ETC FNQ-R-10

Bussmann®
CC-TRON®
FNQ-R
Time-Delay Fuses
⁄‹Ω£™∑ ≈ 1⁄Ω™∑, 600 Volt, ⁄Ω¢ to 30 Amps
Dimensional Data
1.5"
(50.031)
(38.1mm)
.41"
(50.005)
(10.3mm)
Catalog Symbol: FNQ-R
Time-Delay
Application: Circuit Transformer Protection
Ampere Rating: ⁄Ω¢ to 30 Amperes
Voltage Rating: 600 Volts AC (or less)†
Interrupting Rating: 200,000A RMS Sym. (U.L.)
Agency Approvals:
U.L. Listed, Std. 248-4, Class CC, Guide JDDZ, File E4273
CSA Certified, Class CC CSA, Class 1422-01,
File 53787–HRC-MISC
General Information:
• The Bussmann CC-TRON® (FNQ-R) was designed to meet
the needs of control circuit transformer protection.
• Current-limitation protects down stream components
against damaging thermal and magnetic effects of shortcircuit currents.
• Rejection feature. FNQ-R fuses meet the U.L. 508, paragraph 19.2.4 requirement that control circuit fuses used in
equipment listed for use with more than 10,000 ampere
available must have an adequate interrupting rating and
must be rejection type.
• High inrush time-delay. Control circuit transformers can
experience inrush currents up to 85 times their full-load
current rating. FNQ-R fuses can be sized according to
NEC and U.L. requirements and still allow the high inrush
currents, with significantly more time-delay than the U.L.
minimum value of 12 seconds at 200% for Class CC fuses.
• Melamine tube. Nickel-plated brass endcaps.
Maximum Acceptable Rating of Overcurrent Device*
Rated Primary
Current
(Amperes)
Maximum Rating of Overcurrent
Protective Device Expressed As A
Percent of Transformer Primary
Current Rating
Less than 2A
500**
2A to less than 9A
167
9A or more
125
*U.L. 508, Table 19.3.
**300% for other than motor control applications.
†12-30 amp is 300 Vdc and 10 KAIC.
Electrical Ratings (Catalog Symbol and Amperes)
FNQ-R-⁄Ω¢
FNQ-R-1‹Ω¡º
FNQ-R-3¤Ω¡º
FNQ-R-8
FNQ-R-‹Ω¡º
FNQ-R-1›Ω¡º
FNQ-R-3⁄Ω™
FNQ-R-9
FNQ-R-›Ω¡º
FNQ-R-1⁄Ω™
FNQ-R-4
FNQ-R-10
FNQ-R-⁄Ω™
FNQ-R-1flꭧ
FNQ-R-4⁄Ω™
FNQ-R-12
FNQ-R-flꭧ
FNQ-R-1°Ω¡º
FNQ-R-5
FNQ-R-15
FNQ-R-‹Ω¢
FNQ-R-2
FNQ-R-5flꭧ
FNQ-R-17⁄Ω™
FNQ-R-°Ω¡º
FNQ-R-2⁄Ω¢
FNQ-R-6
FNQ-R-20
FNQ-R-1
FNQ-R-2⁄Ω™
FNQ-R-6⁄Ω¢
FNQ-R-25
FNQ-R-1⁄Ω•
FNQ-R-2°Ω¡º
FNQ-R-7
FNQ-R-30
FNQ-R-1⁄Ω¢
FNQ-R-3
FNQ-R-7⁄Ω™
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to BIF document #8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
—
Carton Quantity and Weight
Ampere
Ratings
⁄Ω¢-30
Weight*
Carton
Qty.
Lbs.
Kg.
10
.200
.091
*Weight per carton
3-21-00
N99238
Rev. A
Form No. FNQ-R
Page 1 of 2
BIF Doc #1014
Bussmann®
CC-TRON®
FNQ-R
Time-Delay Fuses
⁄‹Ω£™∑ ≈ 1⁄Ω™∑, 600 Volt, ⁄Ω¢ to 30 Amps
5
100
7-1/2
3
1
1/2
Time-Current Characteristics–Total Clearing
Time-Current Characteristics–Average Melt
AMPERE
RATING
30A
15A
20A
1000
100
TIME IN SECONDS
TIME IN SECONDS
10
1
10
1
.1
.1
10000
CURRENT IN AMPERES
1000
100
10
1
.01
200
10
1
.4
100
.01
RMS SYMMETRICAL CURRENT IN AMPERES
Fuseblock Catalog Numbers
No. of
Screw
Poles Terminal
Pressure
Plate
Box
Terminal
Screw
QuickConnect
Pressure
QuickConnect
1
BC6031S
BC6031P
BC6031B
BC6031SQ
BC6031PQ
2
BC6032S
BC6032P
BC6032B
BC6032SQ
BC6032PQ
3
BC6033S
BC6033P
BC6033B
BC6033SQ
BC6033PQ
See Also OPTIMA - Overcurrent Protection Modules
Catalog Number
BIF Document No.
OPM-SW
Fuse Switch with indication
1101
OPM-CC
Fuse Module with indication
1100
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
3-21-00
N99238
Rev. A
Form No. FNQ-R
Page 2 of 2
BIF Doc #1014