ETC D12305111120

Receiver with Demultiplex Output
Type D 1230 5111
•
•
•
•
•
•
•
•
Product Description
Dupline® receiver with demultiplex output (8:1) for multiplex transmission on Dupline®
channels. Applicable for transmitters with frequency input
Type Selection
Supply
Ordering no.
8 channels
2 x 10 V/10 mA
D 1230 5111 024
D 1230 5111 120
D 1230 5111 220
12 VDC
D 1230 5111 712
Code Module: No code module required. D 1230 5111
automatically uses the highest available channel group of the
Dupline® installation.
Output Specifications
Output voltage VBB
Reverse polarity
protection
Current per output
Total load capability
Short-circuit protection
Built-in protective diodes
Off-state leakage current
Output voltage drop
Cable length
Dielectric voltage
Output - Dupline®
Response time
Installationbus
D 1230 5111 024
Type: Dupline®
D-housing
Receiver
No. of channels
Output type
Supply
Supply Specifications
24 VAC
120 VAC
220 VAC
Outputs
Fieldbus
8-channel receiver
8 : 1 demultiplex function
2 NPN transistor outputs
Enable and disable output operation
D-housing
Plug-in type module
LED-indications for supply and output
AC or DC power supply
Ordering Key
(type FFD 1680, SPEC 918).
Increases the transmission
capacity of a Dupline® system
to max. 3825 x 8-bit measured values.
Du line
®
1 NPN
transistor
(enable)
10 VDC
1 NPN
transistor
(disable)
10 VDC
Yes
≤ 2.5 mA
100%
None
None
≤ 100 µA
≤ 1.2 V
≤3m
Yes
≤ 2.5 mA
100%
None
None
≤ 100 µA
≤ 1.2 V
≤3m
≥ 2 kVAC (rms)
< 1 pulse train
None
< 1 pulse train
Power supply AC types
Rated operational voltage
through pins A1 & A2 220
120
024
Frequency
Voltage interruption
Rated operational power
Rated impulse withstand
voltage
220
120
024
Dielectric voltage
Supply - Dupline®
Supply - Outputs
Alternative DC supply (VDD in)
through pins 3 & 9
Reverse polarity protection
Rate operational current
Inrush current
Rated impulse withstand
voltage
Dielectric voltage
Supply - Dupline®
Supply - Enable output
Supply - Disable output
AC types as supply source
Source voltage (VDD out)
through pins 3 & 9
Source current
Fan out
Cable length
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
Overvoltage cat. III (IEC 60664)
230 VAC +6%, -15% (IEC 60038)
120 VAC ± 10% (IEC 60038)
24 VAC ± 10%
45 to 65 Hz
≤ 40 ms
Typ. 2.5 VA
4 kV
2.5 kV
800 V
≥ 2 kVAC (rms)
≥ 2 kVAC (rms)
12 VDC ± 10%
Yes
≤ 20 mA
≤1A
800 V
None
≥ 2 kVAC (rms)
None
12 VDC
≤ 40 mA
≤ 4 modules .... .... 700
≤3m
1
Du line
D 1230 5111
®
Fieldbus
Installationbus
General Specifications
Output OFF delay
upon loss of Dupline® carrier
Power ON delay
Indication for
Supply ON
Output ON (enable)
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Undefined
Undefined, ≤ 1 s
LED, green
LED, red
IP 40
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
Humidity (non-condensing)
Mechanical resistance
Shock
Vibration
Dimensions
Material
(see "Technical Information")
Weight
AC types
DC types
20 to 80%
15 G (11 ms)
2 G (6 to 55 Hz)
D - Housing
200 g
125 g
Mode of Operation
8-channel receiver with demultiplexed outputs for enable and disable functions.
The receiver continuously receives the status of 8 channels on the highest channel
group of a Dupline® installation (e.g. channel group P if
128 channels are selected on
the channel generator). The
status of these 8 channels is
compared with the address
selected by the DIP switch
selector inside the D 1230
5111. As soon as the trans-
mitted channel status is equal
to the selected address, the
two outputs change state (enable output turns on and disable output turns off).
This module used in connection with transmitters for analogue signals (type FFD 15..)
allows the transmission of 255
individual analogue values on
one channel group. The D
1230 5111 can be used for all
Dupline® transmitters that have
enable or disable inputs, e.g.
FFD 15.., FFD 16.. or SPEC 918.
In the example given below
the Dupline® installation uses
32 channels (FMK 32 of the
channel generator). Therefore, the address setup of the
D 1230 5111 is compared with
the status of channel group
D. As soon as the status of
channel group D (provided by
the transmitter GGD 1550) is
equal to the address setup,
the disable output of the D
1230 5111 turns off. This
causes the FFD 1680 to transmit the counter value on
channel groups A-B for dis-
play on the D6369 6475
(coded for channel groups AB).
Note: If DC-supplied D 1230
5111 receivers are used, the
length of the supply bus must
not exceed 3 m in order to
avoid disturbance unbalancing the Dupline®.
Example
S: signal wire.
2
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
D
1
2
3
0
5
1
1
1
Du line
®
Fieldbus
Installationbus
Wiring Diagrams
D 1230 5111 024/120/220
AC supply (DC supply VDD)
D 1230 5111 712
DC supply
VDD in/out
VDD in/out
Disable VBB1
Disable VBB1
Enable VBB2
Enable VBB2
S: signal wire
AC supply
S: signal wire
Address Selection
Accessories
Socket◊
Socket cover
Hold down spring◊
Front mounting bezel
DIN-rail for D 411
OFF
ON
D 411
BB 5
HF
FRS 2
FMD 411
For further information refer to "Accessories".
MSB LSB
Most Significant bit
= channel 1
Least Significant bit
= channel 8
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
3