Type 2 - Cooper Industries

MOTOR CONTROLLER AND FUSE SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
MAXIMUM
THREE PHASE MOTOR HORSEPOWER
200V(FLC) 230V(FLC) 460V(FLC) 575V(FLC)
C O O R D I N AT E D
PROTECTION
.5(2.2)
TYPE 2
PROTECTION
BUSSMANN/
SIEMENS
.5(2.5)
.75(3.7)
1(4.8)
1(4.8)
1.5(6.9)
2(7.8)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
3(9.6)
3(11.0)
3(11.0)
IEC
5(15.2)
3(4.8)
3(4.8)
5(7.6)
5(7.6)
7.5(11.0)
7.5(11.0)
10(14.0)
5(17.5)
7.5(25.3)
10(32.2)
Maximum ratings are
sized based on the
maximum tested
value that offers
Type 2 protection,
or the maximum
allowed by the
1996/1999 NEC®,
whichever is lower.
Refer to Bussmann
Bulletin SPD,
“Electrical Protection
Handbook” for more
information on Motor
Circuit Protection.
12-28-98
SB98107
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
Rev. A
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
75(221.0)
75(221.0)
100(285.2)
125(359.0)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.0)
30(80.0)
40(104.0)
50(130.0)
60(154.0)
75(192.0)
100(248.0)
125(312.0)
150(360.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
250(302.0)
300(361.0)
CONTACTOR
OLR
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF31/41
3TF31/41
3TF31/41
3TF32/42
3TF32/42
3TF33/43
3TF34/44
3TF46
3TF46
3TF46
3TF47
3TF48
3TF50
3TF50
31T52
31T52
3TF54
3TF54
3TF54
3TF56
3TF56
3UA5000-1A
3UA5000-1A
3UA5000-1C
3UA5000-1D
3UA5000-1E
3UA5000-1F
3UA5000-1F
3UA5000-1G
3UA5000-1H
3UA5000-1J
3UA5000-1J
3UA5000-1K
3UA5000-2S
3UA5200-2A
3UA5200-2B
3UA5200-2C
3UA5500-2D
3UA5800-2E
3UA5800-2F
3UA5800-2T
3UA5800-2V
3UA5800-8W
3UA6000-2X
3UA6000-3J
3UA6200-3L
3UA6200-3L
3UA6600-3B
3UA6600-3C
3UA6600-3D
3UA6600-3D
3UA6600-3E
LPN/LPS
LPJ
LP-CC
CLASS RK1 CLASS J CLASS CC
1.6
1.6
2.8
6
6
8
8
10
15
15
15
20
20
25
30
40
50
60
70
90
125
175
200
250
300
300
300
400
450
500
500
2
2
3
6
6
8
8
10
15
15
15
20
20
25
30
40
50
60
70
90
125
175
200
250
300
300
300
400
450
500
500
2.25
2.25
3
6
6
10
10
10
20
20
20
30
30
30
30
30
Form No. T2-S-BOTH
Page 1 of 2
BIF #8112
MOTOR CONTROLLER AND FUSE SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
MAXIMUM
THREE PHASE MOTOR HORSEPOWER
200V(FLC) 230V(FLC) 460V(FLC) 575V(FLC)
C O O R D I N AT E D
PROTECTION
.5(2.2)
TYPE 2
PROTECTION
BUSSMANN/
SIEMENS
.5(2.5)
.75(3.7)
1(4.8)
.75(3.2)
1(4.2)
1.5(6.0)
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
1.5(6.9)
2(6.8)
5(7.6)
2(7.8)
3(9.6)
3(11.0)
NEMA
7.5(11.0)
10(14.0)
5(17.5)
5(15.2)
7.5(22.0)
15(21.0)
Maximum ratings are
sized based on the
maximum tested
value that offers
Type 2 protection,
or the maximum
allowed by the
1996/1999 NEC®,
whichever is lower.
Refer to Bussmann
Bulletin SPD,
“Electrical Protection
Handbook” for more
information on Motor
Circuit Protection.
7.5(25.3)
10(28.0)
10(32.2)
20(27.0)
25(34.0)
15(42.0)
15(48.3)
20(62.1)
20(54.0)
30(40.0)
40(52.0)
50(65.0)
25(68.0)
60(77.0)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
60(177.0)
30(80.0)
75(96.0)
40(104.0)
50(130.0)
60(154.0)
100(124.0)
125(156.0)
150(180.0)
75(192.0)
75(221.0)
100(248.0)
12-28-98
SB98107
Rev. A
200(240.0)
STARTER
OLR
SXLA
SXLA
SXLA
SXLA
SXLA
SXLA
SXLA
SXLB
SXLA
SXLB
SXLB
SXLB
SXLB
SXLC
SXLC
SXLC
SXLC
SXLD
SXLC
SXLD
SXLD
SXLD
SXLE
SXLE
SXLE
SXLE
SXLF
SXLE
SXLF
SXLF
SXLF
SXLG
SXLG
SXLG
SXLG
SXLG
SXLG
3UA5000-1A
3UA5000-1A
3UA5000-1C
3UA5000-1D
3UA5000-1E
3UA5000-1F
3UA5000-1G
3UA5400-1G
3UA5000-1H
3UA5400-1H
3UA5400-1J
3UA5400-1K
3UA5400-1K
3UA5400-1K
3UA5400-2A
3UA5400-2B
3UA5400-2C
3UA5800-2C
3UA5400-2D
3UA5800-2D
3UA5800-2E
3UA5800-2F
3UA5800-2F
3UA5800-2T
3UA5800-2V
3UA5800-2V
3UA6200-2W
3UA5800-8W
3UA6200-2X
3UA6200-3H
3UA6200-3J
3UA6600-3B
3UA6600-3C
3UA6600-3C
3UA6600-3C
3UA6600-3D
3UA6600-3D
LPN/LPS
LPJ
LP-CC
CLASS RK1 CLASS J CLASS CC
2
2
3
6
6
8
10
10
15
15
15
20
20
20
25
30
40
40
50
50
60
70
70
90
125
150
150
175
200
225
250
300
350
400
400
450
450
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other
copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and
provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to
change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the
right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it
should be tested by the user in all possible applications.
1.6
1.6
2.8
6
6
8
10
10
15
15
15
20
20
20
25
30
40
40
50
50
60
70
70
90
125
150
150
175
200
225
250
300
350
400
400
450
500
2.25
2.25
3
6
6
10
10
10
20
20
20
30
30
30
30
30
30
30
Form No. T2-S-BOTH
Page 2 of 2
BIF #8112