for Single/Block Byte Modes ................... 14
Alarm Speed................................................................................ 27
Write Operations ........................................................................ 14
Look-Up Table: Modes of Operation....................................... 28
Read Operations ......................................................................... 15
Look-Up Table ............................................................................ 28
SMBus Timeout .......................................................................... 15
Setting Up the Look-Up Table in Linear Mode...................... 29
Packet Error Checking (PEC) ................................................... 15
Selecting which Temperature Channel Controls a Fan......... 29
Alert Response Address (ARA) ................................................ 15
Look-Up Table Hysteresis ......................................................... 29
Temperature Measurement System.............................................. 16
Internal Temperature Measurement ........................................ 16
Programming the THERM Limit for Temperature Channels
....................................................................................................... 30
Remote Temperature Measurement......................................... 16
XOR Tree Test Mode.................................................................. 30
Additional Functions ................................................................. 18
Lock Bit........................................................................................ 30
Layout Considerations ................................................................... 19
SW Reset...................................................................................... 30
Limits, Status Registers, and Interrupts ....................................... 20
Outline Dimensions ....................................................................... 39
8-Bit Limits.................................................................................. 20
Ordering Guide .......................................................................... 39
Out-of-Limit Comparisons ....................................................... 20
Analog Monitoring Cycle Time................................................ 20
REVISION HISTORY
8/04—Revision 0: Initial Version
Status Registers ........................................................................... 20
ALERT Interrupt Behavior........................................................ 21
Rev. 0 | Page 2 of 40
ADM1033
GENERAL DESCRIPTION
The ADM1033 is a remote and local temperature sensor and fan
controller. Its remote channel accurately monitors the
temperature of a remote thermal diode, which can be a discrete
2N3904/6 or located on a microprocessor die. The device can
monitor its own ambient temperature as well.
The ADM1033 is also used to monitor and control the speed
of a cooling fan. The user can program a target fan speed, or use
the look-up table to input a temperature-to-fan speed profile.
The look-up table can be configured to run the fan at discrete
speeds (discrete mode) or to ramp the fan speed with temperature (linear mode).
The ADM1033 communicates over a 2-wire SMBus 2.0 interface. An 8-level LOCATION input allows the user to choose
between SMBus 1.1 and SMBus 2.0.
The ALERT output indicates error conditions. In addition, the
THERM I/O signals overtemperature as an output and times
THERM assertions as an input. Pin 8 can be configured as a
reference input for the THERM (PROCHOT) input.
Rev. 0 | Page 3 of 40
ADM1033
SPECIFICATIONS
TA = TMIN to TMAX, VCC = VMIN to VMAX, unless otherwise noted.1
Table 1.
Parameter
POWER SUPPLY
Supply Voltage, VCC2
Supply Current, ICC
Undervoltage Lockout Threshold
Power-On Reset Threshold
TEMPERATURE-TO-DIGITAL CONVERTER
Internal Sensor Accuracy
Min
Typ
Max
Units
3.0
3.3
3.6
3
900
V
mA
µA
V
V
2.5
1
2.4
±1
±2
+2
−4
Resolution
External Diode Sensor Accuracy
0.03125
±0.5
±1
±1
Series Resistance Cancellation
Power Supply Sensitivity
Conversion Time (Local Temperature)
Conversion Time (Remote Temperature)
Total Conversion Time
OPEN-DRAIN DIGITAL OUTPUTS (ALERT,
THERM, FAN_FAULT DRIVE)
Output Low Voltage, VOL
High Level Output Leakage Current, IOH
DIGITAL INPUT LEAKAGE CURRENT (TACH)
Input High Current, IIH
Input Low Current, IIL
Input Capacitance, CIN
DIGITAL INPUT LOGIC LEVELS (TACH)
Input High Voltage, VIH
Input Low Voltage, VIL
Hysteresis
OPEN-DRAIN SERIAL DATA BUS OUTPUT
(SDA)
Output Low Voltage, VOL
High Level Output Leakage Current, IOH
SERIAL BUS DIGITAL INPUTS (SCL, SDA)
Input High Voltage, VIH
Input Low Voltage, VIL
Hysteresis
ANALOG INPUTS (LOCATION, REF)
Input Resistance
V
µA
IOUT = −6.0 mA; VCC = +3 V
VOUT = VCC; VCC = 3 V
1
µA
µA
pF
VIN = VCC
VIN = 0
−1
7
5.5
+0.8
V
V
mV p-p
0.4
1
V
µA
0.8
V
V
mV
160
kΩ
500
0.1
2.1
500
80
125
−40°C ≤ TD ≤ +100°C; TA = +40°C
−40°C ≤ TD ≤ +100°C; +20°C ≤ TA ≤ +60°C
−40°C ≤ TD ≤ +100°C; −40°C ≤ TA ≤ +100°C
0.4
1
1000
±1
11
32
43
2.0
−0.3
20°C ≤ TA ≤ 60°C
−40°C ≤ TA ≤ +100°C
Averaging enabled
Averaging enabled
Averaging enabled
0.03125
85
34
5
0.1
Interface inactive, ADC active
Standby mode
°C
°C
°C
µA
µΑ
µΑ
Ω
%/V
ms
ms
ms
+2
−3
Resolution
Remote Sensor Source Current
°C
°C
°C
°C
Test Conditions/Comments
Rev. 0 | Page 4 of 40
High level
Mid level
Low level
IOUT = −6.0 mA; VCC = +3 V
VOUT = VCC
ADM1033
Parameter
TACHOMETER ACCURACY
Fan Speed Measurement Accuracy
AGTL + INPUT (THERM)
Input High Level
Input Low Level
SERIAL BUS TIMING3
Clock Frequency, fSCLK
Glitch Immunity, tSW
Bus Free Time, tBUF
Start Setup Time, tSU:STA
Start Hold Time, tHD:STA
Stop Condition Setup Time, tSU:STO
SCL Low Time, tLOW
SCL High Time, tHIGH
SCL, SDA Rise Time, tr
SCL, SDA Fall Time, tf
Data Setup Time, tSU:DAT
Detect Clock Low Timeout, tTIMEOUT
Min
Typ
Max
Units
±4
%
0.4
V
V
0.75 × REF
Test Conditions/Comments
See Figure 2
400
50
1.3
0.6
0.6
0.6
1.3
0.6
1000
300
100
25
35
kHz
ns
µs
µs
µs
µs
µs
µs
ns
ns
ns
ms
See Note 4
1
Typicals are at TA = 25°C and represent most likely parametric norm. Standby current typ is measured with VCC = 3.3 V. Timing specifications are tested at logic levels of
VIL = 0.8 V for a falling edge and VIH = 2.1 V for a rising edge.
Operation at 5.5 V is guaranteed by design, not production tested.
3
Guaranteed by design, not production tested.
4
SMBus timeout disabled by default. See the SMBus Timeout section for more information.
2
tLOW
tR
tF
tHD:STA
SCL
tHD:DAT
tHIGH
tSU:STA
tSU:DAT
tSU:STO
SDA
tBUF
P
S
S
Figure 2. Serial Bus Timing Diagram
Rev. 0 | Page 5 of 40
P
04937-0-003
tHD:STA
ADM1033
ABSOLUTE MAXIMUM RATINGS
Table 2.
Parameter
Positive Supply Voltage (VCC)
Value
−0.3 V to +6.5 V
Voltage on Any Input or Output Pin except
FAN_FAULT and LOCATION
Voltage on FAN_FAULT1
Voltage on LOCATION
Input Current at Any Pin
Maximum Junction Temperature (TJmax)
Storage Temperature Range
Lead Temperature, Soldering (10 sec)
IR Reflow Peak Temperature
ESD Rating—All Pins
−0.3 V to +6.5 V
1
VCC
VCC + 0.3V
±20 mA
150°C
−65°C to +150°C
300°C
220°C
1500 V
Stresses above those listed under Absolute Maximum Ratings
may cause permanent damage to the device. This is a stress
rating only; functional operation of the device at these or any
other conditions above those indicated in the operational
section of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect
device reliability.
THERMAL CHARACTERISTICS
16-Lead QSOP Package:
θJA = 150°C/W, θJC = 39°C/W
During power-up, the voltage on FAN_FAULT should not be higher than VCC.
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulates
on the human body and test equipment and can discharge without detection. Although this product features
proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy
electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance
degradation or loss of functionality.
Rev. 0 | Page 6 of 40
ADM1033
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
1
16
SCL
TACH
2
15
SDA
ALERT Comp
3
ADM1033
14
SMBusALERT
NC
4
TOP VIEW
(Not to Scale)
13
LOCATION
GND
5
12
NC
VCC
6
11
NC
THERM
7
10
D+
FAN_FAULT/REF
8
9
D–
NC = NO CONNECT
04937-0-002
DRIVE
Figure 3. Pin Configuration
Table 3. Pin Function Descriptions
Pin No.
1
2
3
Mnemonic
DRIVE
TACH
ALERT Comp
4
5
6
7
NC
GND
VCC
THERM
8
FAN_FAULT/REF
9
10
11
12
13
D−
D+
NC
NC
LOCATION
14
SMBusALERT
15
SDA
16
SCL
Description
DRIVE Pin Drives the Fan. Open-drain output. Requires a pull-up resistor.
Fan Speed Measurement Input. Connects to the fan’s TACH output to measure the fan speed.
Open-Drain Active Low Output. Asserts low whenever a measurement goes outside its programmed limits,
if not masked. Automatically goes high again when the measured parameter falls back within its limits.
No Connect.
Ground for Analog and Digital Circuitry.
Power. Can be powered by 3.3 V standby power, if monitoring in low power states is required.
Can be configured as an overtemperature interrupt output, or as an input to monitor PROCHOT output of
an INTEL CPU. A timer measures assertion times on the THERM pin (either input or output).
FAN_FAULT: Open-Drain Output. Asserts low whenever the fan stalls.
REF: Analog Input Reference for THERM input.
Cathode Connection for the Thermal Diode or Diode-Connected Transistor.
Anode Connection for the Thermal Diode or Diode-Connected Transistor.
No Connect.
No Connect.
8-Level Analog Input. Used to determine the correct SMBus version and the SMBus address (in fixed-anddiscoverable mode), and to set the LLL bits in the UDID (in ARP-capable mode).
Open-Drain Output. Alerts the system in the case of out-of-limit events such as overtemperature. Can be
reset only with software.
Serial Bus Bidirectional Data. Connects to the SMBus master’s data line. Requires a pull-up resistor, if one is
not provided elsewhere in the system.
Serial SMBus Clock Input. Connects to the SMBus master’s clock line. Requires a pull-up resistor, if one is
not provided elsewhere in the system.
Rev. 0 | Page 7 of 40
ADM1033
TYPICAL PERFORMANCE CHARACTERISTICS
20
40
EXT 100mV p-p
EXT 250mV p-p
TEMPERATURE ERROR (°C)
15
D+ TO GND
D+ TO VCC
–20
–40
–60
–80
–100
0
10
20
30
40
50
60
70
LEAKAGE RESISTANCE (MΩ)
80
90
5
0
–5
–10
0
100
Figure 4. Temperature Error vs. PCB Track Resistance, DXP to GND and VCC
0
50
–10
45
DEV 33 (°C)
–20
–30
–40
DEV 31 (°C)
–50
1M
2M
3M
4M
5M
6M
Figure 7. Remote Temperature Error vs. Power Supply Noise Frequency
TEMPERATURE ERROR (°C)
TEMPERATURE ERROR (°C)
10
04937-0-007
0
04937-0-004
TEMPERATURE ERROR (°C)
20
DEV 32 (°C)
–60
40
35
30
25
100mV
20
15
20mV
–70
–80
0
2
4
6
8
CAPACITANCE (nF)
10
04937-0-008
04937-0-005
10
50mV
5
00
12
0
Figure 5. Remote Temperature Error vs. D+, D− Capacitance
1M
2M
3M
4M
NOISE FREQUENCY (Hz)
5M
6M
Figure 8. Remote Temperature Error vs. Common-Mode Noise Frequency
Coupled on D+ and D−
100
4.0
90
3.5
DEV 33
70
60
50
DEV 31
40
30
20
DEV 32
04937-0-006
10
0
–10
1
2
3
4
5
SERIES RESISTANCE IN D+/D– LINES (kΩ)
3.0
2.5
2.0
20mV
1.5
1.0
0.5
04937-0-009
TEMPERATURE ERROR (°C)
TEMPERATURE ERROR (°C)
80
10mV
0
6
0
Figure 6. Remote Temperature Error vs. Series Resistance on D+ and D−
1M
2M
3M
4M
NOISE FREQUENCY
5M
6M
Figure 9. Remote Temperature Error vs. Differential-Mode Noise Frequency
Coupled on D+ and D−
Rev. 0 | Page 8 of 40
ADM1033
0.7
2
1
0.6
STANDBY SUPPLY CURRENT
–1
–2
–3
MEAN
S1
S2
S3
S4
S5
–5
–6
–7
–60
–40
V1
V2
V3
V4
V5
–20
LOW 4 SIGMA
0
20
40
60
80
DIODE TEMPERATURE (°C)
100
120
0.5
0.4
0.3
0.2
0.1
04937-0-013
–4
04937-0-010
TEMPERATURE ERROR (°C)
HIGH 4 SIGMA
0
0
0
140
Figure 10. Remote Temperature Error vs. Actual Diode Temperature
1
2
3
4
SUPPLY VOLTAGE (V)
5
6
Figure 13. Standby Supply Current vs. Supply Voltage
2
1200
1
HIGH 4 SIGMA
1000
0
800
ICC (µA)
–2
–3
MEAN
S1
S2
S3
S4
S5
–5
–6
–7
–50
V1
V2
V3
V4
V5
0
DEV 31
400
DEV 32
DEV 33
LOW 4 SIGMA
50
TEMPERATURE (°C)
200
04937-0-011
–4
600
100
04937-0-014
ERROR (°C)
–1
0
0.01
150
Figure 11. Local Temperature Error vs. Actual Temperature
0.1
1
10
CONVERSION RATE (Hz)
100
Figure 14. Supply Current vs. Conversion Rate
430
1.55
420
1.50
DEV 31
SUPPLY CURRENT
400
DEV 33
390
380
1.45
1.40
1.35
DEV 32
1.30
360
1
10
100
1.25
–60
1000
FSCL (kHz)
Figure 12. Standby Supply Current vs. SCLK Frequency
04937-0-015
370
04937-0-012
ICC (µA)
410
–40
–20
0
20
40
TEMPERATURE (°C)
60
80
Figure 15. Supply Current vs. ADM1033 Temperature
Rev. 0 | Page 9 of 40
100
ADM1033
FUNCTIONAL DESCRIPTION
VCC
The ADM1033 is a local and remote temperature monitor
and fan controller used in a variety of applications, including
microprocessor-based systems. The device accurately monitors
remote and ambient temperature and uses that information to
quietly control the speed of a cooling fan. Whenever the fan
stalls, the device asserts a FAN_FAULT output.
ADM1033
R1
LOCATION
04937-0-016
PIN 13
R2
GND
Figure 16. Bootstrapping the LOCATION Input
SMBus 2.0 ARP-CAPABLE MODE
In ARP-capable mode, the ADM1033 supports such features as
address resolution protocol (ARP) and unique device identifier
(UDID). The UDID is a 128-bit message that describes the
ADM1033’s capabilities to the master. The UDID also includes a
vendor-specific ID for functionally equivalent devices.
VCC
INTERNAL REGISTERS
Table 4 gives a brief description of the ADM1033’s principal
internal registers. For more detailed information on the
function of each register, refer to .
SERIAL BUS INTERFACE
The ADM1033 communicates with the master via the 2-wire
SMBus 2.0 interface. It supports two SMBus 2.0 versions,
determined by the value of the LOCATION input resistors.
ADM1033 NO. 1
ARP
LOCATION = 111
1.5kΩ
ARP
LOCATION = 110
1kΩ
ARP
LOCATION = 101
1kΩ
ARP
LOCATION = 100
1kΩ
FD
ADDRESS = 53h
1kΩ
FD
ADDRESS = 52h
1kΩ
FD
ADDRESS = 51h
1.5kΩ
ADM1033 NO. 2
ADM1033 NO. 3
ADM1033 NO. 4
ADM1033 NO. 5
ADM1033 NO. 6
ADM1033 NO. 7
FD
ADDRESS = 50h
The first version is fully ARP-capable. This means that it
supports address resolution protocol (ARP), allowing the
master to dynamically address the device on power-up. It
responds to ARP commands such as “Prepare to ARP.”
ADM1033 NO. 8
GND
04937-0-017
The ADM1033 has a THERM I/O. As an input, this measures
assertions on the THERM pin. As an output, it asserts a low
signal to indicate when the measured temperature exceeds the
programmed THERM temperature limits. The ADM1033
communicates over an SMBus 2.0 interface. Its LOCATION
input determines which version of SMBus to use, as well as the
SMBus address (in fixed-and-discoverable mode), and the
LOCATION bits in the UDID (in ARP-capable mode).
Figure 17. Setting Up Multiple ADM1033 Addresses
The second SMBus version, fixed-and-discoverable, is
backward-compatible with SMBus 1.0 and 1.1. In this mode, the
ADM1033 powers up with a fixed address, which is determined
by the state of the LOCATION pin on power-up. Note: when
using the ADM1033, addresses 0xC2 and 0xCA should not be
used by any other device on the bus.
LOCATION INPUT
The LOCATION input is a resistor divider input. It has multiple
functions and can specify the following: the SMBus version
(in fixed-and-discoverable or ARP-capable modes); the SMBus
address (in fixed-and-discoverable mode); and the LLL bits
(in UDID in ARP-capable mode).
The voltage of this 8-level input is set by a potential divider. The
voltage on LOCATION is sampled on power-up and digitized
by the on-chip ADC to determine the LOCATION input value.
Because the LOCATION input is sampled only at power-up,
changes made while power is applied have no effect.
In SMBus 2.0 mode, this vendor-specific ID is generated by an
on-chip random number generator. This should enable two
adjacent ADM1033s in the same system to power-up with a
different vendor-specific ID, allowing the master to identify the
two separate ADM1033s and assign a different address to each.
The state of the LOCATION input on power-up is also reflected
in the UDID. This is useful when there are more than one
ADM1033 in the system, so the master knows which one it is
communicating with. The UDID values are listed in Table 6.
The SMBus 2.0 master issues both general and directed ARP
commands. A general command is directed at all ARP devices.
A directed command is targeted at a single device, once an
address has been established. The PEC byte must be used for
ARP commands (refer to Packet Error Checking (PEC)). The
ADM1033 responds to the following commands:
•
Prepare to ARP (general)
•
Reset device (general and directed)
•
Get UDID (general and directed)
•
Assign address (general)
Rev. 0 | Page 10 of 40
ADM1033
Table 4. Internal Register Descriptions
Register
Configuration
Conversion Rate
Address Pointer
Status
Interrupt Mask
Value and Limit
Offset
THERM Limit and
Hysteresis
Look-Up Table
THERM % Ontime and
THERM % Limit
Description
Provides control and configuration of various functions on the device.
Determines the number of measurements per second completed by the ADM1033.
Contains the address that selects one of the other internal registers. When writing to the ADM1033, the first byte
of data is always a register address, which is written to the address pointer register.
Provides the status of each limit comparison.
Allows the option to mask ALERTs due to particular out-of-limit conditions.
Stores the results of temperature and fan speed measurements, along with their limit values.
Allows the local and remote temperature channel readings to be offset by a twos complement value written to
them. These values are automatically added to the temperature values (or subtracted from them if negative). This
allows the systems designer to optimize the system, if required, by adding or subtracting up to 15.875°C from a
temperature reading.
Contains the temperature value at which THERM is asserted and determines the level of hysteresis.
Used to program the look-up table for the fan-speed-to-temperature profile.
Reflects the state of the THERM input and monitors the duration of the assertion time of the signal as a
percentage of a time window. The user can program the length of the time window.
Table 5. Resistor Ratios for Setting LOCATION Bits
Ideal Ratio R2/(R1 + R2)
N/A
0.8125
0.6875
0.5625
0.4375
0.3125
0.1875
N/A
1
R1 (kΩ)
0
18
22
12
15
47
82
O/C
R2 (kΩ)
O/C
82
47
15
12
22
18
0
Actual R2/(R1 + R2)
1
0.82
0.6812
0.5556
0.4444
0.3188
0.18
0
Error (%)
0
+0.75
−0.63
−0.69
+0.69
+0.63
−0.75
0
SMBus Mode
ARP1
ARP1
ARP1
ARP1
FD1
FD1
FD1
FD1
SMBus Address
N/A
N/A
N/A
N/A
0x53
0x52
0x51
0x50
UDID LLL
111
110
101
100
N/A
N/A
N/A
N/A
FD denotes fixed-and-discoverable mode, ARP denotes ARP-capable mode.
Table 6. UDID Values
Bit No.
<127:120>
Name
Device Capabilities
Function
Describes the ADM1033’s capabilities (for instance, that it supports PEC
and uses a random number address device)
UDID version number (Version 1) and silicon revision identification
Vendor ID number, assigned by the SBS Implementer’s Forum or the
PCI SIG
Device ID
<1119:112>
<111:96>
Version/Revision:
Vendor ID
<95:80>
Device ID
<79:64>
Interface
<63:48>
Subsystem Vendor ID
Identifies the protocol layer interfaces supported by the ADM1033. This
represents SMBus 2.0 as the Interface version.
Subsystem Vendor ID = 0 (subsystem fields are unsupported)
<47:32>
Subsystem Device ID
Subsystem Device ID = 0 (subsystem fields are unsupported)
<31:0>
Vendor-Specific ID
A unique number per device. Contains the LOCATION Information (LLL)
and a 16-bit random number (x). See Table 5 for information on setting
the LLL bits.
Rev. 0 | Page 11 of 40
Value
11000001
00001010
00010001
11010100
00010000
00110011
00000000
00000100
00000000
00000000
00000000
00000000
00000000
00000LLL
xxxxxxxx
xxxxxxxx
ADM1033
SMBus 2.0 FIXED-AND-DISCOVERABLE MODE
The ADM1033 supports fixed-and-discoverable mode, which is
backward-compatible with SMBus 1.0 and 1.1. Fixed-anddiscoverable mode supports all the same functionality as ARPcapable mode, except for assign address—in which case it
powers up with a fixed address and is not changed by the assign
address call. The fixed address is determined by the state of the
LOCATION pin on power-up.
SMBus 2.0 READ AND WRITE OPERATIONS
The master initiates a data transfer by establishing a start
condition, defined as a high-to-low transition on the serial data
line (SDA) while the serial clock line (SCL) remains high. This
indicates that an address/data stream is to follow. All slave
peripherals connected to the serial bus respond to the start
condition and shift in the next eight bits, which consist of a 7bit address (MSB first) plus an R/W bit. The last bit determines
the direction of the data transfer (whether data is written to or
read from the slave device).
1.
The peripheral that corresponds to the transmitted address
responds by pulling the data line low during the low period
before the 9th clock pulse. This pulse is known as the
acknowledge bit. All other devices on the bus remain idle
while the selected device waits for data to be read from or
written to it. If the R/W bit is a 0, the master writes to the
slave device. If the R/W bit is a 1, the master reads from it.
2.
Data is sent over the serial bus in sequences of nine clock
pulses—eight bits of data followed by an acknowledge bit
from the slave device. Transitions on the data line must
occur during the low period of the clock signal and remain
stable during the high period, as a low-to-high transition
when the clock is high might be interpreted as a stop
signal. The number of data bytes that can be transmitted
over the serial bus in a single read or write operation is
limited only by what the master and slave devices can
handle.
3.
It is not possible to mix read and write in one operation,
because the type of operation is determined at the beginning
and cannot be changed without starting a new operation.
To write data to one of the device data registers or read data
from it, the address pointer register (APR) must be set so that
the correct data register is addressed. The first byte of a write
operation always contains an address that is stored in the APR.
If data is to be written to the device, the write operation
contains a second data byte. The second data byte is written to
the register selected by the APR.
As shown in Figure 18, the device address is sent over the bus,
followed by R/W set to 0. This is followed by two data bytes.
The first data byte is the address of the designated internal data
register, which is stored in the APR. The second data byte is the
data to be written to the internal data register.
When reading data from a register there are two possibilities:
•
If the ADM1033’s APR value is unknown or incorrect, it
must be set to the correct value before data can be read
from the desired data register. To do this, perform a write
to the ADM1033 as before; but this time send only the data
byte containing the register. (See Figure 19.) A read
operation is then performed. With the serial bus address
and the R/W bit set to 1, the data byte is read from the data
register. (See Figure 20.)
•
If the APR is known to be already at the desired address,
data can be read from the corresponding data register
without first writing to the APR. In this case, Figure 19 can
be omitted.
In Figure 18 to Figure 20, the serial bus address is determined
by the state of the LOCATION pin on power-up.
When all data bytes have been read or written, stop
conditions are established. In write mode, the master pulls
the data line high during the tenth clock pulse to assert a
stop condition. In read mode, the master device overrides
the acknowledge bit by pulling the data line high during
the low period before the ninth clock pulse. This is known
as no acknowledge. The master takes the data line low
during the low period before the tenth clock pulse, then
high during the tenth clock pulse to assert a stop condition.
Rev. 0 | Page 12 of 40
ADM1033
1
9
1
9
SCL
A6
SDA
A5
A4
A3
A2
A1
A0
R/W
START BY
MASTER
D6
D7
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1033
ACK. BY
ADM1033
FRAME 2
ADDRESS POINTER REGISTER BYTE
FRAME 1
SERIAL BUS ADDRESS BYTE
1
9
SCL (CONTINUED)
D6
D5
D4
D2
D3
D1
D0
ACK. BY
ADM1033
STOP BY
MASTER
FRAME 3
DATA BYTE
04937-0-021
D7
SDA (CONTINUED)
Figure 18. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
1
9
1
9
SCL
A6
A5
A4
A3
A2
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
D0
ACK. BY
ADM1033
START BY
MASTER
ACK. BY
ADM1033
FRAME 1
SERIAL BUS ADDRESS BYTE
STOP BY
MASTER
FRAME 2
ADDRESS POINTER REGISTER BYTE
04937-0-022
SDA
Figure 19. Writing to the Address Pointer Register Only (Send Byte)
1
9
1
9
SCL
A6
A5
A4
A3
A2
A1
A0
R/W
D7
D6
D5
D4
D3
D2
D1
ACK. BY
ADM1033
START BY
MASTER
FRAME 1
SERIAL BUS ADDRESS BYTE
NO ACK. BY STOP BY
ADM1033 MASTER
FRAME 2
DATA BYTE FROM ADM1033
Figure 20. Reading Data from a Previously Selected Register
Rev. 0 | Page 13 of 40
D0
04937-0-023
SDA
ADM1033
Write Byte
The ADM1033 supports single-byte and multiple-byte (block)
read and write operations. The register address determines
whether a single-byte or block operation is run. For a singlebyte operation, the MSB of the register address is set to 0; for a
multiple-byte operation, it is set to 1. The number of bytes read
from the ADM1033 in a multiple-byte operation is set in the
#Bytes/Block Read Register at Address 0x00. The number of
bytes written to it is specified in the block-write operation. The
addresses quoted in the register map and throughout this data
sheet assume single-byte operation. For multiple-byte operations, set the MSB of each register address to 1.
The SMBus specifications define protocols for different types of
read and write operations. The ADM1033 supports the
following SMBus write protocols: send byte, write byte, block
write, receive byte, and block read. The following abbreviations
are used in the diagrams:
S—START
P—STOP
R—READ
W—WRITE
A—ACKNOWLEDGE
A—NO ACKNOWLEDGE
In this operation, the master device sends the register address
and one data byte to the slave device as follows:
1.
The master asserts a start condition on SDA.
2.
The master sends the 7-bit slave address followed by a
write bit (low).
3.
The addressed slave device asserts ACK on SDA.
4.
The master sends the register address. The MSB of the
command code should equal 0 for a write-byte operation.
If the MSB equals 1, a block-write operation takes place.
5.
The slave asserts ACK on SDA.
6.
The master sends a data byte.
7.
The slave asserts ACK on SDA.
8.
The master asserts a stop condition on SDA to end the
transaction.
S
SLAVE
REG
W A
A
ADDRESS
ADDRESS
DATA
A P
04937-0-019
REGISTER ADDRESSES FOR
SINGLE/BLOCK BYTE MODES
Figure 22. Write Byte
Block Write
In this operation, the master device writes a block of data to a
slave address as follows. A maximum number of 32 bytes can
be written.
WRITE OPERATIONS
1. The master asserts a start condition on SDA.
Send Byte
In this operation, the master device sends a single-command
byte to a slave device as follows:
2. The master sends the 7-bit slave address followed by a write
bit (low).
3. The addressed slave device asserts ACK on SDA.
1. The master device asserts a start condition on SDA.
2. The master sends a 7-bit address followed by the write bit
(low).
4. The master sends the register address. This register address
sets up the address pointer register and determines if a
block write (MSB = 1) or a byte write (MSB = 0) takes place.
3. The addressed slave device asserts ACK on SDA.
5. The slave asserts ACK on SDA.
4. The master sends the register address.
6. The master sends the byte count.
5. The slave asserts ACK on SDA.
7. The slave asserts ACK on SDA.
6. The master asserts a stop condition on SDA, and the
transaction ends.
8. The master sends N data bytes.
10. The master asserts a stop condition on SDA to end the
transaction.
Figure 21. Send Byte
S
The ADM1033 uses the send-byte operation to write a register
address to the APR for a subsequent read from the same
address. This is illustrated in Figure 21. The user may be
required to read data from the register immediately after setting
up the address. If so, the master can assert a repeat start
condition immediately after the final ACK and carry out a
single-byte read without asserting an intermediate stop condition.
SLAVE
W A
ADDRESS
Rev. 0 | Page 14 of 40
REGISTER
ADDRESS
A
BYTE
A DATA 1 A DATA 2 A DATA N A P
COUNT
Figure 23. Block Write
04918-0-020
SLAVE
REG
W A
A P
ADDRESS
ADDRESS
04937-0-018
S
9. The slave asserts ACK on SDA after each byte.
READ OPERATIONS
S
REGISTER
ADDRESS
SLAVE
W A
ADDRESS
Receive Byte
A S
BYTE
SLAVE
R A
A DATA 1 A DATA N A P
COUNT
ADDRESS
04918-0-025
ADM1033
Figure 25. Block Read from RAM
This operation is useful when repeatedly reading a single
register. The register address must be set up prior to this, with
the MSB at 0 to read a single byte. In this operation, the master
device receives a single byte from a slave device as follows:
1. The master device asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by the
read bit (high).
SMBus TIMEOUT
The ADM1033 has a programmable SMBus timeout feature.
When this is enabled, the SMBus typically times out after 25 ms
of no activity. The timeout is disabled by default. It prevents
SMBus hangups by releasing the bus after a period of inactivity.
To enable the SDA timeout, set the SDA timeout bit (Bit 5) of
Configuration Register 1 (Address 0x01) to 1.
3. The addressed slave device asserts ACK on SDA.
To enable the SCL timeout, set the SCL timeout bit (Bit 4) of
Configuration Register 1 (Address 0x01) to 1.
4. The master receives a data byte.
5. The master sends NO ACK on SDA.
PACKET ERROR CHECKING (PEC)
6. The master asserts a stop condition on SDA and the
transaction ends.
In the ADM1033, the receive-byte protocol is used to read a
single byte from a register whose address has previously been
set by a send-byte or write-byte operation.
DATA
A P
For more information, consult www.SMBus.org.
Figure 24. Receive Byte
ALERT RESPONSE ADDRESS (ARA)
Block Read
In this operation, the master reads a block of data from a slave
device. The number of bytes to be read must be set in advance.
To do this, use a write-byte operation to the #Bytes/Block Read
Register at Address 0x00. The register address determines
whether a block-read or a read-byte operation is to be
completed (set MSB to 1 to specify a block-read operation). A
maximum number of 32 bytes can be read.
1. The master asserts a start condition on SDA.
2. The master sends the 7-bit slave address followed by the
write bit (low).
3. The addressed slave device asserts ACK on SDA.
4. The master sends the register address (MSB = 1).
5. The slave asserts ACK on SDA.
6. The master asserts a repeated start on SDA.
7. The master sends the 7-bit slave address followed by the
read bit (high).
8. The slave asserts ACK on SDA.
9. The slave sends the byte count.
10. The master asserts ACK on SDA.
11. The slave sends N data bytes.
12. The master asserts ACK on SDA after each data byte.
13. The master does not acknowledge after the Nth data byte.
14. The master asserts a stop condition on SDA to end the
transaction.
S
ALERT RESPONSE
DEVICE
R A
A P
ADDRESS
ADDRESS
04937-0-043
SLAVE
R A
ADDRESS
C( x ) = x 8 + x 2 + x + 1
04937-0-024
S
The ADM1033 supports packet error checking (PEC). This
optional feature is triggered by the extra clock for the PEC byte.
The PEC byte is calculated using CRC-8. The frame check
sequence (FCS) conforms to CRC-8 by the following:
Figure 26. Alert Response Address
When multiple devices exist on the same bus, the alert response
address (ARA) feature allows an interrupting device to identify
itself to the host. The ALERT output can be used as an interrupt
output or as an SMBALERT. One or more ALERT outputs can
be connected to a common SMBALERT line, which is
connected to the master. If a device’s ALERT line goes low, the
following procedure occurs:
1. SMBALERT is pulled low.
2. The master initiates a receive-byte operation and sends the
alert response address (ARA 0001 100). This is a general call
address that must not be used as a specific device address.
3. The device with the low ALERT output responds to the
ARA, and the master reads its device address. Once the
address is known, it can be interrogated in the usual way.
4. If low ALERToutput is detected in more than one device,
the one with the lowest device address has priority, in
accordance with normal SMBus arbitration.
5. Once the ADM1033 has responded to the ARA, it resets its
ALERT output. If the error persists, the ALERT is reasserted on the next monitoring cycle.
Rev. 0 | Page 15 of 40
ADM1033
TEMPERATURE MEASUREMENT SYSTEM
Table 8. Local and Remote Sensor Extended Resolution
INTERNAL TEMPERATURE MEASUREMENT
The ADM1033 contains an on-chip band gap temperature
sensor. The on-chip ADC performs conversions on the sensor’s
output and outputs the temperature data in 13-bit format. The
resolution of the local temperature sensor is 0.03125°C.
Table 7 shows the format of the temperature data MSBs. Table 8
shows the local and remote sensor extended resolution data for
the LSBs. To ensure accurate readings, the LSBs should be read
first. This locks the current LSBs and MSBs until the MSBs are
read. They then start to update again. (Reading only the MSBs
does not lock the registers.) Temperature updates to the look-up
table take place in parallel, so fan speeds can be updated even if
the MSBs are locked.
Temperature (°C)
−64
−40
−32
−2
−1
0
1
2
10
20
50
75
100
125
150
191
Digital Output
0000 0000
0001 1000
0010 0000
0011 1110
0011 1111
0100 0000
0100 0001
0100 0010
0100 1010
0101 0100
0111 0010
1000 1011
1010 0100
1011 1101
1101 0110
1111 1111
Temperature Low Bits
00000
00001
00010
00100
01000
01100
10000
10100
11000
11100
Temperature (°C) = (MSB − 64°C) + (LSB × 0.03125)
Example: MSB = 0101 0100 = 84d
LSB = 11100 = 14
Temperature °C = (84 − 64) + (28 × 0.03125) = 20.875
REMOTE TEMPERATURE MEASUREMENT
The ADM1033 measures the temperature of one external diode
sensor or diode-connected transistor, which is connected to
Pins 9 and 10. These pins are dedicated temperature input
channels. The series resistance cancellation (SRC) feature can
automatically cancel out the effect of up to 1 kΩ of resistance in
series with the remote thermal diode.
The forward voltage of a diode or diode-connected transistor,
operated at a constant current, exhibits a negative temperature
coefficient of about −2 mV/°C. Unfortunately, the absolute
value of VBE varies from device to device, and individual
calibration is required to null this out. Therefore, the technique
is unsuitable for mass production.
ADM1033
D+
ADM1033
2N3904
D+
2N3906
D–
D–
Figure 27. Measuring Temperature Using Discrete Transistors
Rev. 0 | Page 16 of 40
04937-0-026
Table 7. Temperature Data Format for
Local and Remote Temperature High Bytes
Extended Resolution (°C)
0.0000
0.03125
0.0625
0.125
0.250
0.375
0.500
0.625
0.750
0.875
ADM1033
VDD
I
N2 × I
N1 × I
IBIAS
D+
VOUT+
TO ADC
D–
LOW-PASS FILTER
fC = 65kHz
VOUT–
04937-0-027
REMOTE
SENSING
TRANSISTOR
Figure 28. ADM1033 Signal Conditioning
The ADM1033 operates at three different currents to measure
the change in VBE.
Figure 28 shows the input signal conditioning used to measure
the output of an external temperature sensor. It also shows the
external sensor as a substrate transistor, provided for
temperature monitoring on some microprocessors. The external
sensor works equally well as a discrete transistor.
If a discrete transistor is used, the collector is not grounded and
should be linked to the base. If a PNP transistor is used, the base
is connected to the D− input and the emitter to the D+ input. If
an NPN transistor is used, the emitter is connected to the D−
input and the base to the D+ input.
If the sensor is used in a very noisy environment, a capacitor
value of up to 1000 pF can be placed between the D+ and D−
inputs to filter the noise. However, additional parasitic capacitance on the lines between D+, D−, and the thermal diode
should also be considered. The total capacitance should never
be greater than 1000 pF.
To measure each ΔVBE, the sensor is switched between operating currents of I, (N1 × I), and (N2 × I). The resulting waveform
is passed through a 65 kHz low-pass filter to remove noise, then
to a chopper-stabilized amplifier that amplifies and rectifies the
waveform. This produces a dc voltage proportional to ∆VBE.
These measurements are used to determine the temperature of
the thermal diode, while automatically compensating for any
series resistance on the D+ and/or D− lines. The temperature is
stored in two registers as a 13-bit word.
To further reduce the effects of noise, digital filtering is performed by averaging the results of 16 measurement cycles at
conversion rates of less than 16 Hz. An external temperature
measurement takes nominally 32 ms when averaging is enabled
and 6 ms when averaging is disabled.
One LSB of the ADC corresponds to 0.03125°C. The ADM1033
can theoretically measure temperatures from −64°C to
+191.96875°C, although −64°C and +191°C are outside its
operating range. The extended temperature resolution data
format is shown in Table 8. The extended temperature
resolution for the local and remote channels is stored in the
extended temperature resolution registers (Reg. 0x40 = Local,
Reg. 0x42 = Remote).
Table 9. Temperature Measurement Registers
Register
0x40
0x41
0x42
0x43
Description
Local Temperature, LSBs
Local Temperature, MSBs
Remote Temperature, LSBs
Remote Temperature, MSBs
Default
0x00
0x00
0x00
0x00
High and low temperature limit registers are associated with
each temperature measurement channel. The appropriate status
bit is set when the high and low limits are exceeded. Exceeding
either limit can cause an SMBALERT interrupt.
Table 10. Temperature Measurement Limit Registers
Register
0x0B
0x0C
0x0D
0x0E
0x0F
0x10
Rev. 0 | Page 17 of 40
Description
Local High Limit
Local Low Limit
Local THERM Limit
Remote High Limit
Remote Low Limit
Remote THERM Limit
Default
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
ADM1033
ADDITIONAL FUNCTIONS
Removing Temperature Errors
Several other temperature measurement functions available on
the ADM1033 offer the systems designer added flexibility.
As CPUs run faster and faster, it becomes more difficult to avoid
high frequency clocks when routing the D+ and D− traces
around a system board. Even when recommended layout
guidelines are followed, temperature errors attributed to noise
coupled onto the D+ and D− lines remain. High frequency
noise generally gives temperature measurements that are too
high by a constant amount. The ADM1033 has local and remote
temperature offset registers at Addresses 0x16 and 0x17—one
for each channel. By completing a one-time calibration, the user
can determine the offset caused by the system board noise and
remove it using the offset registers. The registers automatically
add a twos complement word to the remote temperature measurements, ensuring correct readings in the value registers.
Turn-Off Averaging
The ADM1033 performs averaging at conversion rates of less
than or equal to eight conversions per second. This means that
the value in the measurement register is the average of 16 measurements. For faster measurements, set the conversion rate to 16
conversions per second or greater. (Averaging is not carried out
at these conversion rates.) Or, to switch off averaging at the
slower conversion rates, set Bit 1 (AVG) of Configuration 1
Register (Address 0x01).
Single-Channel ADC Conversions
In normal operating mode, the ADM1033 converts on both the
local temperature and remote channels. However, the user can
set the ADM1033 to convert on one channel only. To enable
single-channel mode, set the round robin bit (Bit 7) in
Configuration Register 2 (Address 0x02) to 0. When the round
robin bit equals 1, the ADM1033 converts on both temperature
channels. In single-channel mode, it converts on one channel
only, to be determined by the state of the channel selector bit
(Bit 4) of Configuration Register 2 (Address 0x02).
Table 11. Channel Selector
Bit 4
0
1
Channel Selector (Configuration 2)
Local Channel (default)
Remote Channel
Table 12. Offset Registers
Registration
0x16
0x17
Description
Local Offset
Remote Offset
Table 13. Offset Register Values
Code
0 0000 000
0 0000 001
0 0000 111
0 0001 111
0 0111 111
0 1111 111
1 0000 000
1 1111 000
Rev. 0 | Page 18 of 40
Offset Value
0°C (Default)
0.125°C
0.875°C
1.875°C
7.875°C
15.875°C
−16°C
−0.875°C
Default
0x00
0x00
ADM1033
LAYOUT CONSIDERATIONS
Digital boards can be electrically noisy environments. Be sure to
protect the analog inputs from noise, particularly when
measuring the very small voltages from a remote diode sensor.
Take the following precautions:
•
Place the ADM1033 as close as possible to the remote
sensing diode. A distance of 4 inches to 8 inches is
adequate, provided that the worst noise sources such as
clock generators, data/address buses, and CRTs are avoided.
•
Route the D+ and D− tracks close together, in parallel, with
grounded guard tracks on each side. Provide a ground
plane under the tracks if possible.
•
Use wide tracks to minimize inductance and reduce noise
pickup. A minimum of 5 mil track width and spacing is
recommended.
•
Try to minimize the number of copper/solder joints, which
can cause thermocouple effects. Where copper/ solder
joints are used, make sure that they are in both the D+ and
D− path and at the same temperature. Thermocouple
effects should not be a major problem because 1°C
corresponds to about 200 µV, and thermocouple voltages
are about 3 µV/°C of temperature difference. Unless there
are two thermocouples with a big temperature differential
between them, thermocouple voltages should be much less
than 200 µV.
5MIL
GND
5MIL
5MIL
D+
5MIL
5MIL
5MIL
GND
04937-0-028
5MIL
D–
•
If the distance to the remote sensor is more than 8 inches,
twisted pair cable is recommended. This works up to about
6 feet to 12 feet.
•
For very long distances (up to 100 feet), use shielded
twisted pair such as Belden #8451 microphone cable.
Connect the twisted pair to D+ and D− and the shield to
GND, close to the ADM1033. Leave the remote end of the
shield unconnected to avoid ground loops.
Because the measurement technique uses switched current
sources, excessive cable and/or filter capacitance can affect the
measurement. When using long cables, the filter capacitor C1
may be reduced or removed. In any case, the total shunt
capacitance should never exceed 1000 pF.
Noise Filtering
For temperature sensors operating in noisy environments,
common practice is to place a capacitor across the D+ and D−
pins to help combat the effects of noise. However, large capacitances affect the accuracy of the temperature measurement, leading
to a recommended maximum capacitor value of 1000 pF. While
this capacitor reduces the noise, it does not eliminate it, making it
difficult to use the sensor in a very noisy environment.
The ADM1033 has a major advantage over other devices when
it comes to eliminating the effects of noise on the external sensor. The series resistance cancellation feature allows a filter to be
constructed between the external temperature sensor and the
part. The effect of any filter resistance seen in series with the remote
sensor is automatically cancelled from the temperature result.
The construction of a filter allows the ADM1033 and the
remote temperature sensor to operate in noisy environments.
Figure 30 shows a low-pass R-C-R filter with the following
values: R = 100 Ω and C = 1 nF. This filtering reduces both
common-mode noise and differential noise.
100Ω
•
REMOTE
TEMPERATURE
SENSOR
Place a 0.1 µF bypass capacitor close to the ADM1033.
1nF
100Ω
D–
04110-0-009
D+
Figure 29. Arrangement of Signal Tracks
Figure 30. Filter Between Remote Sensor and ADM1033
Rev. 0 | Page 19 of 40
ADM1033
LIMITS, STATUS REGISTERS, AND INTERRUPTS
High and low limits are associated with each measurement
channel on the ADM1033 and form the basis of system status
monitoring. The user can set a status bit for any out-of-limit
condition and detect it by polling the device. Alternatively,
SMBusALERTs can be generated to flag a processor or
microcontroller of an out-of-limit condition.
The ADC performs round-robin conversions and takes 11 ms
for the local temperature measurement and 32 ms for each
remote temperature measurement with averaging enabled.
The total monitoring cycle time for the average temperatures is,
therefore, nominally
32 + 11 = 43 ms
8-BIT LIMITS
Table 14 and Table 15 list all the 8-bit limits on the ADM1033:
Table 14. Temperature Limit Registers
Register
0x0B
0x0C
0x0D
0x0E
0x0F
0x10
Description
Local High Limit
Local Low Limit
Local THERM Limit
Remote High Limit
Remote Low Limit
Remote THERM Limit
Default
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
0x8B (75°C)
0x54 (20°C)
0x95 (85°C)
Once the conversion time elapses, the round robin starts again.
For more information, refer to the Conversion Rate Register
section.
Fan TACH measurements take place in parallel and are not
synchronized with the temperature measurements.
STATUS REGISTERS
The results of limit comparisons are stored in the status
registers. A 1 represents an out-of-limit measurement; a 0
represents an in-limit measurement. The status registers are
located at Addresses 0x4F to 0x51.
Table 15. THERM Limit Register
Register
0x19
Description
THERM % Limit
If the measurement is outside its limits, the corresponding
status register bit is set to 1. It remains set at 1 until the
measurement falls back within its limits and either the status
register is read or an ARA is completed.
Default
0xFF
OUT-OF-LIMIT COMPARISONS
The ADM1033 measures all parameters in a round-robin
format and sets the appropriate status bit for out-of limit
conditions. Comparisons are made differently, depending on
whether the measured value is compared to a high or low limit.
To poll the state of the various measurements, read the status
registers over the serial bus. If Bit 0 (ALERT low) of Status
Register 3 (Address 0x51) is set, this means the ADM1033 has
pulled the ALERT output low.
Pin 14 is an SMBusALERT output. This pin automatically
notifies the system supervisor of an out-of-limit condition.
Reading the status register clears the status bit, as long as the
error condition has been cleared.
High Limit: ≥ Comparison Performed
Low Limit: < Comparison Performed
ANALOG MONITORING CYCLE TIME
The analog monitoring cycle time begins on power-up or, if
monitoring has been disabled, by writing a 1 to the monitor/
STBY bit of Configuration Register 1 (Address 0x01). The
ADC measures each one of the analog inputs in turn; as each
measurement is completed, the result is automatically stored in
the appropriate value register. The round-robin monitoring
cycle continues, unless it is disabled. To disable the cycle, write
a 0 to the monitor/STBY bit (Bit 0) of Configuration Register 1
(Address 0x01).
Pin 3 is an ALERT Comp output. This pin asserts low when
ever an unmasked measurement goes outside its limit. Unlike
SMBusALERT, it automatically resets once the measurement
falls back within the programmed limits.
Status register bits are sticky. Whenever a status bit is set due to
an out-of-limit condition, it remains set—even after the triggering event has cleared. The only way to clear the status bit is to
read the status register (after the triggering event has cleared).
Interrupt mask registers (Reg. 0x08, Reg. 0x09, Reg. 0x0A) allow
individual interrupt sources to be masked from causing an
ALERT. If one of these masked interrupt sources goes out of
limit, its associated status bit is set in the status register.
Rev. 0 | Page 20 of 40
ADM1033
Table 16. Status Register 1 (Reg. 0x4F)
ALERT INTERRUPT BEHAVIOR
Bit No.
7
Name
LH
6
LL
The ADM1033 generates an ALERT to signal out-of-limit
conditions. Out-of-limit conditions can also be detected by
polling the status registers. The ADM1033 has two ALERT
outputs, called ALERT Comp and SMBusALERT.
5
RH
4
RL
3
RD
2
1
0
Unused
Unused
Unused
Table 17. Status Register 2 (Reg. 0x50)
Bit No.
7
Name
LT
6
RT
5
4
Unused
T%
3
TA
2
TS
1
0
Res
Res
Description
1 = Local THERM temperature limit has
been exceeded.
1 = Remote THERM temperature limit has
been exceeded.
Reserved.
1 = THERM timer limit has been
exceeded.
1 = One of the THERM limits has been
exceeded; and the THERM output signal
has been asserted.
1 = THERM pin is active. Clears on a read,
if THERM is not active.
Reserved.
Reserved.
Table 18. Status Register 3 (Reg. 0x51)
Bit No.
7
6
Name
FS
FA
5
4
3
2
1
0
Res
Res
Res
Res
Res
ALERT
Description
1= Fan has stalled.
1= Fan ALARM speed, indicates fan is
running at alarm speed.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
1= SMBusALERT low, indicates the
ADM1033 has pulled the SMBusALERT
line low.
In SMBusALERT mode, the output remains low until the
following combination of conditions occur: the measurement
falls back within its programmed limits, and either the status
register is read or an ARA is completed.
In ALERT Comp mode, the output automatically resets
once the temperature measurement falls back within the
programmed limits.
For the SMBusALERT output, a status bit is set when a
measurement goes outside its programmed limit. If the
corresponding mask bit is not set, the SMBusALERT output
is pulled low. If the measured value falls back within the limits,
the SMBusALERT output remains low until the corresponding
status register is read or until an ARA is completed, as long as
no other measurement is outside its limits.
On the other hand, the ALERT Comp output is automatically
pulled low when a measurement goes outside its programmed
limits. Once the measurement falls back within its limits, the
ALERT output is automatically pulled back high again,
assuming no other measurement channel is outside its limits.
The main difference between the two outputs is that the
SMBusALERT does not reset without software intervention,
while the ALERT Comp output automatically resets itself. Note:
In this data sheet, an ALERT refers to both the ALERT Comp
and SMBusALERT, unless otherwise stated.
TEMPERATURE
LIMITS
ALERT, 70°C
TIME
SMBusALERT
ALERT COMP
CLEARED
ON READ
Figure 31. How ALERT Comparator and SMBusALERT Outputs Work
Rev. 0 | Page 21 of 40
04937-0-029
Description
1 = Local high temperature limit has been
exceeded.
1 = Local low temperature limit has been
exceeded.
1= Remote high temperature limit has
been exceeded.
1 = Remote low temperature limit has
been exceeded.
1 = Remote diode error; indicates an
open or short on the D1+/D1− pins.
Reserved.
Reserved.
Reserved.
ADM1033
HANDLING SMBUSALERT INTERRUPTS
Table 19. Mask Register 1 (Reg. 0x08)
To prevent tie-ups due to service interrupts, follow these steps:
Bit No.
7
Name
LH
2. Enter the interrupt handler.
6
LL
3. Read the status register to identify the interrupt source.
5
RH
4. Mask the interrupt source by setting the appropriate mask
bit in the interrupt mask registers (Reg. 0x08 to Reg. 0x0A).
4
RL
3
RD
2
1
0
Res
Res
Res
1. Detect an SMBus assertion.
5. Take the appropriate action for a given interrupt source.
6. Exit the interrupt handler.
7. Periodically poll the status register. If the interrupt status bit
has cleared, reset the corresponding interrupt mask bit to 0.
This causes the SMBusALERT output and status bits to
behave as shown in Figure 32.
HIGH LIMIT
TEMPERATURE
CLEARED ON READ
(TEMP BELOW LIMIT)
SMBusALERT
Table 20. Mask Register 2 (Reg. 0x09)
Bit No.
7
6
5
4
Name
Res
Res
Res
T%
3
TA
2
TS
1
0
Res
Res
TEMP BACK IN LIMIT
(STATUS BIT STAYS SET)
INTERRUPT
MASK BIT SET
INTERRUPT MASK BIT
CLEARED
(SMBusALERT REARMED)
Figure 32. Handling SMBusALERTs
04937-0-030
"STICKY"
STATUS BIT
Description
1 masks the ALERT for the local high
temperature.
1 masks the ALERT for the local low
temperature.
1 masks the ALERT for the remote high
temperature.
1 masks the ALERT for the remote low
temperature.
1 masks the ALERT for the remote diode
errors.
Reserved.
Reserved.
Reserved.
Description
Reserved.
Reserved.
Reserved.
1 masks the ALERT for the THERM timer
limit.
1 masks the ALERT for the THERM limit
being exceeded and the THERM output
signal being asserted.
1 masks the ALERT for a transition on
THERM; has no effect on ALERT in ALERT
Comp mode.
Reserved.
Reserved.
Table 21. Mask Register 3 (Reg. 0x0A)
INTERRUPT MASKING REGISTER
Mask Registers 1, 2, and 3 are located at Addresses 0x08, 0x09,
and 0x0A. These registers allow individual interrupt sources to
be masked out to prevent the ALERT interrupts. Note that
masking the interrupt source prevents only the ALERT from
being asserted; the appropriate status bit is set as normal.
Bit No.
7
6
Name
FS
FA
5
4
3
2
1
0
Res
Res
Res
Res
Res
Res
Rev. 0 | Page 22 of 40
Description
1 masks the ALERT for fan stalling.
1 masks the ALERT for fan running at
ALARM speed.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
ADM1033
FAN_FAULT OUTPUT
CONVERSION RATE REGISTER
The FAN_FAULT output signals when the fan stalls. Pin 8, a
dual-function pin, defaults to a FAN_FAULT output. It can also
be reconfigured as an analog input reference for the THERM
input. To configure the pin, set the FAN_FAULT/REF bit (Bit 7)
in Configuration Register 4 (Address 0x04) to 1.
The ADM1033 makes up to 64 measurements per second.
However, for the sake of reduced power consumption and better
noise immunity, users can run the ADM1033 at a slower
conversion rate. Averaging does not occur at rates of 16, 32, and
64 conversions per second. Table 23 lists the available rates. The
conversion rate register is located at Address 0x05. Note that the
current round-robin loop must be completed before the newly
programmed conversion rate can take effect.
FAULT QUEUE
The ADM1033 has a programmable fault queue option that lets
the user program the number of out-of-limit measurements
allowable before generating an SMBusALERT. The fault queue
affects only temperature measurement channels and is operational only in SMBusALERT mode. It performs some simple
filtering, which is particularly useful at the higher conversion
rates (16, 32, and 64 conversions per second), where averaging is
not carried out.
There is a queue for each of the temperature channels. If L (the
value programmed to the fault queue) or more consecutive outof-limit measurements are made on the same temperature
channel, the fault queue fills and the SMBusALERT output
triggers. To fill the fault queue, the user needs L or more
consecutive out-of-limit measurements on the local, or L or
more consecutive out-of-limit measurements on the remote
channel. The fault queue is independent of the state of the bits
in the status register.
Table 22. Fault Queue (Address 0x06)
Bits <3:0>
000x
001x
01xx
1xxx
SMBus ARA command
•
Read Status Register 1
•
Power-on reset
Code
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x07
0x08
0x09
0x0A
0x0B to 0xFF
Conversion Rate
0.0625
0.125
0.25
0.5
1
2
4
8
16
32
64
Reserved
THERM I/O TIMER AND LIMITS
Pin 7 can be configured as either an input or output. As an
output, it is asserted low to signal that the measured temperature has exceeded preprogrammed temperature limits. The
output is automatically pulled high again when the temperature
falls below the (THERM − Hysteresis) limit. The value of hysteresis is programmable in Register 0x1A. THERM is enabled as
an output by default on power-up.
Fault Queue
1
2
3
4
To reset the fault queue, do one of the following:
•
Table 23. Conversion Rates
TEMPERATURE
LIMITS
THERM, 85°C
THERM-HYST,
80°C
TIME
THERM
Figure 33. THERM Behavior
Rev. 0 | Page 23 of 40
04937-0-031
The SMBusALERT clears, even if the condition that caused the
SMBusALERT remains. The SMBusALERT is reasserted, if the
fault queue fills up.
ADM1033
Once the THERM limits are exceeded, the fans are boosted to
full speed—that is, as long as the boost disable bit (Bit 1) is not
set in Configuration Register 2 (Address 0x02).
When THERM is configured as an input only, set the enable
THERM events bits in Configuration Register 4 (Address 0x04)
to allow Pin 7 to operate as an I/O.
To configure THERM as an input, set the THERM timer bit
(Bit 2) of Configuration Register 1 (Address 0x01) to 1. (It no
longer operates as an output.) The ADM1033 can then detect
whenever the THERM input is asserted low. This can be connected to a trip point temperature sensor or to the PROCHOT
output of a CPU. With processor core voltages reducing all the
time, the threshold for the ADTL + PROCHOT output also
reduces as new processors become available. The default threshold on THERM is the normal CMOS threshold. However, Pin 8
(FAN_FAULT/REF) can be reconfigured as a REF input. This
is done by setting Bit 7 (FAN_FAULT/REF) in Configuration
Register 4 (Address 0x04) to 1. The processor VCCP should be
connected to this input to provide a reference for the THERM
input. The resulting THERM threshold is 0.75 × VCCP, the
correct threshold for an AGTL+ signal.
To configure the THERM pin to be pulled low as an output
whenever the local temperature exceeds the local THERM limit,
set the enable local THERM events bit (Bit 0) of Configuration
Register 4 (Address 0x04).
To configure the THERM pin to be pulled low as an output
whenever the remote temperature exceeds the remote THERM
limit, set the enable remote THERM events bit (Bit 1) of
Configuration Register 4 (Address 0x04).
THERM % LIMIT REGISTER
The THERM % limit is programmed to Register 0x19. An
ALERT is generated if the THERM is asserted for longer than
the programmed percentage limit. The limit is programmed as a
percentage of the chosen time window.
0x00 = 0%
The ADM1033 can also measure assertion times on the
THERM input as a percentage of an on-time window. This
window is programmable in Configuration Register 4
(Address 0x04) using Bits <6:4> (THERM % on-time window).
Values of between 0.25 and 8 are programmable. The assertion
time, as a percentage of the time window, is stored in the
THERM % on-time register (Address 0x4E).
A THERM % (0x19) limit is also associated with this register.
Once the measured percentage exceeds the percentage limit,
the THERM % exceeded bit (Bit 4) in Status Register 2
(Address 0x50) is asserted and an ALERT is generated, as long
as the mask bit is not set. If the limit is set to 0x00, an ALERT
is generated on the first assertion. If the limit is set to 0xFF, an
ALERT is never generated. This is because 0xFF corresponds to
the THERM input, which is asserted all the time.
0xFF = 100%
Therefore, 1 LSB = 0.39%
Example
If a time window of 8 seconds is chosen, and an ALERT is to be
generated if THERM is asserted for more than 1 second,
program the following value to the limit register:
% Limit = 1/8 × 100 = 12.5%
12.5% / 0.39% = 32d = 0x20 = 0010 0000
An ALERT is generated if the THERM limit is exceeded after
the time window has elapsed, assuming it is not masked.
Table 24. THERM % On-Time Window
Code
THERM % On-Time Window
000
001
010
011
100
101
110
111
0.25 s
0.5 s
1s
2
4s
8s
8s
8s
Rev. 0 | Page 24 of 40
ADM1033
FAN DRIVE SIGNAL
The ADM1033 controls the speed of a cooling fan. Varying the
duty cycle (on/off time) of a square wave applied to the fan
varies the speed of the fan. The ADM1033 uses a control
method called synchronous speed control, in which the PWM
drive signal applied to the fan is synchronized with the fan’s
TACH signal. See the Synchronous Speed Control section.
The external circuitry required to drive the fan is simple. A
single N-channel MOSFET is the only drive device required.
The specifications of the MOSFET depend on the maximum
current required by the fan and the gate voltage drive (VGS < 3 V
for direct interfacing to the drive pin). VGS can be greater than
3 V, as long as the pull-up on the gate is tied to 5 V. The MOSFET
should also have a low on resistance to ensure that there is no
significant voltage drop across the FET. A high on resistance
reduces the voltage applied across the fan and, therefore, the
maximum operating speed of the fan. Figure 34 shows a scheme
for driving a 3-wire fan.
12V
10kΩ
10kΩ
TACH
4.7kΩ
ADM1033
TACH
12V
12V
FAN
If in doubt as to whether a fan has an open collector or totempole TACH output, use one of the input signal conditioning
circuits shown in the Fan Inputs section.
When designing drive circuits with transistors and FETs, make
sure that the drive pins are not required to source current and
that they sink less than the maximum current specified.
SYNCHRONOUS SPEED CONTROL
The ADM1033 drives the fan using a control scheme called
synchronous speed control. In this scheme, the PWM drive
signal applied to the fan is synchronized with the TACH signal.
Accurate and repeatable fan speed measurements are the main
benefits. The fan is allowed to run reliably at speeds as low as
30 % of the full capability.
The drive signal applied to the fan is synchronized with the
TACH signal. The ADM1033 switches on the drive signal and
waits for a transition on the TACH signal. When a transition
takes place on the TACH signal, the PWM drive is switched off
for a period of time called tOFF. The drive signal is then switched
on again. The tOFF time is varied in order to vary the fan speed.
If the fan runs too fast, the tOFF time is increased. If the fan runs
too slow, the tOFF time is decreased.
1N4148
3.3V
Q1
NDT3055L
DRIVE
Because the drive signal is synchronized with the TACH signal,
the frequency with which the fan is driven depends on the current speed of the fan and the number of poles in it.
04937-0-032
100kΩ
Figure 34. Interfacing a 3-Wire Fan to the ADM1033 Using an
N-Channel MOSFET
Figure 34 uses a 10 kΩ pull-up resistor for the TACH signal.
This assumes that the TACH signal is an open collector from
the fan. In all cases, the fan’s TACH signal must be kept below 5
V maximum to prevent damaging the ADM1033.
Figure 35 shows how the synchronous speed drive signal works.
The ideal TACH signal is the signal that would be output from
the fan, if power were applied 100% of the time. It is representative of the actual speed of the fan. The actual TACH signal is the
signal seen on the TACH output from the fan, if using a scope.
In effect, the actual TACH signal is the ideal TACH signal
chopped with the drive signal.
POLE TRANSITION POINTS
IDEAL TACH
tPOLE
DRIVE
tOFF
DASH = TACH FLOATS HIGH BY PULL-UP RESISTOR
SOLID = TRUE TACH WHEN FAN IS POWERED
Figure 35. Drive Signal by Using Synchronous Control
Rev. 0 | Page 25 of 40
04937-0-033
ACTUAL TACH
ADM1033
Pin 2 is the TACH input intended for fan speed measurement.
This input is open-drain.
Signal conditioning on the ADM1033 accommodates the slow
rise and fall time of typical tachometer outputs. The maximum
input signal range is from 0 V to 5 V, even when VCC is less than
5 V. If these inputs are supplied from fan outputs that exceed
0 V to 5 V, either resistive attenuation of the fan signal or diode
clamping must be used to keep the fan inputs within an
acceptable range.
The fan inputs have an input resistance of about 160 kΩ to
ground. Consider this when calculating resistor values.
With a pull-up voltage of 12 V and pull-up resistor of less than
1 kΩ, suitable values for R1 and R2 would be 100 kΩ and 47 kΩ.
This gives a high input voltage of 3.83 V.
12V
VCC
R1*
TACH
OUTPUT
Figure 36 to Figure 38 show examples of possible fan input
circuits.
FAN SPEED MEASUREMENT
FAN SPEED
COUNTER
ZD1*
100kΩ
TYP
DRIVE X
04937-0-035
VCC
TACH X
*CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × VCC
Figure 36. Fan with TACH Pull-Up to Voltage > 5 V, Clamped with Zener Diode
If the fan output has a resistive pull-up to 12 V (or another
voltage greater than 5 V), the fan output can be clamped with a
Zener diode, as shown in Figure 36. Select a Zener voltage that
is greater than VIH but less than 5 V, allowing for the voltage
tolerance of the Zener. A value of between 3 V and 5 V is
suitable.
12V
VCC
PULL-UP TYP
<1 kΩ OR
TOTEM POLE
R1
10kΩ
ADM1033
FAN(0–7)
ZD1
ZENER*
FAN SPEED
COUNTER
* CHOOSE ZD1 VOLTAGE APPROXIMATELY 0.8 × VCC
The fan counter does not count the fan TACH output pulses
directly. This is because the fan may be spinning at less than
1,000 rpm and it would take several seconds to accumulate a
large and accurate count. Instead, the period of the fan
revolution is measured by gating an on-chip 81.92 kHz
oscillator into the input of a 16-bit counter for one complete
revolution of the fan. Therefore, the accumulated count value is
actually proportional to the fan tachometer period and inversely
proportional to the fan speed.
The number of poles in the fan must be programmed in
Configuration Register 3 (Address 0x03). This number must be
an even number only, because there cannot be an uneven
number of poles in a fan. A TACH period is output for every
two poles. Therefore, the number of poles must be known so
that the ADM1033 can measure for a full revolution.
Figure 39 shows the fan speed measurement period, assuming
that the fan outputs an ideal TACH signal. In reality, the TACH
signal output by the fan is chopped by the drive signal. However,
because the drive signal and TACH signal are synchronized,
there is enough information available for the ADM1033 to
measure the fan speed accurately.
04937-0-036
TACH
OUTPUT
R2
Figure 38. Fan with Strong TACH Pull-Up to Voltage > VCC to Totem Pole
Output, Attenuated with R1/R2
ADM1033
TACH
OUTPUT
FAN SPEED
COUNTER
*SEE TEXT
VCC
PULL-UP
4.7kΩ
TYP
FAN(0–7)
Figure 37. Fan with Strong TACH Pull-Up to Voltage > VCC or Totem Pole
Output, Clamped with Zener and Resistor
If the fan has a strong pull-up (less than 1 kΩ to 12 V) or a
totem-pole output, then a series resistor can be added to limit
the Zener current, as shown in Figure 37.
CLOCK
IDEAL
TACH
Or, resistive attenuation can be used, as shown in Figure 38.
FAN
MEASUREMENT
PERIOD
Figure 39. Fan Speed Measurement for a 4-Pole Fan
R1 and R2 should be chosen such that
2 V < VPULL-UP × R2/(RPULL-UP + R1 + R2) < 5 V
Rev. 0 | Page 26 of 40
04937-0-038
5V OR 12V
FAN
ADM1033
<1 kΩ
04937-0-037
FAN INPUTS
ADM1033
FAN SPEED MEASUREMENT REGISTERS
ALARM SPEED
The16-bit measurements listed in Table 25 are stored in the
TACH value registers.
The fan ALARM speed (Bit 6) in Status Register 3 (Address 0x51)
is set whenever the fan runs at alarm speed. This occurs if the
device is programmed to run the fan at full speed whenever the
THERM temperature limits are exceeded. The device runs at
alarm speed, for example, if the Boost Disable bit (Bit 1) of the
Configuration 2 Register (Address 0x02) is not set to 1.
Table 25. TACH Value Registers
Register
0x4A
0x4B
Description
TACH Period, LSB
TACH Period, MSB
Default
0xFF
0xFF
Fan Response Register
READING FAN SPEED
Reading back the fan speed involves a 2-register read for each
measurement. The low byte should be read first. This freezes the
high byte until both high and low byte registers have been read,
preventing erroneous fan speed measurement readings.
The fan tachometer reading registers report back the number of
12.20 µs period clocks (81.92 kHz oscillator) gated to the fan
speed counter for one full rotation of the fan (assuming the
correct number of poles is programmed). Because the
ADM1033 essentially measures the fan TACH period, the
higher the count value, the slower the fan’s actual speed. A 16bit fan TACH reading of 0xFFFF indicates that the fan has
stalled or is running very slowly (<75 rpm).
CALCULATING FAN SPEED
Fan speed in rpm is calculated as follows. This calculation
assumes the number of poles programmed in Configuration
Register 3 (Address 0x03) is correct for the fan used.
Fan Speed (rpm) = (81920 × 60)/Fan TACH Reading
The ADM1033 fan speed controller operates by reading the
current fan speed, comparing it with the programmed fan
speed, and then updating the drive signal applied to the fan. The
fan response register determines the rate at which the
ADM1033 looks at and updates the drive signal. Different fans
have different inertias and respond to a changing drive signal
more or less quickly than others. The fan’s response register
allows the user to tailor the ADM1033 to a particular fan, to
prevent situations like overshoot.
The user selects the number of updates to the drive signal per
second. Table 26 lists the available options.
Table 26. Fan Response Codes
Code
000
001
010
011
100
101
110
111
Update Rate
1.25 updates/s
2.5 updates/s = default
5 updates/s
10 updates/s
20 updates/s
40 updates/s
80 updates/s
160 updates/s
where the Fan TACH Reading is the 16-bit Fan Tachometer
Reading.
Example:
TACH High Byte (Reg. 0×28) = 0×7
Table 27. Fan Response Register (Address 0x3C)
Bit
<7:3>
<2:0>
TACH Low Byte (Reg. 0×29) = 0×FF
What is the fan speed in rpm?
Fan TACH Reading = 0×17FF = 6143d
rpm = (f × 60)/Fan TACH Reading
rpm = (81920 × 60)/6143
Fan Speed = 800 rpm
Rev. 0 | Page 27 of 40
Function
Unused
Fan Response
ADM1033
LOOK-UP TABLE: MODES OF OPERATION
LOOK-UP TABLE
The ADM1033 look-up table has two modes of operation used
to determine the behavior of the system:
The ADM1033 allows the user to program a temperature-tofan-speed profile. There are 24 registers in the look-up table,
eight for temperature and 16 for target fan speed (each target
fan speed is two registers). In total, there are eight available
points.
•
Manual mode
•
Look-up table
Manual Mode
In manual mode, the ADM1033 is under software control. The
software programs the required fan speed value or target rpm
value. The ADM1033 then outputs that fan speed.
Programming Target Fan Speed
In this mode, the user programs the target rpm as a TACH
count for N poles or a TACH count for one full rotation of the
fan. This assumes that the number of poles is programmed
correctly in Configuration 3 Register (Address 0x03).
Follow these steps to program the target fan speed:
There are two options when programming the look-up table. It
can be programmed to make the fan run at discrete speeds and
jump to the new speed once the temperature threshold is
crossed. Or, it can linearly ramp the TACH count between the
two temperature thresholds.
Figure 40 and Figure 41 show what the look-up table looks like,
if all eight points are used on the one curve for both fans.
Figure 40 shows the transfer curve when the fan is programmed
to run at discrete speeds. The ADM1033 spins the fan at its new
speed once a threshold is crossed.
FAN SPEED
1.
2.
Place the ADM1033 in manual mode. Set Bit 7 (Table/SW)
of Configuration Register 1 (Address 0x01) = 0.
TACH COUNT 8
TACH COUNT 7
Program the target TACH count (fan speed) using the
following equation:
TACH COUNT 6
TACH COUNT 5
TACH COUNT 4
TACH COUNT 3
TACH Count = (f × 60)/R
TACH COUNT 2
where:
f = clock frequency = 81.92 kHz
T1
T2
T3
T4
T5
T6
T7
R = required rpm value
T8
TEMPERATURE
04937-0-039
TACH COUNT 1
Figure 40. Programming the Look-Up Table in Discrete RPM Mode
Example 1: If the desired value is 5,000 rpm, program the
following value to the TACH pulse period registers:
Figure 41 shows the transfer curve if the linear fan speeds
option is chosen. At temperature T1, the fan runs at Fan Speed 1.
As the temperature increases, the fan speed increases until it
reaches Fan Speed 2 at T2.
TACH Pulse Period = (f × 60)/5000
TACH Pulse Period = 983d = 0x03D7
FAN SPEED
Example 2: If the desired value is 3,500 rpm, program the
following value to the TACH pulse period registers:
TACH COUNT 8
TACH COUNT 7
TACH COUNT 6
TACH COUNT 5
TACH COUNT 4
TACH Pulse Period = (f × 60)/3500
TACH Pulse Period = 1404d = 0x057C
TACH COUNT 3
Table 28. Registers to be Programmed
Description
Look-Up Table LSB
Look-Up Table MSB
Look-Up Table LSB
Look-Up Table MSB
TACH COUNT 2
Address
0x2A
0x2B
0x2C
0x2D
Value
0xD7
0x03
0x7C
0x05
TACH COUNT 1
T1
T2
T3
T4
T5
T6
T7
T8
TEMPERATURE
Figure 41. Programming the Look-Up Table in Linear Fan Speeds Mode
Rev. 0 | Page 28 of 40
04937-0-040
Fan
Example 1
Example 1
Example 2
Example 2
ADM1033
FAN SPEED
SETTING UP THE LOOK-UP TABLE
IN LINEAR MODE
TACH COUNT 2 TO 8
When discrete/linear speed (Bit 2) is set to 1 (default), the
TACH count decreases linearly and the fan speed increases with
temperature. At temperature TX, the fan runs at FSX and speed
increases with temperature to FSX+1 at temperature TX+1.
T1
T2
T (3 TO 8) = 191 °C
TEMPERATURE
04918-0-041
TACH COUNT 1
Figure 42. Programming Two Points on the Look-Up Table
Alternatively, the fan can be run at discrete fan speeds. When
discrete/linear speed (Bit 2) is set to 0, the fan runs at a new
speed once the temperature threshold is exceeded.
SELECTING WHICH TEMPERATURE CHANNEL
CONTROLS A FAN
Once the temperature exceeds the highest temperature point in
the look-up table, the fan speed remains at the highest speed
until the temperature drops below the T7 temperature value.
Fan Behavior Register (Address 0x07)
If the temperatures in T1 to T8 are not programmed in
succession, the fan speed moves to the next highest programmed temperature as the temperature increases. Similarly,
when the temperature decreases, it ignores programmed higher
temperatures and jumps to the next lower temperature. Therefore, the temperature-to-fan-speed profile for increasing and
decreasing temperature can be different.
The ADM1033 can be configured so that either the local
temperature or the remote temperature controls the fan.
In default, the remote temperature controls the fan.
When programming the look-up table, the user has the option
to use between two and eight points for the fan (eight points
only if the same curve is to be used for both fans).
If the user wants to program only the transfer curve and knows
the starting temperature, minimum fan speed, maximum
temperature, and maximum fan speed, then only four parameters are required: T1, T2, FS1, and FS2. The remaining look-up
temperature thresholds should remain at their default values of
+191°C. FS 3 to FS8 should be programmed with the same value
as FS2 to give the flat curve, if required, or, they can be left at
the default value of 0.
However, it is normal to program a THERM limit as well. Once
this temperature is exceeded and the boost bit is set, the fan
runs to full speed. This overrides the table.
Table 29. Look-Up Table Register Addresses
x
1
2
3
4
5
6
7
8
Temperature, x
0x22
0x23
0x24
0x25
0x26
0x27
0x28
0x29
RPMx, LSB
0x2A
0x2C
0x2E
0x30
0x32
0x34
0x36
0x38
RPMx, MSB
0x2B
0x2D
0x2F
0x31
0x33
0x35
0x37
0x39
Bits <1:0> = DRIVE Behavior
Table 30. Drive BHVR Bits
Bits
00
01
10
11
Drive x BHVR
Local Temperature Controls the Fan
Remote Temperature Controls the Fan
Remote Temperature Controls the Fan
Fan Runs at Full Speed
LOOK-UP TABLE HYSTERESIS
The user can program a hysteresis to be applied to the look-up
table. The advantage of this is apparent, if the temperature is
cycling around one of the threshold temperatures, particularly
when the look-up table is configured in discrete mode. It is not
as important in linear mode.
Table 31. Programming the Hysteresis
Code
0000 0000
0000 0001
0000 0010
0000 0101
0000 1000
0000 1111
Hysteresis Value
0°C
1°C
2°C
5°C
8°C
15°C
The hysteresis register of the look-up table is at Address 0x3A.
A hysteresis value of between 0°C and 15°C can be
programmed with a resolution of 1°C and applied to all the
temperature thresholds. Table 31 gives sample values for
programming.
Rev. 0 | Page 29 of 40
ADM1033
XOR TREE TEST MODE
THERM is the absolute maximum temperature allowed on a
temperature channel. Above this temperature, a component
such as the CPU or VRM might operate beyond its safe
operating limit. When the temperature exceeds THERM, all fans
are driven at full speed to provide critical system cooling. The
fans remain running at 100% until the temperature drops below
THERM − Hysteresis. The hysteresis value can be programmed; its default is 5°C. If the boost disable bit (Bit 1) is set
in Configuration Register 2, the fans do not run to full speed.
The ADM1033 includes an XOR tree test mode. This mode
is useful for in-circuit test equipment at board-level testing.
By applying stimulus to the pins included in the XOR test, it
is possible to detect opens or shorts on the system board.
Figure 43 shows the signals exercised in this mode.
TACH1
ALERT_COMP
THERM
The THERM limit is considered the maximum worst-case
operating temperature of the system. Exceeding any THERM
limit runs all fans at full speed, a condition with very negative
acoustic effects. This limit should be set up as a fail-safe and not
exceeded under normal system operating conditions. The
THERM temperature limit registers are listed in Table 32.
FAN_FAULT/REF
LOCATION
ALERT
Figure 43. XOR Tree Test
Table 32. THERM Hysteresis Registers
Address
0x0D
0x10
Description
Local THERM Limit
Remote THERM Limit
Default
0x95 (85°C)
0x95 (85°C)
The THERM hysteresis register is at Address 0x1A. A value is
programmed and applied to both temperature channels—local
and remote. A THERM hysteresis value of between 0°C and
15°C can be programmed with a resolution of 1°C. See Table 33.
Table 33. Programming THERM Hysteresis
Code
0000 0000
0000 0001
0000 0010
0000 0101
0000 1000
0000 1111
Hysteresis Value
0°C
1°C
2°C
5°C
8°C
15°C
DRIVE1
04937-0-042
PROGRAMMING THE THERM LIMIT FOR
TEMPERATURE CHANNELS
LOCK BIT
Setting the lock bit (Bit 6) of Configuration Register 1 (Address
0x01) makes all the lockable registers read-only. These registers
remain read only until the ADM1033 is powered down and
back up again. For more information on which registers are
lockable, see Table 33.
SW RESET
Setting the software reset bit (Bit 0) of Configuration Register 1
(Address 0x01) resets all software-resettable bits to their default
value. For more information on resetting registers and their
default values, see Table 34 to Table 68.
Rev. 0 | Page 30 of 40
ADM1033
Table 34. ADM1033 Registers
Address
0x00/80
0x01/81
0x02/82
0x03/83
0x04/84
0x05/85
0x06/86
0x07/87
0x08/88
0x09/89
0x0A/8A
0x0B/8B
0x0C/8C
0x0D/8D
0x0E/8E
0x0F/8F
0x10/90
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0x16/96
0x17/97
0x19/99
0x1A/9A
0x22/A2
0x23/A3
0x24/A4
0x25/A5
0x26/A6
0x27/A7
0x28/A8
0x29/A9
0x2A/AA
0x2B/AB
0x2C/AC
0x2D/AD
0x2E/AE
0x2F/AF
0x30/B0
0x31/B1
0x32/B2
0x33/B3
0x34/B4
0x35/B5
0x36/B6
0x37/B7
0x38/B8
0x39/B9
0x3A/BA
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0x3C/BC
0x3D\BD
0x3E\BE
R/W
R
R
Description
#Bytes/Block Read
Configuration 1
Configuration 2
Configuration 3
Configuration 4
Conversion Rate
Fault Queue
Fan Behavior
Mask 1
Mask 2
Mask 3
Local High Limit
Local Low Limit
Local THERM Limit
Remote High Limit
Remote Low Limit
Remote THERM
Limit
Local Offset
Remote Offset
THERM % Limit
THERM Hysteresis
Look-Up Table T1
Look-Up Table T2
Look-Up Table T3
Look-Up Table T4
Look-Up Table T5
Look-Up Table T6
Look-Up Table T7
Look-Up Table T8
Look-Up Table, FS1
Look-Up Table, FS1
Look-Up Table, FS2
Look-Up Table, FS2
Look-Up Table, FS3
Look-Up Table, FS3
Look-Up Table, FS4
Look-Up Table, FS4
Look-Up Table, FS5
Look-Up Table, FS5
Look-Up Table, FS6
Look-Up Table, FS6
Look-Up Table, FS7
Look-Up Table, FS7
Look-Up Table, FS8
Look-Up Table, FS8
Look-Up Table
Hysteresis
Fan Response
Device ID
Company ID
Bit 7
7
Table/SW
RR
RES
FF/REF
RES
RES
RES
LH
RES
FS
7
7
7
7
7
7
Bit 6
6
Lock
RES
RES
%T
RES
F1 Off
RES
LL
RES
FA
6
6
6
6
6
6
Bit 5
5
SDA
RES
RES
%T
RES
RES
RES
RH
RES
RES
5
5
5
5
5
5
Bit 4
4
SCL
CS
RES
%T
RES
RES
RES
RL
%T
RES
4
4
4
4
4
4
Bit 3
3
ALERT
LUT
#FP
XOR
Conv
FQ
RES
RD
TA
RES
3
3
3
3
3
3
Bit 2
2
TIMER
D/L
#FP
RES
Conv
FQ
RES
RES
TS
RES
2
2
2
2
2
2
Bit 1
1
AVG
BD
#FP
RTM
Conv
FQ
DB
RES
RES
RES
1
1
1
1
1
1
Bit 0
0
MON
Reset
#FP
LTM
Conv
FQ
DB
RES
RES
RES
0
0
0
0
0
0
Default
7
7
7
RES
7
7
7
7
7
7
7
7
7
15
7
15
7
15
7
15
7
15
7
15
7
15
7
15
RES
6
6
6
RES
6
6
6
6
6
6
6
6
6
14
6
14
6
14
6
14
6
14
6
14
6
14
6
14
RES
5
5
5
RES
5
5
5
5
5
5
5
5
5
13
5
13
5
13
5
13
5
13
5
13
5
13
5
13
RES
4
4
4
RES
4
4
4
4
4
4
4
4
4
12
4
12
4
12
4
12
4
12
4
12
4
12
4
12
RES
3
3
3
Hys
3
3
3
3
3
3
3
3
3
11
3
11
3
11
3
11
3
11
3
11
3
11
3
11
HYS
2
2
2
Hys
2
2
2
2
2
2
2
2
2
10
2
10
2
10
2
10
2
10
2
10
2
10
2
10
HYS
1
1
1
Hys
1
1
1
1
1
1
1
1
1
9
1
9
1
9
1
9
1
9
1
9
1
9
1
9
HYS
0
0
0
Hys
0
0
0
0
0
0
0
0
0
8
0
8
0
8
0
8
0
8
0
8
0
8
0
8
HYS
RES
7
7
RES
6
6
RES
5
5
RES
4
4
RES
3
3
FR
2
2
FR
1
1
FR
0
0
Rev. 0 | Page 31 of 40
0x20
0x01
Lockable
Y
Y
0x84
0x44
0x00
0x07
0x01
0x09
0x52
0x10
0x00
0x8B
0x54
0x95
Y
Y
Y
Y
Y
Y
N
N
N
N
N
Y
0x8B
0x54
0x95
N
N
Y
0x00
0x00
0x00
Y
Y
Y
0x05
N
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0x00
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
0x00
0x33
0x41
Y
N
N
ADM1033
Address
0x3F\BF
0x40\C0
0x41\C1
0x42\C2
R/W
R
R
R
R
0x43\C3
R
0x4A\CA
0x4B\CB
0x4E\CE
0x4F\CF
0x50\D0
0x51\D1
R
R
R
R
R
R
Description
Revision Register
Local Temperature
Local Temperature
Remote
Temperature
Remote
Temperature
TACH Period
TACH Period
THERM % On-Time
Status 1
Status 2
Status 3
Bit 7
7
4
12
4
Bit 6
6
3
11
3
Bit 5
5
2
10
2
Bit 4
4
1
9
1
Bit 3
3
0
8
0
Bit 2
2
RES
7
RES
Bit 1
1
RES
6
RES
Bit 0
0
RES
5
RES
Default
Lockable
0x02
0x00
0x00
0x00
N
N
N
N
12
11
10
9
8
7
6
5
0x00
N
7
15
7
LH
LT
FS
6
14
6
LL
RT
FA
5
13
5
RH
RES
RES
4
12
4
RL
%T
RES
3
11
3
RTH
TA
RES
2
10
2
RES
TS
RES
1
9
1
RES
RES
RES
0
8
0
RES
RES
ALERT
0xFF
0xFF
0x00
0x00
0x00
0x00
N
N
N
N
N
N
Table 35. Register 0x00, # Bytes/Block Read, Power-On Reset = 0x20, Lock = Y, S/W Reset = Y
Bit
Name
R/W Description
<7:0> # Bytes Block Read
R/W Block reads are # bytes/block read long. The maximum is 32 bytes, the SMBus transaction limit.
Table 36. Register 0x01, Configuration Register 1, Power-On Default = 0x01, Lock = Y, SW Reset = Y
Bit
7
Name
SW Con
R/W
R/W
6
Lock Bit
R/W
5
4
3
2
1
SDA Timeout
SCL Timeout
Reserved
Enable THERM Timer
Averaging Off
R/W
R/W
R/W
R/W
R/W
0
Monitor/STBY
R/W
Description
Set to 1 to have look-up table control the fan speed. Set to 0 to put ADM1033 in software/manual
control mode. Default = 0.
Set to 1 to prevent the user from writing to the ADM1033 registers. 1 = ADM1033 registers locked.
0 = ADM1033 registers unlocked. Default = 0.
1 = SDA timeout enabled. 0 = SDA timeout disabled. Default = 0.
1 = SCL timeout enabled. 0 = SDL timeout disabled. Default = 0.
Reserved.
1 = timer enabled, 0 = timer disabled. Enables THERM as an input. Default = 0.
Disables averaging at the slower conversion rates (8 Hz and slower). Averaging is automatically
disabled at the higher (16, 32, and 64) conversion rates. Default = Averaging On = 0.
Set to 1 to enable monitoring of temperature. Set to 0 to disable temperature monitoring. PowerOn Default = 1.
Table 37. Register 0x02, Configuration Register 2, Power-On Default = 0x84, Lock = Y, SW Reset = Y
Bit
7
Name
Round Robin
R/W
R/W
<6:5>
4
3
2
Reserved
Channel Selector
Reserved
Discrete/Linear RPM
R/W
R/W
R/W
R/W
1
Boost Disable
R/W
0
SW Reset
R/W
Description
Enables round-robin mode. Set to 0 for single-channel mode. (The ADC converts on only one
channel, which is determined by the channel selector bits.) Default = Round Robin = 1.
Reserved.
0 = local temperature measurements, 1 = remote temperature measurements.
Reserved.
Determines whether the fans run at discrete speeds or whether the fan speed increases with
temperature between the two thresholds. Default = 1 = linear.
Set to 1 to prevent fans from being boosted, if either THERM temperature or THERM timer limits are
exceeded. Under these conditions, the fans run at the previously calculated speed. Default = 0.
Set this bit to 1 to reset the ADM1033 registers to their default values, excluding the limit registers,
offset registers, and look-up table registers. This bit self-clears. Default = 0.
Table 38. Register 0x03, Configuration Register 3, Power-On Default = 0x44, Lock = Y, SW Reset = Y
Bit
<7:4>
<3:0>
Name
Unused
#Poles Fan
R/W
R/W
R/W
Description
Reserved.
Write the number of poles in the fan to this register. Power-On Default = 4 poles = 100. This value
should be an even number only.
Rev. 0 | Page 32 of 40
ADM1033
Table 39. Register 0x04, Configuration Register 4, Power-On Default = 0x00, Lock = Y, SW Reset = Y
Bit
7
Name
FAN_FAULT REF
R/W
R/W
<6:4>
THERM % Time Window
R/W
3
2
1
XOR Test
Unused
Enable Remote THERM Events
R/W
R/W
R/W
0
Enable Local THERM Events
R/W
Description
Sets the function for Pin 8. 0 = Default = FAN_FAULT Output (THERM Input is CMOS).
1 = Reference Input for THERM .
These bits set the time window over which THERM % is calculated.
000 = 0.25 s
001 = 0.5 s
010 = 1 s
011 = 2 s
100 = 4 s
101 = 8 s
110 = 8 s
111 = 8 s
Set this bit to 1 to enable the XOR connectivity test.
Reserved.
This bit enables THERM assertions as an output. Functions when the THERM timer is
enabled and the remote temperature exceeds its THERM limit.
This bit enables THERM assertions as an output. Functions when the THERM timer is
enabled and the local temperature exceeds its THERM limit.
Table 40. Register 0x05, Conversion Rate Register, Power-On Default = 0x0A, Lock = Y, SW Reset = Y
Bit
7
<6:4>
<3:0>
Name
Reserved
Unused
Conversion Rate
R/W
R/W
R
R/W
Description
Reserved. Do not write a 1 to this bit.
Reserved.
These 4 bits set the conversion rates of the ADM1033. Changing these bits does not
update the conversion rate until the start of the next round robin.
0000 = 0.0625 conversions/s
0001 = 0.125 conversions/s
0010 = 0.25 conversions/s
0011 = 0.5 conversions/s
0100 = 1 conversion/s
0101 = 2 conversions/s
0110 = 4 conversions/s
0111 = 8 conversions/s
1000 = 16 conversions/s
1001 = 32 conversions/s
1010 = 64 conversions/s
Table 41. Register 0x06, Fault Queue, Power-On Default = 0x01, Lock = Y, SW Reset = Y
Bit
<7:4>
<3:0>
Name
Unused
Fault Queue Length
R/W
R
R/W
Description
Reserved.
These 4 bits set the fault queue (the number of out-of-limit measurements made
before an ALERT is generated).
000x = 1
001x = 2
01xx = 3
1xxx = 4
Rev. 0 | Page 33 of 40
ADM1033
Table 42. Register 0x07, Fan BHVR Register, Power-On Default = 0x09, Lock = Y, SW Reset = Y
Bit
7
6
Name
Reserved
Fan Off
R/W
R
R/W
<5:2>
<1:0>
Reserved
DRIVE BHVR
R
R/W
Description
Reserved.
When this bit is set to 1, the fan switches off, regardless of programmed target
fan speed. Default = 0.
Reserved.
Determine which temperature source controls the DRIVE Output.
00 = local temp controls the DRIVE. 01 = remote temperature controls the
DRIVE. 10 = remote temperature controls the DRIVE. 11 = DRIVE at full speed.
Table 43. Register 0x08, Mask Register 1, Power-On Default = 0x52, Lock = N, SW Reset = Y
Bit
7
Name
Local Temp High
R/W
R/W
6
Local Temp Low
R/W
5
Remote High
R/W
4
Remote Low
R
3
Remote Diode Error
R
2
1
0
Unused
Unused
Unused
R
R
R
Description
A 1 disables the corresponding interrupt status bit from causing the interrupt
output to be set. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt
output to be set. The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt
output to be set. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from causing the interrupt
output to be set. The status bit is not affected. Default = 1.
A 1 disables the corresponding interrupt status bit from causing the interrupt
output to be set. The status bit is not affected. Default = 0.
Reserved.
Reserved.
Reserved.
Table 44. Register 0x09, Mask Register 2, Power-On Default = 0x10, Lock = N, SW Reset = Y
Bit
<7:5>
4
Name
Unused
THERM %
R/W
R
R/W
3
THERM Assert
R/W
2
THERM_State
R/W
<1:0>
Unused
R
Description
Unused.
A 1 disables the corresponding interrupt status bit from setting the interrupt
output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt
output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt
output. The status bit is not affected. Default = 0. This bit has no effect for the
ALERT Comp output.
Unused.
Table 45. Register 0x0A, Mask Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
Name
Fan Stalled
R/W
R/W
6
Fan Alarm Speed
R/W
5
4
3
2
1
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
R
R
R
R
R
R
Description
A 1 disables the corresponding interrupt status bit from setting the interrupt
output. The status bit is not affected. Default = 0.
A 1 disables the corresponding interrupt status bit from setting the interrupt
output. The status bit is not affected. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Reserved. Default = 0.
Rev. 0 | Page 34 of 40
ADM1033
Table 46. Register 0x0B, Local High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit
<7:0>
Name
Local High Limit
R/W
R/W
Description
When the local temperature exceeds this point, the corresponding interrupt status
bit is set.
Table 47. Register 0x0C, Local Low Limit, Power-On Default = 0x54, Clock = N, SW Reset = N
Bit
<7:0>
Name
Local Low Limit
R/W
R/W
Description
When the local temperature falls below this point, the corresponding interrupt status
bit is set.
Table 48. Register 0x0D, Local THERM Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Local THERM Limit
R/W
R/W
Description
When the local temperature exceeds this point, the corresponding status bit is set
and the THERM output is activated.
Table 49. Register 0x0E, Remote High Limit, Power-On Default = 0x8B, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote High Limit
R/W
R/W
Description
When the remote temperature exceeds this point, the corresponding interrupt status
bit is set.
Table 50. Register 0x0F, Remote Low Limit, Power-On Default = 0x54, Lock = N, SW Reset = N
Bit
<7:0>
Name
Remote Low Limit
R/W
R/W
Description
When the remote temperature falls below this point, the corresponding interrupt
status bit is set.
Table 51. Register 0x10, Remote THERM Limit, Power-On Default = 0x95, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote THERM Limit
R/W
R/W
Description
When the temperature exceeds this point, the corresponding status bit is set and the
THERM output is activated.
Table 52. Register 0x16, Local Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Local Offset
R/W
R/W
Description
Allows a twos complement offset to be automatically added to or subtracted from
the local temperature measurement. Resolution = 0.125°C. Maximum offset = −16°C to
+15.875°C. Default = 0.
Table 53. Register 0x17, Remote Offset Register, Power-On Default = 0x00, Lock = Y, SW Reset = N
Bit
<7:0>
Name
Remote Offset
R/W
R/W
Description
Allows a twos complement offset to be automatically added to or subtracted from
the remote temperature measurement. Resolution = 0.125°C. Maximum offset = −16°C
to +15.875°C. Default = 0.
Table 54. Register 0x19, THERM Timer % Limit, Power-On Default = 0xFF, Lock = Y, SW Reset = N
Bit
<7:0>
Name
THERM Timer on % Limit
R/W
R/W
Description
If the THERM is asserted for greater than or equal to the THERM timer on % limit of
the time window, then the corresponding status bit is set.
Rev. 0 | Page 35 of 40
ADM1033
Table 55. Register 0x1A, THERM Hysteresis, Power-On Default = 0x05, Lock = Y, SW Reset = N
Bit
<7:4>
<3:0>
Name
Reserved
THERM Hysteresis
R/W
R
R/W
Description
Reserved.
An unsigned THERM hysteresis value, LSB = 1°C. Once THERM has been
activated on a temperature channel, if the temperature drops below the THERM
limit − hysteresis, the THERM is deactivated.
Table 56. Look-Up Table Registers, Lock = Y, SW Reset = Y
Register Address
0x22
0x23
0x24
0x25
0x26
0x27
0x28
0x29
0x2A
0x2B
0x2C
0x2D
0x2E
0x2F
0x30
0x31
0x32
0x33
0x34
0x35
0x36
0x37
0x38
0x39
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Description
Look-Up Table, T1
Look-Up Table, T2
Look-Up Table, T3
Look-Up Table, T4
Look-Up Table, T5
Look-Up Table, T6
Look-Up Table, T7
Look-Up Table, T8
Look-Up Table, RPM1, LSB
Look-Up Table, RPM1, MSB
Look-Up Table, RPM2, LSB
Look-Up Table, RPM2, MSB
Look-Up Table, RPM3, LSB
Look-Up Table, RPM3, MSB
Look-Up Table, RPM4, LSB
Look-Up Table, RPM4, MSB
Look-Up Table, RPM5, LSB
Look-Up Table, RPM5, MSB
Look-Up Table, RPM6, LSB
Look-Up Table, RPM6, MSB
Look-Up Table, RPM7, LSB
Look-Up Table, RPM7, MSB
Look-Up Table, RPM8, LSB
Look-Up Table, RPM8, MSB
Power-On Default
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
0xFF
Table 57. Register 0x3A, Look-Up Table Hysteresis, Power-On Default = 0x02, Lock = Y, SW Reset = Y
Bit
<7:4>
<3:0>
Name
Reserved
Look-Up Table Hysteresis
R/W
R
R/W
Description
Reserved.
These bits determine the hysteresis applied to the temperature thresholds in
the look-up table. LSB size = 1°C.
Table 58. Register 0x3, Fan Response Register, Power-On Default = 0x11, Lock = Y, SW Reset = Y
Bit
<7:3>
<2:0>
Name
Reserved
Fan Response
R/W
R
R/W
Description
Reserved.
These bits set the fan’s response in the rpm control mode.
000 = 1.25 updates/s
001 = 2.5 updates/s (default)
010 = 5 updates/s
011 = 10 updates/s
100 = 20 updates/s
101 = 40 updates/s
110 = 80 updates/s
111 = 160 updates/s
Rev. 0 | Page 36 of 40
ADM1033
Table 59. Register 0x3D, Device ID, Power-On Default = 0x33, Lock = N, SW Reset = N
Bit
<7:0>
Name
Device ID
R/W
R
Description
This read-only value contains the device ID, which is 0x33.
Table 60. Register 0x3E, Company ID, Power-On Default = 0x41, Lock = N, SW Reset = N
Bit
<7:0>
Name
Company ID
R/W
R
Description
This read-only value contains the company ID, which is 0x41.
Table 61. Register 0x3D, Revision Register, Power-On Default = 0x02, Lock = N, SW Reset = N
Bit
<7:0>
Name
Revision ID
R/W
R
Description
This read-only value contains the revision ID.
Table 62. Register 0x40/41, Local Temperature Registers, Power-On Default = 0x02, Lock = N, SW Reset = Y
Bit
<4:0>
Name
Local Temperature LSB
R/W
R
<12:5>
Local Temperature MSB
R
Description
Contains the LSBs of the last measured local temperature value. Resolution =
0.03125°C.
Contains the MSBs of the last measured local temperature value. Resolution = 1°C.
Table 63. Register 0x42/43, Remote Temperature Registers, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<4:0>
Name
Remote Temperature LSB
R/W
R
<12:5>
Remote Temperature MSB
R
Description
Contains the LSBs of the last measured remote temperature value. Resolution =
0.03125°C.
Contains the MSBs of the last measured remote temperature value. Resolution = 1°C.
Table 64. Register 0x4A/4B, TACH Period, Power-On Default = 0xFF, Lock = N, SW Reset = Y
Bit
<7:0>
<15:8>
Name
Fan Period Count, LSB
Fan Period Count, MSB
R/W
R
R
Description
This register contains the LSBs of the last measured fan revolution count.
This register contains the MSBs of the last measured fan revolution count.
Table 65. Register 0x4E, THERM % On-Time; Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
<7:0>
Name
THERM % On Time
R/W
R
Description
This value represents the % on time of THERM activity within the time window set by
the configuration bits.
Table 66. Register 0x4F, Status 1, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
5
4
3
Name
Local Temp High
Local Temp Low
Remote Temp High
Remote Temp Low
Remote Diode Error
R/W
R
R
R
R
R
<2:0>
Reserved
R
Description
A 1 indicates the local high limit has been tripped.
A 1 indicates the local low limit has been tripped.
A 1 indicates the remote high limit has been tripped.
A 1 indicates the remote low limit has been tripped.
A 1 indicates a short or an open has been detected on the remote temperature
channel. This test is completed once on each conversion.
Reserved.
Rev. 0 | Page 37 of 40
ADM1033
Table 67. Register 0x50, Status 2, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
5
4
Name
Local THERM
Remote THERM
Reserved
THERM % Exceeded
R/W
R
R
R
R
3
2
1
0
THERM Asserted
THERM_State
Reserved
Reserved
R
R
R
R
Description
A 1 indicates the local THERM limit has been tripped.
A 1 indicates the remote THERM limit has been tripped.
Reserved for future use.
A 1 indicates the THERM signal has been asserted for longer than the programmed limit.
Clear on read. If THERM % Limit = 0x00 and THERM is asserted, it reasserts immediately.
A 1 indicates the THERM signal has been asserted low, as an input only.
A 1 indicates the THERM pin has been asserted low as an output.
Reserved.
Reserved.
Table 68. Register 0x51, Status Register 3, Power-On Default = 0x00, Lock = N, SW Reset = Y
Bit
7
6
Name
Fan Stalled
Fan Alarm Speed
R/W
R
R
5
4
3
2
1
0
Reserved
Reserved
Reserved
Reserved
Reserved
ALERT Low
R
R
R
R
R
R
Description
A 1 indicates the fan has stalled.
A 1 indicates the fan is running at full speed, due to an ALARM condition (for instance, if the
THERM temperature limit is exceeded).
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
A 1 indicates the ADM1033 has pulled the ALERT output pin low. Allows polling of a single
status register to determine if an ALERT condition has occurred in any of the status registers.
Rev. 0 | Page 38 of 40
ADM1033
OUTLINE DIMENSIONS
0.193
BSC
9
16
0.154
BSC
1
0.236
BSC
8
PIN 1
0.069
0.053
0.065
0.049
0.010
0.025
0.004
BSC
COPLANARITY
0.004
0.012
0.008
SEATING
PLANE
0.010
0.006
8°
0°
0.050
0.016
COMPLIANT TO JEDEC STANDARDS MO-137AB
Figure 44. 16-Lead Shrink Small Outline Package [QSOP]
(RQ-16)
Dimensions shown in inches
ORDERING GUIDE
Model
ADM1033ARQ
Temperature Range
−40°C to +125°C
Package Description
16-Lead QSOP
Package Option
RQ-16
ADM1033ARQ-REEL
ADM1033ARQ-REEL7
ADM1033ARQZ1
ADM1033ARQZ-REEL1
ADM1033ARQZ-REEL71
−40°C to +125°C
−40°C to +125°C
−40°C to +125°C
−40°C to +125°C
−40°C to +125°C
16-Lead QSOP
16-Lead QSOP
16-Lead QSOP
16-Lead QSOP
16-Lead QSOP
RQ-16
RQ-16
RQ-16
RQ-16
RQ-16
1
Z = Pb-free part.
Rev. 0 | Page 39 of 40
ADM1033
NOTES
© 2004 Analog Devices, Inc. All rights reserved. Trademarks and
registered trademarks are the property of their respective owners.
D04937–0–8/04(0)
Rev. 0 | Page 40 of 40