ALLEN-BRADLEY 194E-HE8N-175

IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Features
•
•
•
•
•
•
•
•
•
•
Description
Bulletin 194E load switches are designed for use in North America
as local motor isolation and for IEC disconnect switch applications
outside of North America. Available in 3- and 4-pole versions with
add-on grounding and neutral terminals and auxiliary contacts,
Bulletin 194Es use similar operating handles as the Bulletin 194L
Control and Load Switches.
Bulletin 194E switches are offered in two mounting styles, Front/
Door and Base/DIN configurations, for a variety of installations.
Switch body styles for Bulletin 194E base-mounted switches include
standard interlock shaft; Bulletin 194E front-mounted switches
include standard shaft.
Two-position OFF-ON switch is used to connect or disconnect a
variety of inductive loads, including solenoids, actuators, valves,
magnetic starters, relays, and motors up to 100 HP.
At-Motor Disconnect Switch
125, 160, 250, 315 A Versions of Inductive Load-Rated Switches
IP65/Type 1/3/3R/12 Operating Handles
IP2LX Finger-Safe Terminals
3- and 4-Pole Versions
Front/Door or DIN/Base Mounting Configurations
OFF-ON Configurations
Box Lug and Bolt-on Terminals Available
Switches Include Operating Shaft
Suitable as Motor Disconnect
Conformity to Standards
• IEC 207
• IEC 947-1
• IEC 947-3 low-voltage switchgear and control gear part 3:
switches, disconnecters, switch-disconnecters and fusecombination units. CE
• UL 508: Industrial Control Equipment. CUL
Approvals
• UL listed (Box Lug Version)
• UR recognized (Bolt-on Version)
• CUL listed (Box Lug Version)
• CUR recognized (Bolt-on Version)
• Meets IEC, VDE and BS standard requirements
• IEC/CE marked for all applicable directives (per EN 60947-3)
Your order must include:
• Catalogue Number of switch body.
• Catalogue Number of actuator.
• If required, Catalogue Number of accessories.
10-25
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Product Selection
OFF-ON Base-Mounted Switch — with Box Lugs — UL Listed
Switch Body
Function
Sw. Angle
No. of
Poles
ON
1
3
OFF
0
O
90
ON
1
4
OFF
0
O
90
OFF/0
0
0
0
0
0
0
0
ON/1
X
X
X
X
X
X
X
Max. Load
(Amps)
AC23 Rated kw
690V AC 50 Hz
Hp @ 480V AC
60 Hz 3 ∅
Catalogue Number
125
37
60
194E-A125-1753
160
37
60
194E-A160-1753
250
45
75
194E-A250-1753
315
45
100
194E-A315-1753
125
37
60
194E-A125-1754
160
37
60
194E-A160-1754
250
45
75
194E-A250-1754
315
45
100
194E-A315-1754
Max. Load
(Amps)
AC23 Rated kw
690V AC 50 Hz
Hp @ 480V AC
60 Hz 3 ∅
Catalogue Number
125
37
60
194E-B125-1753
160
37
60
194E-B160-1753
250
45
75
194E-B250-1753
315
45
100
194E-B315-1753
125
37
60
194E-B125-1754
160
37
60
194E-B160-1754
250
45
75
194E-B250-1754
315
45
100
194E-B315-1754
OFF-ON Base-Mounted Switch — with Bolt-on Wiring — UR Recognized
Switch Body
Function
Sw. Angle
No. of
Poles
ON
1
3
OFF
0
O
90
ON
1
4
OFF
0
O
90
OFF/0
0
0
0
0
0
0
0
ON/1
X
X
X
X
X
X
X
OFF-ON Front-Mounted Switch — with Box Lugs — UL-Listed
Switch Body
Function
Sw. Angle
ON
1
OFF
0
O
90
ON
1
OFF
0
O
90
No. of
Poles
OFF/0
ON/1
1
2
3
0
0
0
X
X
X
1
2
3
4
0
0
0
0
X
X
X
X
Max. Load
(Amps)
125
AC23 Rated kw
690V AC 50 Hz
37
Hp @ 480V AC
60 Hz 3 ∅
60
Catalogue Number
194E-E125-1753
160
37
60
194E-E160-1753
250
45
75
194E-E250-1753
315
45
100
194E-E315-1753
125
37
60
194E-E125-1754
160
37
60
194E-E160-1754
250
45
75
194E-E250-1754
315
45
100
194E-E315-1754
OFF-ON Front-Mounted Switch — with Bolt-on Wiring — UR-Recognized
Switch Body
Function
Sw. Angle
ON
1
OFF
0
O
10-26
OFF/0
ON/1
Max. Load
(Amps)
AC23 Rated kw
690V AC 50 Hz
Hp @ 480V AC
60 Hz 3 ∅
Catalogue Number
1
0
X
125
37
60
194E-F125-1753
2
0
X
160
37
60
194E-F160-1753
3
0
X
250
45
75
194E-F250-1753
315
45
100
194E-F315-1753
125
37
60
194E-F125-1754
160
37
60
194E-F160-1754
250
45
75
194E-F250-1754
315
45
100
194E-F315-1754
90
ON
1
OFF
0
No. of
Poles
90
O
1
2
3
4
0
0
0
0
X
X
X
X
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Accessories
Handles
Actuators 194E — 125…315 A
Actuators with Screw
Fixing (Includes Legend
Plate and Control Knob)
Rating
Colour
Black
Type A
Legend Plate Size
88 mm x 88 mm
3-15/32 in. x 3-15/32 in.
Type I
IP65
Type 3/3R/12
Type G
Red/Yellow
Type N
Auxiliary Contacts—2 N.O./1 N.C.
Earthing/Grounding Terminal
PE
PE
Neutral Terminal
N
N
194E-HE13A-175
194E-125…315A
194E-HE8I-175
ON
1
130 mm x 130 mm
5-1/8 in. x 5-1/8 in.
OFF
0
135 mm x 135 mm
5-5/16 in. x 5-5/16 in.
90 mm x 90 mm
3-35/64 in. x 3-35/64 in.
135 mm x 135 mm
5-5/16 in. x 5-5/16 in.
Catalogue Number
194E-HE8A-175
90 mm x 90 mm
3-35/64 in. x 3-35/64 in.
Black
Legend
Marking
130 mm x 130 mm
5-1/8 in. x 5-1/8 in.
88 mm x 88 mm
3-15/32 in. x 3-15/32 in.
Red/Yellow
Use with
Catalogue
Number
194E-HE13I-175
O
194E-HE8G-175
90
194E-HE13G-175
194E-125…315A
194E-HE8N-175
194E-HE13N-175
Use with
194E-A125-160
194E-B125-160
194E-A250-315
194E-B250-315
194E-E125-160
194E-F125-160
194E-E250-315
194E-F250-315
Catalogue Number
Use with
194E-A135-160
194E-E135-160
194E-A250-315
194E-E250-315
194E-B135-160
194E-F135-160
194E-B250
194E-F250
194E-B315
194E-F315
Catalogue Number
Use with
194E-A125-160
194E-E125-160
194E-A250-315
194E-E250-315
194E-B125-160
194E-F125-160
194E-B250
194E-F250
194E-B315
194E-F315
Catalogue Number
194E-AB-P21-160
194E-AB-P21-315
194E-EF-P21-160
194E-EF-P21-315
194E-AE160-PE
194E-AE315-PE
194E-BF160-PE
194E-BF250-PE
194E-BF315-PE
194E-AE160-TN
194E-AE315-TN
194E-BF160-TN
194E-BF250-TN
194E-BF315-TN
10-27
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Accessories
Handles (continued)
Terminal Cover
Use with
194E-A125-160
194E-E125-160
194E-A250-315
194E-E250-315
194E-B125-160
194E-F125-160
194E-B250-315
194E-F250-315
Catalogue Number
2 covers per
pole required
194E-AE125-C1
2 covers per
pole required
194E-AE250-C1
2 covers per
pole required
194E-BF125-C1
2 covers per
pole required
194E-BF250-C1
Legend
Additional Name Plate and Frame
Colour
Gray/Black
10 per package
Red/
Yellow
10-28
Legend Size
Use with
19.2 mm x 49 mm
3/4 in. x 1-59/64 in.
88 mm x 88 mm
90 mm x 90 mm
130 mm x 130 mm
135 mm x 135 mm
legend frames
(Size 8,13)
Legend Marking
MAIN SWITCH
HAUPTSCHALTER
INTERR. PRINCIPALE
INTERR. PRINCIPAUX
INTERR. PRINCIPAL
HUVUDBRYTARE
WAHLSCHALTER
Catalogue Number
194L-G3515A
194L-G3515B
194L-G3515C
194L-G3515D
194L-G3515E
194L-G3515F
194L-G3515G
EMERGENCY OFF
194L-G3515H
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Specifications
IEC Performance Data for 194E
Rated insulation voltage Ui: ➊
[V]
194E-125
1000
194E-160
1000
194E-250
1000
194-315
1000
Rated impulse withstand voltage Uimp
Rated frequency
Rated thermal current Ith open
[kV]
[kV]
[V]
[Hz]
[A]
8
3.5
1000
50/60
125
8
3.5
1000
50/60
160
8
3.5
1000
50/60
250
8
3.5
1000
50/60
315
Rated thermal current Ithe enclosed
[A]
125
160
250
315
[A]
125
160
250
315
[kW]
[kW]
[kW]
[kW]
[kW]
[kW]
[kA]
[A]
[A]
[A]
[A]
[A]
30
45
37
22
37
30
30
125
2500
800
750
340
30
55
37
30
45
37
30
160
3000
900
850
340
37
90
45
37
55
45
30
250
4600
1600
1380
400
55
110
45
45
75
45
30
315
5800
1800
1650
400
Test voltage 1 min
Rated voltage Ue ➊➋
Rated current Ie
AC-1 /
Non inductive or slightly induc. load
Switching of resistive loads with slight
AC-21A
overload
Rated power Pe
AC-23A
Occasional switching of motor and
other highly inductive loads
AC-3
Squirrel-cage motors: starting and
stopping of running motors
Conditional rated short-circuit current
Max. fuse rating of circuit (type g, G)
Rated short-time current Icw 1S
Rated breaking capacity
AC-23A (cos ϕ 0.45)
230V
400V
690V
230V
400V
690V
400/415V
230V
400V
690V
➊ Valid for line with grounded common neutral termination, over voltage category III, pollution degree 3. Other values on request.
➋ Not suitable for load-switching applications (AC-20A) above 690V.
10-29
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Specifications
IEC Performance Data for 194E (continued)
DC Switching Capacity
194E-125
194E-160
194E-250
194E-315
[A]
[A]
[A]
125
110
45
160
140
55
250
220
85
315
280
110
[A]
[A]
[A]
125
80
16
160
100
20
250
150
32
315
200
40
Rated current Ie
DC-21A
For resistive loads T≤1 ms
Rated voltage [V]
60
110
220
Rated voltage [V]
110
220
440
No. Poles in series
3
3
3
No. Poles in series
4
4
4
Rated voltage [V]
24
48
60
110
220
No. Poles in series
4
4
4
4
4
[kW]
[kW]
[kW]
[kW]
[kW]
3
6
7.5
10
4.5
3.8
7.5
9.5
12.5
5.5
6
12
15
20
8
7.5
15
19
25
10
Rated voltage [V]
24
48
60
110
220
No. Poles in series
4
4
4
4
4
[kW]
[kW]
[kW]
[kW]
[kW]
3
6
7.5
8.8
2.5
3.8
7.5
9.5
11
3.5
6
12
15
17.5
5.5
7.5
15
19
22
7
194E-125
600
600
150
150
194E-160
600
600
200
200
194E-250
600
600
250
250
194E-315
600
600
300
300
80
7.5
88
20
78
35
62
35
84
15
8
30
77
60
62
60
100
10
110
25
88
40
70
40
108
20
104
40
77
60
62
60
135
15
136
30
99
45
86
50
160
30
154
60
96
75
77
75
180
20
155
35
108
50
104
60
208
40
192
75
124
100
99
100
Rated power Pe
DC-22A, DC-3
For Inductive loads T≤2.5 ms
Rated Power Pe
DC-23A, DC-5
For Inductive loads T≤15 ms
UL CSA Performance Data for 194E
Rated Insulation Voltage
Rated voltage
Continuous current
Ampere rating for general use
Heavy Pilot Duty
Standard Duty
Motor rating 60Hz
[V]
[V]
[A]
[A]
[AC]
[DC]
120V, 1 P
240V, 1 P
1-phase (2-poles)
480V, 1 P
600V, 1 P
120V, 3 P
240V, 3 P
3-Phase
480V, 3 P
600V, 3 P
10-30
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
[FLA]
[HP]
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Specifications
Mechanical Data
194E-125
IP65
—
IP65
IP20
IP20
—
194E-160
IP65
—
IP65
IP20
IP20
—
194E-250
IP65
—
IP65
IP20
IP20
—
194E-315
IP65
—
IP65
IP20
IP20
—
[Million
operations]
0.1
0.1
0.075
0.075
No.
—
B11
70
—
B14
150
—
B14
150
Actuators
Protection class according to IEC 529
Front side Front unit
Box lugs ➊
Bolt-on
straight version ➊
bent version
Mechanical life
Box lugs — max. wire gauges
Terminal sizes according to IEC 947-1
Fine strands, 1 conductor
Gauge
Max.
mm2
—
B11
70
Min.
mm2
16
16
25
25
Rigid wire, 1 conductor
Max.
mm
2
95
95
185
185
Wire gauges according to UL / CSA
Min.
Max.
mm2
AWG
MCM
AWG
10
3/0
—
8
10
3/0
—
8
16
—
350
4
16
—
350
4
Min.
➊ When provided with terminal covers.
Approvals
Catalogue No. or Designation
194E-A125
194E-E125
194E-A160
194E-E160
194E-A250
194E-E250
194E-A315
194E-E315
194E-B125
194E-F125
194E-B160
194E-F160
194E-B250
194E-F250
194E-B315
194E-F315
Aux. switch blocks
Ground terminal
Neutral terminal
UL-Listed
(marked w/UL)
A
A
A
A
—
—
—
—
Z
Z
Z
UR-Recognized
(marked w/UR)
—
—
—
—
A
A
A
A
Z
Z
Z
UL-Listed for
Canada (marked
with cUL)
A
A
A
A
—
—
—
—
Z
Z
Z
UR-Recognized
for Canada
(marked w/cUR)
—
—
—
—
A
A
A
A
Z
Z
Z
CE
A
A
A
A
A
A
A
A
Z
Z
Z
A = approved or test passed
Z = accessories are covered by the approval for the switch
10-31
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes.
Front-Installation Box Lugs, 3- and 4-Pole
I
max. E
mm 2
A
F
H
G
C
B
Switch Body 194E-E
[A]
A
91
(3-19/32)
91
(3-19/32)
103
(4-3/64)
103
(4-3/64)
125
160
250
315
D
B
112
(4-13/32)
112
(4-13/32)
145
(5-23/32)
145
(5-23/32)
C
36
(1-13/32)
36
(1-13/32)
44
(1-23/32)
44
(1-23/32)
D
38
(1-1/2)
38
(1-1/2)
52.5
(2-1/16)
52.5
(2-1/16)
E
95
(3-23/64)
95
(3-23/64)
185
(7-9/32)
185
(7-9/32)
F
88
(3-7/16)
88
(3-7/16)
88
(3-7/16)
88
(3-7/16)
G
68
(2-5/8)
68
(2-5/8)
68
(2-5/8)
68
(2-5/8)
H
108
(4-1/4)
108
(4-1/4)
120
(4-11/16)
120
(4-11/16)
I
M5
(3/16)
M5
(3/16)
M5
(3/16)
M5
(3/16)
Front-Installation Bolt-on Terminals, 3- and 4-Pole
F
O
G
P
D
A
H
I
N
M
E
L
B
Switch Body 194E-F
[A]
A
91
125
(3-19/32)
91
160
(3-19/32)
103
250
(4-3/64)
103
315
(4-3/64)
10-32
B
112
(4-3/32)
112
(4-3/32)
145
(5-23/32)
145
(5-23/32)
C
38
(1-1/2)
38
(1-1/2)
52.5
(1-22/32)
52.5
(1-22/32)
C
D
65.5
(2-9/16)
65.5
(2-9/16)
60.4
(2-3/8)
60.4
(2-3/8)
E
3
(1/8)
3
(1/8)
4
(5/32)
4
(5/32)
F
2
(3/32)
2
(3/32)
2
(3/32)
2
(3/32)
G
36
(1-13/32)
36
(1-13/32)
44
(1-23/32)
52
(2-1/16)
H
88
(3-7/16)
88
(3-7/16)
88
(3-7/16)
88
(3-7/16)
I
68
(2-5/8)
68
(2-5/8)
68
(2-5/8)
68
(2-5/8)
L
10
(13/32)
10
(13/32)
13
(1/2)
13
(1/2)
M
90
(3-17/32)
90
(3-17/32)
100
(3-15/16)
100
(3-15/16)
N
64
(2-17/32)
64
(2-17/32)
70
(2-3/4)
70
(2-3/4)
O
M5
(3/16)
M5
(3/16)
M5
(3/16)
M5
(3/16)
P
M10
(3/8)
M10
(3/8)
M12
(15/32)
M12
(15/32)
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes.
Base-Mounting Box Lugs, 3- and 4-Pole
E
L
max. D
mm 2
A
H
F
B
C
G
E
Switch Body 194E-A
[A]
A
91
125
(3-19/32)
91
160
(3-19/32)
98
250
(3-27/32)
98
315
(3-27/32)
I
B
112
(4-13/32)
112
(4-13/32)
145
(5-23/32)
145
(5-23/32)
C
38
(1-1/2)
38
(1-1/2)
52.5
(1-23/32)
52.5
(1-23/32)
D
95
(3-23/64)
95
(3-23/64)
185
(7-9/32)
185
(7-9/32)
E
2
(3/32)
2
(3/32)
2
(3/32)
2
(3/32)
F
118
(4-5/8)
118
(4-5/8)
140
(5-1/2)
140
(5-1/2)
G
6.4
(1/4)
6.4
(1/4)
6.4
(1/4)
6.4
(1/4)
H
108
(4-1/4)
108
(4-1/4)
126
(4-15/16)
126
(4-15/16)
I
64
(2-17/32)
64
(2-17/32)
70
(2-3/4)
70
(2-3/4)
L
36
(1-13/32)
36
(1-13/32)
44
(2-1/16)
44
(2-1/16)
Base-Mounting Bolt-on Terminals, 3- and 4-Pole
Q
P
O
F
N
G
L M
E
A
D
F
B
C
H
Switch Body 194E-B
[A]
A
B
C
91
112
38
125 (3-19/32) (4-13/32) (1-1/2)
91
112
38
160 (3-19/32) (4-13/32) (1-1/2)
98
145
52.5
250 (3-27/64)
(5-23/32) (1-23/32)
98
145
52.5
315 (3-27/64)
(5-23/32) (1-23/32)
D
36.5
(1-7/16)
36.5
(1-7/16)
38.6
(1-1/2)
38.6
(1-1/2)
E
3
(1/8)
3
(1/8)
4
(5/32)
4
(5/32)
F
2
(3/32)
2
(3/32)
2
(3/32)
2
(3/32)
G
76
(3)
76
(3)
80
(3-1/8)
80
(3-1/8)
I
H
I
L
M
N
36
20
90
64
10
(1-13/32) (3/4) (3-17/32) (2-17/32) (13/32)
36
20
90
64
10
(1-13/32) (3/4) (3-17/32) (2-17/32) (13/32)
44
26
100
70
13
(1-23/32) (1-1/64) (3-15/16) (2-3/4)
(1/2)
44
26
100
70
13
(1-23/32) (1-1/64) (3-15/16) (2-3/4)
(1/2)
O
M10
(3/8)
M10
(3/8)
M12
(15/32)
M12
(15/32)
P
36
(1-13/32)
36
(1-13/32)
44
(1-23/32)
52
(2-1/16)
Q
6.4
(1/4)
6.4
(1/4)
6.4
(1/4)
6.4
(1/4)
10-33
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes.
Box Ground and Neutral Terminal
Switch Body 194E-F
[A]
A
37.8
(1-1/2)
37.8
(1-1/2)
52.3
(2-1/16)
52.3
(2-1/16)
125
160
250
315
B
64
(2-17/32)
64
(2-17/32)
71.1
(2-25/32)
71.1
(2-25/32)
C
108
(4-1/4)
108
(4-1/4)
126
(4-15/16)
126
(4-15/16)
D
37.8
(1-1/2)
37.8
(1-1/2)
52.3
(2-1/16)
52.3
(2-1/16)
E
64
(2-17/32)
64
(2-17/32)
80.6
(3-1/8)
80.6
(3-1/8)
F
108
(4-1/4)
108
(4-1/4)
126
(4-15/16)
126
(4-15/16)
Bolt Ground and Neutral Terminal
FRONT
BASE
L
F
D
H
B
A
Switch Body 194E-F
[A]
A
37.8
125
(1-1/2)
37.8
160
(1-1/2)
52.3
250
(2-1/16)
52.3
315
(2-1/16)
N
G
C
B
64
(2-17/32)
64
(2-17/32)
68
(2-21/32)
68
(2-21/32)
I
E
C
10
(13/32)
10
(13/32)
13
(1/2)
13
(1/2)
D
M10
(13/32)
M10
(13/32)
M12
(15/32)
M12
(15/32)
E
90
(3-17/32)
90
(3-17/32)
100
(3-15/16)
100
(3-15/16)
F
3
(1/8)
3
(1/8)
4
(5/32)
4
(5/32)
G
37.8
(1-1/2)
37.8
(1-1/2)
52.3
(2-1/16)
52.3
(2-1/16)
H
64
(2-17/32)
64
(2-17/32)
68
(2-21/32)
68
(2-21/32)
M
I
10
(13/32)
10
(13/32)
13
(1/2)
13
(1/2)
Auxiliary Contacts
FRONT
14
(9/16)
10-34
BASE
50
(1 31/32)
14
(9/16)
50
(1 31/32)
L
M10
(13/32)
M10
(13/32)
M12
(15/32)
M12
(15/32)
M
90
(3-17/32)
90
(3-17/32)
100
(3-15/16)
100
(3-15/16)
N
3
(1/8)
3
(1/8)
4
(5/32)
4
(5/32)
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes.
Terminal Cover
A
Switch Body 194E-F
A
76.2
125
(3)
76.2
160
(3)
88
250
(3-15/32)
88
315
(3-15/32)
B
B
95
(3-3/4)
95
(3-3/4)
109.5
(4-5/16)
109.5
(4-5/16)
Door Clutches
L for Standard Shaft
93…199 mm
(3-21/32in…7-27/32in)
Shaft must be cut
to length at
installation.
fl 27
(1-1/16)
5.4 mm
(7/32)
88
(3-15/32)
68
(2-11/16)
L
10-35
IEC Load Switches
Bulletin 194E
125 Amps to 315 Amps
Approximate Dimensions—mm (inches)
Dimensions are not intended to be used for manufacturing purposes.
Actuators (Type 194E-HE-8A-8I-8G-8N)
1-4 mm
(1/32-1/8)
1-4 mm
(1/32-1/8)
68
(2-11/16)
fl 5.3
(7/32)
92 x 92
(1-5/8 x 1-5/8)
88 x 88
(3-15/16 x 3-15/16)
fl 12
(15/32)
45
(1-49/64)
68
(2-11/16)
49
(1-15/16)
Actuators (Type 194E-HE-13A-13I-13G-13N)
1-4 mm
(1/32-1/8)
1-4 mm
(1/32-1/8)
68
(2-11/16)
fl 5.3
(7/32)
130 x 130
(5-1/8 x 5-1/8)
135 x 135
(5-5/16 x 5-5/16)
68
(2-11/16)
fl 20
(15/32)
55
(2-5/32)
68
(2-11/16)
Additional Name Plate
Frame and legend snaps on to actuator bezel. Fits size 8 and 13 actuators.
84
(3-5/16)
18
(23/32)
G3515
6.7
(9/32)
10-36