ETC DIB01

Monitoring Relays
1-Phase True RMS AC/DC Over or Under Current
Types DIB01, PIB01
DIB01
• TRMS AC/DC over or under current
monitoring relay
• Current measuring through internal shunt
• Selection of measuring range by DIP-switches
• Measuring ranges from 0.1 mA to 10 A AC/DC
• Adjustable current on relative scale
• Adjustable hysteresis on relative scale
• Adjustable delay function (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with
DIN/EN 50 022 (DIB01) or plug-in module (PIB01)
• 22.5 mm Euronorm housing (DIB01)
or 36 mm plug-in module (PIB01)
• LED indication for relay, alarm and power supply ON
• Galvanically separated power supply
PIB01
Product Description
DIB01 and PIB01 are precise
TRMS AC/DC over or under
current (selectable by DIPswitch) monitoring relays.
Direct measuring or through
current transformer.
Owing to the built-in latch
function, the ON-position of
the relay output can be
maintained. Inhibit function
Ordering Key
can be used to avoid relay
operation when not desired
(maintenance, transitions).
The LED's indicate the state
of the alarm and the output
relay. Through the built-in
shunt it is possible to monitor loads up to 10 A AC/DC.
DIB 01 C B23 5A
Housing
Function
Type
Item number
Output
Power supply
Measuring range
Type Selection
Mounting
Output
DIN-rail
SPDT
Plug-in
SPDT
Measuring range
0.1 to 5 mA AC/DC
1 to 50 mA AC/DC
10 to 500 mA AC/DC
0.1 to 5 A AC/DC
1 to 10 A AC/DC
0.1 to 5 mA AC/DC
1 to 50 mA AC/DC
10 to 500 mA AC/DC
0.1 to 5 A AC/DC
1 to 10 A AC/DC
Supply: 24 VDC
Supply: 24/48 VAC
Supply: 115/230 VAC
DIB 01 C 724 5mA
DIB 01 C 724 50mA
DIB 01 C 724 500mA
DIB 01 C 724 5A
DIB 01 C 724 10A
PIB 01 C 724 5mA
PIB 01 C 724 50mA
PIB 01 C 724 500mA
PIB 01 C 724 5A
PIB 01 C 724 10A
DIB 01 C B48 5mA
DIB 01 C B48 50mA
DIB 01 C B48 500mA
DIB 01 C B48 5A
DIB 01 C B48 10A
PIB 01 C B48 5mA
PIB 01 C B48 50mA
PIB 01 C B48 500mA
PIB 01 C B48 5A
PIB 01 C B48 10A
DIB 01 C B23 5mA
DIB 01 C B23 50mA
DIB 01 C B23 500mA
DIB 01 C B23 5A
DIB 01 C B23 10A
PIB 01 C B23 5mA
PIB 01 C B23 50mA
PIB 01 C B23 500mA
PIB 01 C B23 5A
PIB 01 C B23 10A
Input Specifications
Input
Current level
Measuring ranges (cont.)
DIB01: Terminals Y1, Y2
PIB01: Terminals 5, 7
Measuring ranges
..5MA:
0.1 to 1 mA AC/DC
0.2 to 2 mA AC/DC
0.5 to 5 mA AC/DC
Max. current for 1 s
..50MA: 1 to 10 mA AC/DC
2 to 20 mA AC/DC
5 to 50 mA AC/DC
Max. current for 1 s
Internal resist.
50 Ω
50 Ω
50 Ω
5Ω
5Ω
5Ω
Max. curr.
50 mA
50 mA
50 mA
100 mA
150 mA
150 mA
150 mA
500 mA
Specifications are subject to change without notice (21.10.00)
..500MA: 10 to 100 mA AC/DC
20 to 200 mA AC/DC
50 to 500 mA AC/DC
Max. current for 1 s
..5A:
0.1 to 1 A AC/DC
0.2 to 2 A AC/DC
0.5 to 5 A AC/DC
Max. current for 1 s
..10A:
1 to 10 A AC/DC
Max. current for 1 s
Internal resist.
0.5 Ω
0.5 Ω
0.5 Ω
0.05 Ω
0.05 Ω
0.05 Ω
3 mΩ
Max. curr.
700 mA
700 mA
700 mA
1.4 A
6A
6A
6A
15 A
11 A
15 A
1
DIB01, PIB01
Input Specifications (cont.)
Output Specifications
Measuring ranges (cont.)
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
AC 1
DC 12
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
Standard CT (examples)
TADK2
50 A/5 A
TAD2
150 A/5 A
TAD6
400 A/5 A
TAD12
1000 A/5 A
TACO200
6000 A/5 A
Note:
The input voltage cannot
raise over 300 VAC/DC with
respect to ground (PIB01 only)
Contact input
DIB01
PIB01
Disabled
Enabled
Latch disable
AACrms
5 to 50 A
15 to 150 A
40 to 400 A
100 to 1000 A
600 to 6000 A
Max. curr.
60 A
180 A
480 A
1200 A
7200 A
Terminals Z1, Y1
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
SPDT relay
250 VAC
µ
8 A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
≥ 30 x 106 operations
≥ 105 operations
(at 8 A, 250 V, cos ϕ = 1)
≤ 7200 operations/h
Operating frequency
Dielectric strength
≥ 2 kVAC (rms)
Dielectric voltage
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Supply Specifications
General Specifications
Power supply
Rated operational voltage
through terminals:
A1, A2 or A3, A2 (DIB01)
2, 10 or 11, 10
(PIB01)
724:
B48:
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
24 VDC ± 20%, insulated
24/48 VAC ± 15%
45 to 65 Hz, insulated
115/230 VAC ± 15%
45 to 65 Hz, insulated
DC supply
AC supply
2 kV
4 kV
4 kV
4 kV
4 kV
4 kV
Alarm ON delay
Alarm OFF delay
Accuracy
Temperature drift
Delay ON alarm
Repeatability
Indication for
Power supply ON
Alarm ON
B23:
Dielectric voltage
Supply to input
Supply to output
Input to output
Rated operational power
AC
DC
4 VA
3W
Output relay ON
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
Housing dimensions
DIn-rail version
Plug-in version
Weight
Screw terminals
Tightening torque
CE-Marking
2
1 s ± 0.5 s or 6 s ± 0.5 s
(input signal variation from
-20% to +20% or from
+20% to -20% of set value)
< 100 ms
< 100 ms
(15 min warm-up time)
± 1000 ppm/°C
± 10% on set value ± 50 ms
± 0.5% on full-scale
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
(EN 60529)
IP 20
3 (DIB01), 2 (PIB01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
22.5 x 80 x 99.5 mm
36 x 80 x 87 mm
Approx. 150 g
Max. 0.5 Nm
acc. to IEC 60947
Yes
Specifications are subject to change without notice (21.10.00)
DIB01, PIB01
Mode of Operation
DIB01 and PIB01 monitor
both AC and DC over or
under current through an
internal shunt.
Example 1
(connection between terminals Z1, Y1 or 8, 9 - latching
function enabled)
Example 2 (Stardard CT)
(no connection between terminals Z1, Y1 or 8, 9 - latch
function disabled)
The relay operates and latches in operating position
when the measured value
exceeds (or drops below) the
set level for more than the
set delay time. Provided that
the current has dropped
below (or has exceeded) the
set point (see hysteresis setting), the relay releases when
the interconnection between
terminals Z1, Y1 or 8, 9 is
interrupted or the power
supply is interrupted as well.
The red LED flashes until the
delay time has expired or the
measured value comes back
to a non-alarm value (see
hysteresis setting).
The relay operates when the
measured value exceeds (or
drops below) the set level for
more than the set delay time.
It releases when the current
drops below (or exceeds) the
set level (see hysteresis setting) or when power supply
is interrupted.
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
Function/Range/Level and Time Delay Setting
Selection of measuring range:
DIP-switch selector (1 to 2)
Selection of function:
DIP-switch selector (3 to 5)
Selection of function:
DIP-switch selector (6)
Selection of level and time
delay:
..5MA
12
3
6
Upper knob:
Setting of hysteresis on relative scale: 0 to 30% on set
value.
ON
..50MA
12
ON
Input range:
0.1 - 1 mA
0.2 - 2 mA
0.5 - 5 mA
Relay energized in normal
condition.
Input range:
1 - 10 mA
2 - 20 mA
5 - 50 mA
..500MA
12
Input range:
ON
10 - 100 mA
20 - 200 mA
50 - 500 mA
..5A
12
ON
Relay de-energized in
normal condition.
Input range:
0.1 - 1 A
0.2 - 2 A
0.5 - 5 A
4
Power ON delay 6 ± 0.5 s
Power ON delay 1 ± 0.5 s
Over current monitoring
relay. The alarm condition
occurs when the current input
is over the set point value.
Under current monitoring
relay. The alarm condition
occurs when the current input
is under the set point value.
Centre knob:
Current level setting on relative scale: 10 to 110% on full
scale.
Lower knob:
Setting of delay on alarm time
on absolute scale (0.1 to 30 s).
5
Contact input as latch function enable. When the contact
is closed, the latch function is
activated. Reset of the latch
condition occurs when the contact is open or by power down.
Contact input as inhibit of
alarm enable. When the contact is closed the relay remains
in normal position even if the
alarm condition occurs.
Specifications are subject to change without notice (21.10.00)
3
DIB01, PIB01
Wiring Diagrams
Example 1
Example 1
Latch/Inhibit
enable
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
PE
Y1
A1
Latch/Inhibit
enable
L
µ
A3
16
9
18
I
PE
Y2
24 VDC (+)
48/230 VAC 24/115 VAC
A2
7
8
2
4
3
I
5
15
µ
11
10
1
N (-)
N (-)
Example 2
Example 2
24 VDC (+)
48/230 VAC 24/115 VAC
24 VDC (+)
48/230 VAC 24/115 VAC
L
Z1
Y1
A1
L
µ
A3
16
9
18
I
Y2
7
A2
8
µ
11
4
3
I
5
15
2
10
1
N (-)
N (-)
PIB01
DIB01
Operation Diagrams
Over current
Under current - Latch function
Power supply
Power supply
Latch ON
Set Level
Hysteresis
Hysteresis
Set Level
1 or 6 s
Relay ON
Red LED ON
1 or 6 s
Relay ON
Red LED ON
Under current
Over current - Inhibit function
Power supply
Power supply
Inhibit ON
Set Level
Hysteresis
Set Level
Hysteresis
Relay ON
Red LED ON
1 or 6 s
1 or 6 s
Relay ON
Red LED ON
4