ETC 235.1

AXIAL LEAD AND CARTRIDGE FUSES
DESIGNED TO MEET UL/CSA STANDARDS
5 x 20 mm Fast-Acting Type
U® L
1
®
• Designed to UL/CSA/ANCE 248 Standard.
• Available in Cartridge and Axial Lead Format.
• Available in ratings of 0.100 to 6 amperes.
ELECTRICAL CHARACTERISTICS:
% of Ampere
Rating
110%
135%
200%
Opening
Time
4 hours, Minimum
1 hour, Maximum
1 second, Maximum
AGENCY APPROVALS: Listed by Underwriters
Laboratories and Certified by CSA. Approved by MITI from
1 through 5 amperes.
ORDERING INFORMATION:
Nominal
Resistance
Cold Ohms
8.40
5.75
3.15
2.25
1.60
1.08
0.455
0.318
0.263
0.195
0.153
0.106
0.0775
0.0600
0.0438
0.0348
0.0248
0.0185
0.0150
Nominal
Melting I2t
A2 Sec.
0.00160
0.00280
0.00890
0.0170
0.0330
0.0600
0.0710
0.115
0.160
0.260
0.480
1.12
2.08
2.72
5.59
8.62
17.60
28.15
48.60
235 000 Series
236 000 Series
.635
(.025")
5
(.197")
20
(.787")
5.25
(.207")
20.24
(.797")
40
(1.58")
Average Time Current Curves
.100A
.125A
.200A
.250A
.300A
.400A
.500A
.600A
.700A
.800A
1A
1.25A
1.6A
2A
2.5A
3A
4A
5A
6A
Axial Lead
Catalog
Ampere Voltage
Number
Rating Rating
236.100
.100
250
236.125
.125
250
236.200
.200
250
236.250
.250
250
236.300
.300
250
236.400
.400
250
236.500
.500
250
236.600
.600
250
236.700
.700
250
236.800
.800
250
236 001
1
250
236 1.25
1.25
250
236 01.6
1.6
250
236 002
2
250
236 02.5
2.5
250
236 003
3
250
236 004
4
125
236 005
5
125
236 006
6
125
10000
1000
100
TIME IN SECONDS
Cartridge
Catalog
Number
235.100
235.125
235.200
235.250
235.300
235.400
235.500
235.600
235.700
235.800
235 001
235 1.25
235 01.6
235 002
235 02.5
235 003
235 004
235 005
235 006
10
1
0.1
0.01
0.001
0.1
1
10
CURRENT IN AMPERES
100
1000