Axial Lead and Cartridge Fuses Designed to IEC Standard RoHS Pb 5 x 20 mm Fast-Acting Fuse 216 Series ® ® • Designed to International (IEC) Standards for use globally. • Meets the IEC 60127-2, Sheet 1 specification for Fast Acting Fuses. • Available in Cartridge and Axial Lead Form. • Available in ratings of 0.050 to 10 amperes. • High breaking capacity. • RoHS compliant and Lead-Free version available, add XP suffix to standard catalog number ELECTRICAL CHARACTERISTICS: 150% 210% Ampere Rating .05 – 6.3 8-10 Opening Time 60 minutes, Minimum 30 minutes, Minimum .05 – 10 30 minutes, Maximum .05 – 4 5– 6.3 8-10 .05 – 6.3 8-10 .05 – 6.3 8-10 275% 400% 1000% 0.01 sec., Min.; 2 sec. Max. 0.01 sec., Min.; 3 sec. Max. 0.04 sec., Min.; 20 sec. Max. .003 sec., Min.; 0.3 sec. Max. .01 sec., Min.; 1.0 sec. Max. .02 seconds, Maximum .03 seconds, Maximum INTERRUPTING RATING: 1500 amperes @ 250 VAC, 0.7-0.8 power factor. RoHS compliant and Lead-Free version available, add XP suffix to standard catalog number Ampere Rating .050 .063 .080 .100 .125 .160 .200 .250 .315 .400 .500 .630 .800 1 1.25 1.6 2 2.5 3.15 4 5 6.3 8* 10* cycles –65°C to +125°C) Vibration: MIL-STD-202F Method 201A Humidity: MIL-STD-202F Method 103B, Test Condition A. high relative humidity (95%) and elevated temperature (40°C) for 240 hours. Salt Spray: MIL-STD-202F Method 101D, Test Condition B PHYSICAL SPECIFICATIONS: Material: Body: Ceramic ORDERING INFORMATION: Cartridge Catalog Number 216.050 216.063 216.080 216.100 216.125 216.160 216.200 216.250 216.315 216.400 216.500 216.630 216.800 216 001 216 1.25 216 01.6 216 002 216 02.5 216 3.15 216 004 216 005 216 06.3 216 008 216 010 ENVIRONMENTAL SPECIFICATIONS: Operating temperature: -55˚C to 125˚C Thermal Shock: MIL-STD-202F Method 107G, Test Condition B: (5 Voltage Rating 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 250 Nominal Resistance Cold Ohms 15.90 10.45 7.89 5.42 3.68 5.20 3.35 2.35 1.85 1.67 1.20 0.790 0.588 0.228 0.153 0.108 0.0770 0.0575 0.0333 0.0243 0.0168 0.0125 0.0120 0.00775 Nominal Melting I2t A2 Sec. 0.00019 0.00055 0.00086 0.0033 0.0056 0.0018 0.0045 0.0092 0.015 0.028 0.045 0.097 0.18 0.19 0.49 1.04 1.92 2.77 7.85 15.4 28.2 57.9 66.1 158.5 Cap: Nickel Plated Brass Leads: Tin Plated Copper Filler Sand (160mA – 10A) Terminal Strength: MIL-STD-202F Method 211A, Test Condition A Solderability: Reference IEC 60127 Second Edition 2003-01 Annex A Product Marking: Cap 1: current and voltage rating. Cap 2: Agency approval markings. Packaging: Available in Bulk (v=5, H=100, M=1000 pcs/pkg) or on Tape/Reel (MRET1=1000 pcs/reel). w w w. l i t t e l f u s e . c o m 11 AXIAL LEAD AND CARTRIDGE FUSES % of Ampere Rating 415 Axial Lead and Cartridge Fuses Designed to IEC Standard RoHS 5 x 20 mm Fast-Acting Fuse 216 Series Pb ® ® Agency Approvals Agency Approvals Certificate No. Ampere Range Cartridge NBK250702-E10480 NBK250702-E10480 Leaded NBK250702-E10480 NBK250702-E10480 Certificate No. Certificate No. A&C E 5.2+0.1 -0.2 1A – 10A 5.1+0.6 B&D F 2003010207079960 2002010207007594 50mA – 800mA 1A – 6.3A SU05001-2013 1A – 10A 0216.050 XE1 to 0216.100 XE1 40 5.1+0.6 22.5 MAX 6.0 MAX 0.65 Recognised File No. E10480 Guide No. JDYX2 ® ® File No. Acc. Class No. 029862 LR1422-30 Licence No. KM41462 File No. 9848103, 9931059 304518 & 304555 50mA – 10A 0216001.XE1 to 0216010.XE1 1A – 6.3A 32mA – 6.3A 50mA – 10A Notes: * Ratings above 6.3A have 0.8 mm dia lead 1 For RoHS compliant parts replace XE with XEP 2 For RoHS compliant parts add suffix 'XP' 10000 1000 100 10 1 0.1 0.01 0.001 0.01 0.1 1 10 100 1000 CURRENT IN AMPERES 416 40 22.5 MAX 0.65* All dimensions in mm 0.050A 0.063A 0.080A 0.100A 0.125A 0.160A 0.200A 0.250A 0.315A 0.400A 0.500A 0.630A 0.800A 1A 1.25A 1.6A 2A 2.5A 3.15A 4A 5A 6.3A 8A 10A Average Time Current Curves TIME IN SECONDS 20+0.5 0216 0002 w w w. l i t t e l f u s e . c o m 5.8 MAX