OMRON CJ1W

SYSMAC CJ-series Controller Link Units
CJ1W-CLK
CSM_CJ1W-CLK_DS_E_2_1
New Controller Link Units, Now with
4,000 Send Words
• The Controller Link is an FA network that can send and
receive large amounts of data easily and at high speed.
The Controller Link supports data links that enable sharing
data between PLCs and computers and a message
service that enables sending and receiving data whenever
required.
• Systems can be flexibly built by using Repeater Units to
enable T-branches, long-distance wiring, and converting
part of the network to optical cable.
CJ1W-CLK23
Features
• Large-capacity data links are easily achieved without programming simply by setting data link tables.
• Up to 20,000(See note 1.) send/receive words can be set per node for Units (up to 62,000 words for Boards).
• Data links can be performed with up to 4,000(See note 2.) words per node while ensuring data concurrency.
• User-set data link tables can be changed while data links are operating.(See note 3.)
• Errors for the entire system can be monitored by using error diagnosis support software and a variety of status flags.
Note: 1. Supported for unit version 1.2 or later.
2. CJ1W-CLK23 and 3G8F7-CLK@3 are supported.
3. Supported for CJ1W-CLK23, 3G8F7-CLK@3, and models ending with "-V1".
System Configuration
Wired Controller Link Units
Basic Wiring (Daisy Chain Connection)
A
A
A
B
A
T-Branch Wiring, Partial Conversion to
Optical Cable
B
A
A
(1)
B
1km Max. *
(1)
Long-distance Wiring
A
D
D
A
A
(1)
C
(1)
B
A
(2)
A
C
D
A
(1)
(1)
1km Max. *
1km Max. *
1km Max. *
B
(1)
A: Wired Controller Link Unit
B: Wired Controller Link Support Board
C: Wire-to-Optical Repeater Unit
D: Wire-to-Wire Repeater Unit
* At 500 kbits/s
(1): Twisted-pair cable
(2): Optical cable
1
CJ1W-CLK
Ordering Information
Controller Link Units, New Models
Specifications
Unit
classification
Product
name
Communications
cable
Communications
type
Wired shielded
twisted-pair
cable(See note.)
Data links and
message service
No. of unit
numbers
allocated
Max. Units
mountable
per CPU
Unit
Duplex
support
Current consumption
(A)
Model
5 V DC
Standards
24 V DC
Controller
Link
Unit
CJ1
CPU
Bus Unit
No
8
1
−
0.35
CJ1W-CLK23
UC1,N,L,
CE
Controller Link Units, Old Models
New models are fully compatible with old models and provide enhanced functionality, such as an increase in the number of send words from 1,000
to 4,000 words. Both types can be used simultaneously on the same network. Select a new model when ordering.
Specifications
Unit
classification
CJ1
CPU
Bus Unit
Product
name
Controller
Link
Unit
Communications
cable
Communications
type
Duplex
support
Max. Units
mountable
per CPU
Unit
Wired shielded
twisted-pair cable
(See note.)
Data links and
message service
No
8
No. of unit
numbers
allocated
1
Current
consumption (A)
5 V DC
0.35
Standards
24 V DC
Model
Note: New models
are listed abobe.
−
CJ1W-CLK21-V1
UC1,N,L,
CE
Note: Use the following special cable for shielded, twisted-pair cable.
• ESVC0.5×2C-13262 (Bando Electric Wire: Japanese Company)
• ESNC0.5×2C-99-087B (Nihon Electric Wire & Cable Corporation: Japanese Company)
• ESPC 1P×0.5mm2 (Nagaoka Electric Wire Co.,Ltd.: Japanese Company)
• Li2Y-FCY2×0.56qmm (Kromberg & Schubert, Komtec Department: German Company)
• 1×2×AWG-20PE+Tr.CUSN+PVC (Draka Cables Industrial: Spanish Company)
• #9207 (Belden: US Company)
Accessories
There is no accessory for the CJ series Controller Link Unit.
Controller Link Support Boards, New Models
Specifications
Product name
Controller Link
Support Board for
PCI Bus
Communications
cable
Wired shielded
twisted-pair cable
Communications
type
Data links and
message service
Accessories
• CD-ROM ×1 (See note.)
• INSTALLATION GUIDE (W467) ×1
• Communications connector ×1
Model
3G8F7-CLK23-E
Standards
CE
Controller Link Support Boards, Old Models
New models are fully compatible with old models and provide enhanced functionality, such as an increase in the number of send words from 1,000
to 4,000 words. Both types can be used simultaneously on the same network. Select a new model when ordering.
Specifications
Product name
Controller Link
Support Board for
PCI Bus
Communications
cable
Wired shielded
twisted-pair cable
Communications
type
Data links and
message service
Model
Accessories
• CD-ROM ×1 (See note.)
• INSTALLATION GUIDE (W422) ×1
• Communications connector ×1
Note: New models are
listed abobe.
Standards
3G8F7-CLK21-EV1
CE
Note: The CD-ROM contains the following software.
• Controller Link (PCI) Driver
• FinsGateway Version 2003 (PCI-CLK Edition)
• FinsGateway Version 3 (PCI-CLK Edition)
• Setup Diagnostic Utility
• C Library
2
CJ1W-CLK
Repeater Units
Name
Specifications
Controller Link
Repeater Unit
CS1W-RPT
01
PWR
T/R1
T/R2
Model
Wire-to-Wire Model
CS1W-RPT01
Wire-to-Optical (H-PCF) Model (See note 1.)
CS1W-RPT02
Wire-to-Optical (GI) Model (See note 2.)
CS1W-RPT03
Standards
UC1,CE
SL1
TER SW
SW1
1 BAUD
2 RATE
ON
TER SW
SL2
DC24V
INPUT
Using Repeater Units enables T-branches and long-distance wiring for Wired Controller Link networks, 62-node configurations, and converting
part of the network to optical cable.
Note: 1. When using wire-to-optical (H-PCF) cable, use a H-PCF cable (for both Controller Link and SYSMAC LINK) or a H-PCF optical fiber cable
with connector.
2. When using wire-to-optical (GI) cable, use a GI optical cable (for Controller Link).
Relay Terminal Block
Name
Specifications
Model
Standards
Relay Terminal Block for
Wired Controller Link Units
Used for Wired Controller Link Units (set of 5)
−
CJ1W-TB101
Controller Link Units can be replaced without stopping the communications of the entire network if a Relay Terminal Block is installed in advance
on the Unit in a Wired Controller Link network. Relay Terminal Blocks cannot be used on Controller Link Support Boards.
H-PCF Cables and Optical Connectors
Name
Application/construction
Specifications
Black
1
2
3
4
Optical Fiber Cables
Optical
Connectors
(Crimp-cut)
Controller Link,
SYSMAC LINK,
SYSBUS
5
6
1. Optical fiber single-core cord
2. Tension member (plastic-sheathed
wire)
3. Filler (plastic)
4. Filler surrounding signal wires
(plastic, yarn, or fiber)
5. Holding tape (plastic)
6. Heat-resistant PV sheath
Two-core optical
cable with tension
member
Model
10 m
S3200-HCCB101
Black
50 m
S3200-HCCB501
Black
100 m
S3200-HCCB102
Black
500 m
S3200-HCCB502
Black
1000 m
S3200-HCCB103
Orange
10 m
S3200-HCCO101
Orange
50 m
S3200-HCCO501
Orange
100 m
S3200-HCCO102
Orange
500 m
S3200-HCCO502
Orange
1000 m
S3200-HCCO103
Half lock
S3200-COCF2571
Full lock
S3200-COCF2071
Standards
−
CS1W-RPT02
H-PCF Optical Fiber Cables with Connectors (Black Composite Cables with Two-Optical Lines and Two
Power Supply Lines)
Application
Appearance
Model
Standards
S3200-CN@@@-20-20
Controller Link,
SYSMAC LINK
S3200-CN@@@-20-25
−
S3200-CN@@@-25-25
Optical connectors for H-PCF Optical Cables with Connectors are adhesive polished.
• Cable Length
The following cable lengths are available: 2 m, 5 m, 15 m, 20 m. For lengths of 21 m or more, contact your OMRON sales representative.
3
CJ1W-CLK
• Model Numbers
(1) 2 m, 5 m, 10 m, 15 m, or 20 m
(2) 21 m or longer
S3200-CN@@@
@@@-20-25
1.
2.
1. H-PCF
Optical Fiber Cable
S3200-CN-20-20
1.
3.
2. Cable length
@@@
Length
201
2m
501
5m
102
10 m
152
15 m
202
20 m
3. Specify the
cable length
in meters.
3. Connectors (both ends)
Number Connector lock
20
Full-lock
25
Half-lock
Cable length
• Optical Connector Assembly Tool
Name
Applicable Unit
Model
This tool is used on site for mounting crimp-cut
connectors and hard plastic-clad silica optical fiber
for optical transmission systems of SYSMAC
C-series SYSBUS, SYSMAC LINK, and Controller
Link.
Optical Fiber
Assembly Tool
(See note.)
Manufacturer
Standards
Sumitomo Electric
Industries, Ltd.
CAK-0057
−
Note: There is a risk of quality problems when using cables assembled by typical users, so we recommend purchasing cables with preattached
connectors or having a qualified technician assemble the cables.
GI Optical Cables
A qualified technician must select, assemble, and install GI Optical Fiber Cable, so always let an optical cable specialist handle the GI cable.
Usable Optical Cables and Optical Connectors
• Optical fiber types: Graded, indexed, multi-mode, all quartz glass, fiber (GI-type AGF cable)
• Optical fiber construction (core diameter/clad diameter): 62.5/125 μm or 50/125 μm
• Optical fiber optical characteristics of optical fiber: Refer to the tables.
• Optical connector: ST connector (IEC-874-10)
• 50/125 μm AGF Cable
Item
Minimum
Numerical
Aperture (N.A)
−
Transmission
loss (dB)
−
Connection
loss (dB)
Transmission
bandwidth
(MHz-km)
−
500
• 62.5/125 μm AGF Cable
Standard
Maximum
−
−
Item
Minimum
−
Numerical
Aperture (N.A)
−
−
0.21
−
Conditions
3.0Lf
0.5 km ≤ Lf
3.0Lf+0.2
0.2 km ≤ Lf
≤ 0.5 km
3.0Lf+0.4
Lf ≤ 0.2 km
1.0
−
λ = 0.8 μm
Ta = 25°C
Transmission
loss (dB)
λ = 0.8 μm, one location
Connection
loss (dB)
λ = 0.85 μm (LD)
Transmission
bandwidth
(MHz-km)
Lf is fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
−
−
200
Standard
Maximum
Conditions
−
−
0.28
−
−
−
3.5Lf
0.5 km ≤ Lf
3.5Lf+0.2
0.2 km ≤ Lf
≤ 0.5 km
3.5Lf+0.4
Lf ≤ 0.2 km
1.0
λ = 0.8 μm, one location
−
λ = 0.8 μm
Ta = 25°C
λ = 0.85 μm (LD)
Lf is fiber length in km, Ta is ambient temperature, and λ is the peak
wavelength of the test light source.
International Standards
• The standards indicated in the "Standards" column are those current for UL, CSA, cULus, cUL, NK, and Lloyd standards and EC Directives as
of the end of July 2007. The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA,
UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives.
• Ask your OMRON representative for the conditions under which the standards were met.
4
CJ1W-CLK
Mountable Racks
CJ1 System
Model
CPU Rack
CJ1W-CLK23
Unit version 2.0
CJ1W-CLK21-V1
Unit version 1.2
CP1H System
Expansion
Backplane
8 Units (per CPU Unit)
NSJ System
CP1H PLC
NSJ Controller
Expansion
Backplane
2 Units
(See note 1.)
Not supported
(See note 2.)
8 Units
(See note 3.)
Note: 1. A CP1W-EXT01 CJ Unit Adaptor is required.
2. One NSJW-CLK21-V1 can be mounted to the NSJ Controller.
3. If an Expansion Rack is used, the NSJW-CLK21-V1 cannot be mounted to the NSJ Controller.
Communications Specifications
Items
Specifications
Model
CJ1W-CLK23
3G8F7-CLK23-E
CJ1W-CLK21-V1
3G8F7-CLK21-EV1
Type
Wired (shielded twisted-pair cable)
Communications method
N:N token-bus method
Code
Manchester code
Modulation
Baseband code
Synchronization
Flag synchronization (conforms to HDLC frames)
Transmission path format Multidrop method (bus type)
Transmission speed
Maximum transmission
distance
The following are the maximum transmission distances depending on the transmission speed.
2 Mbits/s: 500 m
1 Mbits/s: 800 m
500 kbits/s: 1 km
Maximum distance
between nodes
Not specified. (Maximum transmission distance must be satisfied for the entire system.)
Medium
Specified shielded twist-pair cable
Two signal wires, one shield
Node connection method
PLC: Connection to terminal block
Computer: Connection using special (supplied) connector
Maximum number of
nodes
32 or 62 nodes (See note 1 and 2.)
Applicable Programming
Devices
CX-Integrator in CX-One, CX-Net in CX-Programmer (See note 2.), and Programming Console
Communications
functions
Data links and message service
Number of data link words
Send words per node: 4,000 words max. (CJ1W-CLK@3), 1,000 words max. (All other Units)
Number of send/receive words per node: 12,000 words max. (Pre-Ver. 1.2)
20,000 words max. (unit Ver. 1.2 or later)
Total number of send words per network: 62,000 words max.
Data link areas
PLC: Bit areas (CIO Area, Work Area, Link Area (See note 3.)), Data Memory (DM), Extended DM Area (EM)
Computer: FinsGateway event memory
Message length
2,012 bytes max. (including the header)
RAS functions
Error control
•
•
•
•
•
Polling node backup function
Self-diagnosis function (hardware checking at startup)
Echoback test and broadcast test (using the FINS command)
Watchdog timer
Error log function
Manchester code check
CRC check (CCITT X16+X12+X5+1)
Note: 1. With wired models, the maximum number of nodes is 32 if Repeater Units are not used. A Repeater Unit is required when building a
network with more than 32 nodes. If a Repeater Unit is used, be sure to use only the following Controller Link Units or Boards and set
the Wired Network 62 Node Enable Bit in the DM Parameter Area software switches at all nodes.
CS1W-CLK23/CLK21-V1
CJ1W-CLK23/CLK21-V1
3G8F7-CLK23-E/CLK21-EV1
2. CX-Net in CX-Programmer version 3.1 or earlier can be used only in a system with a maximum of 32 nodes (node address 1 to 32). If a
system is to be used with a maximum of 62 nodes (node addresses 1 to 62), use CX-Net in CX-Programmer version 3.2 or higher or the
CX-Integrator.
3. CJ-series PLCs do not have a Link Area, but LR000 to LR199 are automatically converted CIO 1000 to CIO 1199.
5
CJ1W-CLK
Individual Specifications
Controller Link Units
Item
Specifications
Model
CJ1W-CLK23
CJ1W-CLK21-V1
Applicable PLC
All CJ-series CPU Units
Number of mountable Units
8 max.
Installation site
Install onto a CPU Backplane or Expansion Backplane (classified as a CPU Bus Unit).
Storage location of network parameters
and manually set data link tables
System Bus Unit Area (in the CPU Unit parameter area).
Storage location of routing tables
CPU Unit parameter area
Weight
110 g
Current consumption: 5 V in PLC
0.35 A
Controller Link Support Boards (for PCI Bus)
Item
Specifications
Model
3G8F7-CLK23-E
3G8F7-CLK21-EV1
3G8F7-CLK13-E
3G8F7-CLK12-EV1
Computer-compatible models
IBM PC/AT or compatible
• CPU: Intel Celeron 400 MHz or better
• Main memory: 128 MB minimum
• One or more PCI bus slots (PCI bus revision 2.0 or later, power supply: 5 V)
• Free hard disk space: 70 MB min.
• CD-ROM drive: One required for installation
• Display: VGA (640 x 480 (pixels) min.)
(Other conditions conform to the OS.)
• FinsGateway Version2003
WindowsXP Professional
WindowsXP Home Edition
Windows2000 Professional
• FinsGateway Version3
WindowsXP Professional
WindowsXP Home Edition
Windows2000 Professional
WindowsNT4.0 (Service Pack 3 or higher)
WindowsME
Windows98SE
Compatible OS
Weight
104 g
Current consumption
3G8F7-CLK53-E
3G8F7-CLK52-EV1
5 V in PLC
0.35 A
External 24 V
−
120 g
(excluding mounting bracket)
124 g
(excluding mounting bracket)
0.54 A
0.60 A
0.35 A
0.35 A
Install FinsGateway version 3 if the operating system is Windows NT 4.0 (Service pack 3 or higher), Windows ME, or Windows 98SE. In that case,
however, the new functions of Controller Link Support Boards for the PCI Bus cannot be used (i.e., automatic data link creation with 1:N allocation,
changing data link tables with active data links, 62-node setting for wired models, and maximum of 4000 send words).
Repeater Units
Item
Specifications
Model
CS1W-RPT01
CS1W-RPT02
Supported Units/Boards
All wired Controller Link Units and Boards
Note: If a maximum of 62 nodes is used, models that support 62 nodes must be used.
Transmission line
Wire-to-wire
Wire-to-optical (H-PCF)
Wire-to-optical (GI)
Transmission line format
Multi-drop
Tree
1:1 type
1:1 type
Installation
Repeater Units are not mounted to the PLC. They are mounted separately with screws or on a DIN Track.
Weight
126 g
Allowable power supply
voltage range
20.4 to 26.4 V DC (24 V DC −15 to 10%)
Current consumption
24 V DC at 0.06 A
Inrush current
2.5 A max. at 24 V DC (5 ms after startup)
113 g (excluding mounting bracket)
CS1W-RPT03
116 g (excluding mounting bracket)
24 V DC at 0.07 A
Repeater Units are used to expand the Controller Link network for wired models. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
6
CJ1W-CLK
External Interface
CJ1W-CLK23/CJ1W-CLK21-V1
CLK21-V1
RUN ERC
INS
SD
TER ERH M/A LNK
RD
EF012
6789
345
ABCD
901
456
23
LED Indicators
Display the Unit and network status.
UNIT
No.
Unit Number Switch
One rotary switch. The unit number of the Unit on the PLC is set in single-digit
hexadecimal.
NODE
No.
x101
Node Address Switches
Two rotary switches. The node address of the Unit on the Controller Link Network is
set in 2-digit decimal.
78
901
78
x100
1 BAUD
2 RATE
ON
ON
1 2
SW1
456
23
ON
Baud Rate Switches
A two-pin DIP switch. The following setting is made.
Pins 1 and 2: Baud rate
TER SW
BD H
Terminating Resistance Switch
A slide switch. Use this switch to set the terminating resistance to ON for nodes at
both ends of the Controller Link Network.
BD L
SHLD
Terminal Block for the Communications Cable
Terminals to connect to the Controller Link Network communications cable
(twisted-pair cable).
Definition of Terminal Block Pin Names for Communications Cables
Marking
■
Notation
BD H
Signal name
Line color
Communication data, high
Black
@
BD L
Communication data, low
White
None
SHLD
Shield
None
Crimp Terminals
Use crimp terminals (M3) having the dimensions shown below.
6.2 mm max.
6.2 mm max.
7
CJ1W-CLK
Differences in Specifications of New and Old Models
Controller Link Units
Functions
CJ1W-CLK23
CJ1W-CLK21-V1
Unit version 2.0
Unit version 1.2
Note: The following
models are discontinued.
CJ1W-CLK21-V1
Note: The following models
are discontinued.
Pre-Ver. 1.2
Pre-Ver. 1.2
CJ1W-CLK21
Number of data link send
words (data link areas that are
created for a single node in a
single PLC)
20,000 max.
Number of send words per
node (total of area 1 and area
2)
4,000 words max.
(user-set links only)
Data Link Area
Allocation setting can be performed for same areas in Allocation setting can be performed for same areas in
areas 1 and 2.
areas 1 and 2.
12,000 max.
1,000 words max.
Max. Units mountable per PLC 8 Units
Automatic data link setting
4 Units
Choose from equality layout or 1:N allocations (common type, 1:1, chain type)
Supported for equality
layout only.
Changing data link allocations
Supported (Data link tables can be changed during active data links.)
during active data links
Not supported.
Maximum connectable nodes
62 nodes (See note 1.)
32 nodes
Mixed use
Yes (See note 2.)
Compatible support software
CX-Integrator for CX-One
CX-Net for
V2.1or higher, or CX-Net
CX-Programmer Ver. 5.0
for CX-Programmer Ver.
or higher
7.2 or higher
CX-Net for
CX-Programmer Ver. 3.2
or higher
CX-Net for
CX-Programmer Ver. 1.0
or higher
Note: 1. For wired models, the maximum number of nodes is 32 if Repeater Units are not used.
2. Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications
for the old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed.
Controller Link Support Boards (for PCI Bus)
Functions
3G8F7-CLK23-E
3G8F7-CLK21-EV1
Note: The following models are
discontinued.
3G8F7-CLK21-E
Number of data link send/
receive words (data link areas
for sending/receiving that are
created for a single node in a
single computer)
62,000 max.
Send words per node
4,000 words max.
(user-set links only)
32,000 max.
1,000 words max.
Changing data link allocations
Supported. (Data link tables can be changed during active data links.)
during active data links
Not supported.
Maximum connectable nodes
62 nodes (See note 1.)
32 nodes
Mixed use
Yes (See note 2.)
Compatible FinsGateway and
version of supplied CD
(See note 3.)
FinsGateway Version 2003.21 or
higher (CD Ver. 3.00 or higher)
FinsGateway Version 2003.00 or
higher (CD Ver. 2.00 or higher)
FinsGateway Version 3.00 or
higher (CD Ver. 1.00 or higher)
Compatible support software
CX-Integrator for CX-One Ver. 2.1
or higher , or CX-Net for
CX-Programmer Ver. 7.2 or higher
CX-Net for CX-Programmer Ver.
3.2 or higher
CX-Net for Ver. 1.0 or higher
Note: 1. For wired models, the maximum number of nodes is 32 if repeater units are not used.
2. Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications
for the old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed..
3. FinsGateway Version 2003 is compatible with Windows XP and Windows 2000. For Windows NT4.0 (Service Pack 3 or higher), Windows
ME, or Windows 98SE, use FinsGateway Version3. (With FinsGateway Version 3, only functions supported by the 3G8F7-CLK21 can
be used.)
8
CJ1W-CLK
Usage Precautions
• Old models and new models can be used mixed on the same network. In that case, however, build the system using the specifications for the
old models. The data link send/receive words can be separately set to their maximums when new and old models are mixed.
• Repeater Units can be used to expand a Wired Controller Link Network. For Wired-to-optical Repeater Units, always use a set of two (1:1).
Optical Ring Controller Link Units and Boards cannot be connected to the optical cable section between Repeater Units.
• Connect Repeater Units so that there are no more than two stages between any two nodes. One set of two Wire-to-Optical Repeater Units is
counted as one stage.
Dimensions
(Unit: mm)
CJ1W- CLK23/ CJ1W- CLK21-V1
65
2.7
90
2.7
82
31
9
CJ1W-CLK
Related Manuals
Cat.No
Model
Name
Applications
Description
W309
CS1W-CLK23
CS1W-CLK21-V1
CJ1W-CLK23
CJ1W-CLK21-V1
C200HW-CLK21
CVM1-CLK21
CQM1H-CLK21
CS1W-RPT01/02/03
Controller Link Units Operation Manual
W422
3G8F7-CLK12-V1
3G8F7-CLK52-V1
3G8F7-CLK21-V1
Used when information
Controller Link Support Boards for PCI Bus regarding setup procedures Describes the setup method for
for Controller Link Support the Controller Link Support Boards
Installation Guide
for PCI bus connections.
Boards for PCI bus
(3G8F7-CLK12/21/52-V1)
connections is needed.
W467
3G8F7-CLK13
3G8F7-CLK12-V1
3G8F7-CLK53
3G8F7-CLK52-V1
3G8F7-CLK23
3G8F7-CLK21-V1
Used when information
Controller Link Support Board for PCI Bus regarding setup procedures Describes the setup method for
for Controller Link Support the Controller Link Support Boards
Installation Guide
for PCI bus connections.
(3G8F7-CLK13/12-V1/53/52-V1/23/21-V1) Boards for PCI bus
connections is needed.
W383
3G8F7-CLK13
3G8F7-CLK12-V1
3G8F7-CLK53
3G8F7-CLK52-V1
3G8F7-CLK23
3G8F7-CLK21-V1
Used when information
regarding setup procedures Describes the setup method for
Controller Link Support Boards for PCI Bus
for Controller Link Support the Controller Link Support Boards
Operation Manual
for PCI bus connections.
Boards for PCI bus
connections is needed.
W464
CXONE-AL@@C-JV2/
CX-Integrator Ver. 2.1 Operation Manual
AL@@D-JV2
Used when network setup
or network monitoring
needs to be performed.
Describes the operating
procedures for the CX-Integrator.
W463
CX-One Ver. 2.1 FA Integrated Tool
CXONE-AL@@C-JV2/
Package
AL@@D-JV2
Setup Manual
Used when installing
software from the CX-One.
Provides an overview of the FA
Integration Tool Package CX-One,
and describes the CX-One
installation procedures.
Used when information
regarding operating
procedures for Wired
Controller Link Units is
needed.
Describes operating procedures
for Controller Link Units. Controller
Link Units can connect to Wired
Controller Link Units.
10
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2009.1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2009 All Right Reserved.