OMRON G3PC_07

SSR with Failure Detection Function
G3PC
Detects failures in SSRs used for heater
temperature control and simultaneously
outputs alarm signals. This product
supports the safe design of heater control
systems, and contributes to maintenance
improvements by the user.
• Main detection items:
SSR short-circuits and SSR open-circuits
• Alarm output possible to NPN/PNP-input devices.
• The failure-detection function is built-in and power is supplied
from the main circuit power supply making wiring simple.
• Slim design (width: 22.5 mm) incorporating radiator.
• In addition to screw mounting, DIN track mounting is also possible.
• Conforms to international standards (IEC, UL, and CSA).
Ordering Information
■ List of Models
Insulation method
Zero-cross function
Phototriac coupler
Yes
Indicators
Applicable output load
Yes
(See page 75)
20 A, 100 to 240 VAC
(resistive load: AC, Class1)
Model number
G3PC-220B-VD
■ Accessories (Order Separately)
Name
Mounting Track
Dimensions
50 cm (l) × 7.3 mm (t)
Model number
PFP-50N
1 m (l) × 7.3 mm (t)
PFP-100N
1 m (l) × 16 mm (t)
PFP-100N2
Specifications
SSR
■ Ratings (At an Ambient Temperature of 25°C)
Detection Power Supply
Main Circuit
Rated power supply voltage
100 to 240 VAC (50/60 Hz)
Rated load voltage
100 to 240 VAC (50/60 Hz)
Operating voltage range
75 to 264 VAC (50/60 Hz)
Operating voltage range
75 to 264 VDC (50/60 Hz)
Current consumption
15 mA AC max. (at 200 VAC)
Rated carry current
20 A (Ta = 40)
Minimum load current
0.1 A
Inrush current resistance (peak value)
220 A (60 Hz, 1 cycle)
Permissible (I2t)
260 A2S
Applicable load
(with Class-1 AC resistive load)
4 kW (at 200 VAC)
Operating Circuit
Input method
Voltage input
Rated input voltage
12 to 24 VDC
Operating input voltage
range
9.6 to 30 VDC
Must-operate voltage
9.6 VDC max.
Alarm Output
Reset voltage
1 VDC min.
Output OFF collector voltage
30 VDC max.
Input current
7 mA DC max. (at rated input voltage)
Maximum carry current
0.1 A
Output form
Independent NPN open collector
SSR with Failure Detection Function
G3PC
J-71
■ Characteristics
1/2 of load power source cycle + 1 ms max.
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
Main circuit
Alarm output
Output ON voltage drop
1.6 V rms max.
OFF leakage current
10 mA max. (at 200 VAC)
Output ON voltage drop
1.5 V max.
OFF leakage current
0.1 mA max.
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to10 Hz, 0.35-mm single amplitude
Shock resistance
Destruction: 294 m/s2
Ambient temperature
Operating: -20 to 60°C (with no icing or condensation)
Storage: -30 to 70°C (with no icing or condensation)
Ambient operating humidity
45% to 85%
Weight
Approx. 300 g
Approved standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3) approved by VDE
EMC
Emission
Immunity
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
Immunity
Dips
EN55011 Group 1 Class B
IEC947-4-3, EN61000-4-2
4 kV contact discharge
8 kV air discharge
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
IEC947-4-3, EN61000-4-5
2 kV
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
IEC947-4-3, EN61000-4-11
Engineering Data
Ta = +25°C
8
The figure will be less than 1/2 for repetitive
input.
25
20
Input impedance
6
15
4
Inrush Current Resistivity
(Non-repetitive Input)
Inrush current (A. Peak)
10
Load Current vs.
Ambient Temperature
Load current (A)
Input impedance (kΩ)
Input current (mA)
Input Voltage vs. Input
Current
Input Voltage vs. Input
Impedance
250
200
150
10
100
5
50
Input current
2
0
J-72
0
10
20
30
40
Input voltage (V)
-20
0
20
SSR with Failure Detection Function G3PC
40
60
80
100
Ambient temperature (˚C)
0
10
30 50
100
300 500 1,000 3,000 5,000
Energized time (ms)
Operation
■ Failure Detection Function
Conditions for SSR Failure Detection
Failure mode
(See note 1.)
Operating input (between
terminals A1 and A2)
Detection time
Alarm display
(See note 3.)
SSR short-circuit
OFF
0.5 s max. (See note 2.)
Red
Open collector transistor
output
SSR half-wave short-circuit OFF
SSR open-circuit
Alarm display (between
terminals X1 and X2)
(See note 3.)
ON
SSR half-wave open-circuit ON
Note: 1. The contents of each of the above failure modes is as follows:
SSR short-circuit: SSR output circuit remains in the ON state.
SSR half-wave short-circuit: SSR output circuit remains in the ON state in one direction.
SSR open-circuit: SSR output circuit remains in the OFF state.
SSR half-wave open-circuit: SSR output circuit remains in the OFF state in one direction.
In addition to the failure modes listed above, detection of circuit disconnections for the load circuit is also possible. (As a rough guide,
circuit disconnection will be detected if the load impedance is greater than or equal to 1 MΩ.)
2. The same power supply is used for both the detection and for the output circuit and so detection is not performed during power interruptions.
3. If power supply (terminal 3) is in the open state, the SSR will still turn ON and OFF in the same way but the failure detection function and
alarm display will not operate properly.
Connection Diagrams (Main Circuit)
The following diagrams show the applicable load connection configurations for SSR failure detection.
Single Phase
3-phase Star
Connection
G3PC
G3PC
3-phase Delta
Connection (3-phase,
2-wire Switching)
G3PC
G3PC
G3PC
G3PC
3-phase V
Connection
G3PC
G3PC
Heater
er
at
er
He
at
He
er
at
He
er
er
er
at
at
at
He
He
He
Heater
Heater
SSR
Note: With 3-phase connection, so that the power supply voltage is applied between the G3PC’s terminals 1/L1 and 3, connect the desired phase
to terminal 3.
Timing Chart
SSR failure detection
SSR ON normally
Main circuit power
supply (load side)
SSR OFF normally
SSR short-circuit
Reset (See note.)
SSR open-circuit
Circuit disconnection detection on the load side
Reset (See note.)
Load circuit disconnection
Reset (See note.)
Operating input
(between terminals
A1 and A2)
Input LED
(yellow)
Load current
RDY/ALM LED
(Green:
; Red:
)
Alarm output
(between terminals
X1 and X2)
Note: After failure detection, if the detection conditions differ to the conditions given under Conditions for SSR Failure Detection, alarm output is
reset.
SSR with Failure Detection Function
G3PC
J-73
Dimensions
G3PC-220B-VD
Mounting Holes
22.5 max.
Tow, 4.6 dia.
130 max.
1
Terminal cover
114.4
Three, 4.5 dia. or M4
13.5
68
100 max.
90±0.2 80
8.5x3
90±0.3
4.6x5.6 elliptic hole
Note The above diagram
is for when the terminal cover is open.
84.2
13±0.3
Note The above diagram
is for when the terminal cover is closed.
Accessories (Order Separately)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
35±0.3
25
25
15 25 10 25
1,000(500)
(500) 10
1,000
(seenote)
note)
(see
27±0.15
15 (5)
(see note)
4.5
35±0.3 27 24
15 25
Note Values in parentheses indicate dimensions for the
PFP-50N.
J-74
SSR with Failure Detection Function G3PC
10
25
25
1,000
10
25 15
1
29.2
1.5
Installation
■ External Specifications
Appearance
Terminal Arrangement
Terminal name
Terminal number
Main circuit terminals 1/L1, 2/T1
(output)
1/L1
Screw size
M4
3
RDY/ALM
Detection power sup- 3
ply terminal (input)
A1(IN+)
Operating circuit terminals (input)
A1, A2
Alarm output terminals (output)
X1, X2
INPUT
A2(IN−)
M3.5
X1(ALM+)
X2(ALM−)
2/T1
Indicators
Name
Status indicators
Input indicator
Symbol
Color
Meaning
RDY
Green
SSR normal
ALM
Red
SSR failure detection
and circuit disconnection detection
INPUT
Yellow
Operating
Note: The same indicator is used as both the power supply indicator
and the alarm indicator.
■ Connection Example
(See note 1.)
Display Labels
L1
1
AC
3
Voltage output for Temperature
Controller, sequencer
A1
12 to 24
VDC
IN
A2
X1
Input for Temperature
Controller, sequencer
ALM
X2
30 VDC
min.
2
T1
(See note 2.)
SSR with Failure Detection Function
G3PC
J-75
SSR
Heater
Note: 1. If the detection power supply terminal (terminal 3) is not connected, failure detection is not performed and so be sure to connect this
terminal.
2. If the load is connected to terminal 1/L1, failure detection may not operate correctly and so connect the load to terminal 2/T1.
3. With inductive loads (relay coil, etc.), connect back-current prevention diodes to both sides of the load.
Precautions
Refer to the Technical Information for SSRs (Cat. No. J137) for general precautions.
Wiring
• When using crimp terminals, observe the terminal clearances
shown below.
■ Correct Use
Main Circuit Power Supply Operating Input/Alarm Output
(Terminals 1 to 3)
(Terminals A1, A2, X1, and X2)
Before Actual Operation
10
1. In actual operation, the G3PC may cause accidents that were
unforeseeable at the theoretical stage. Therefore it is necessary
to test the G3PC under a variety of conditions that are possible.
As for the characteristics of the G3PC, it is necessary to consider
the differences between G3PC Units.
2. The ratings in this datasheet are for testing in a temperature
range of 15 to 30°C, a relative humidity range of 25% to 85%, and
an atmospheric pressure range of 88 to 106 kPa. When testing
operation, it is necessary to confirm correct operation not only
with the actual load that will be used, but also at the same ambient conditions as for actual operation.
Mounting Method
7.0
12.4
10
M3.5
• Be sure that all lead wires are of a thickness appropriate for the
current.
• The output terminals are charged, and touching them may result in
electric shock, even when the G3PC is OFF. Separate the outputs
from the power supply by installing a circuit-breaker at a higher
level in the circuit.
Tightening Torque
DIN Track Mounting
When mounting to a DIN track, mount the G3PC until it clicks into
place, otherwise it become loose during use and fall. Fix both ends
with end plates.
Panel Mounting
When mounting directly to a panel, observe the following conditions:
Screw diameter: M4
Tightening torque: 0.98 to 1.47 N·m
Terminal number
Screw terminal
diameter
Tightening torque
A1, A2, X1, X2
M3.5
0.59 to 1.18 N·m
1/L1, 2/T1, 3
M4
0.98 to 1.47 N·m
Horizontal Mounting
Vertical direction
Vertical Mounting
Be sure to tighten the screws to the specified torques given below.
Not doing so may result in malfunction.
Panel
Panel
Note: Use the G3PC at a load current of 50% of the rated load current
when it is mounted horizontally.
Side-by-side Mounting
Wiring duct
5 mm
80 mm min.
Wiring duct
80 mm min.
Note: Use the G3PC at a load current of 80% of the rated load current
when it is mounted side-by-side.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J127-E1-02
J-76
In the interest of product improvement, specifications are subject to change without notice.
SSR with Failure Detection Function G3PC