SYSTEMSENSOR 2551HR

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2551HR Plug-in Intelligent
Photoelectronic Sensors
with Communications
Specifications
Diameter:
Height:
Weight:
Installation Temperature Range
Installation Humidity Range:
Mounting:
Maximum Air Velocity:
Voltage Range:
Standby Current:
LED Current:
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
6.1 inches (15.5 cm) installed in B501B
4.0 inches (10.2 cm) installed in B501
3.2 inches (8.1 cm)
Add 0.5 inches (1.3 cm) for thermal models
9.6 ounces (272 g)
2551: 32° to 120° F (0° to 49° C)
2551T: 32° to 100° F (0° to 38° C)
10% to 93% Relative Humidity
B501B flanged base
B501 flangeless base
B501 with RMK400 recessed mounting kit
3000 Ft./Min. (15 m/S)
15 to 32 Volts DC Peak
230 µA @ 24 VDC
6.5 mA @ 24 VDC
capability is available as an optional accessory (part no.
RA400Z).
Before Installing
Please thoroughly read the system wiring and installation
manual, which provides detailed information on sensor
spacing, placement, zoning, and special applications. Copies of these manuals are available from System Sensor.
Wiring Guide
Refer to the installation instructions for the particular plugin base being used: 1) for the B501B base (D550-01-01); 2)
for the B501 base (D550-02-00); 3) for the RMK400 used
with the B501 base (D450-07-00). Bases are provided with
screw terminals for power, ground, and remote annunciator
connections (see Figure 1).
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: These detectors must be tested and maintained regularly following NFPA 72 requirements. These
detectors should be cleaned at least once a year.
NOTE: All wiring must conform to applicable local codes,
ordinances, and regulations.
General Description
The model 2551HR photoelectronic sensors utilize a stateof-the-art, optical sensing chamber. These sensors are designed for use with duct housings DH500 and DH500AC/
DC only, and to be used with compatible control panels
only. Connect detectors only to compatible control units.
(For installation in Canada, refer to CAN/ULC-S524-M86,
Standard for the Installation of Fire Alarm Systems and CEC
Part 1, Sec. 32.)
NOTE: Verify that all sensor bases are installed and that
the wiring polarity is correct at each base.
WARNING
Remove power from the loop before installing sensors.
1. Install sensors:
a. Verify that the sensor type matches the type written
on the label on the base.
b. Set the sensor to a desired address and then write the
address on the label on the base.
c. Place the sensor into the sensor base.
Two LEDs on each sensor light to provide a local 360° visibility of the sensor indication. The LEDs can be latched
ON by code command from the panel for an alarm indication. The LEDs can also be unlatched to the normal condition by code command. Remote LED annunciator
D500-41-00
1
I56-1437-00
Figure 1. Wiring Diagram:
REMOTE ANNUNCIATOR
+
-
CAUTION: Do not loop wire under terminal 1 or 2.
Break wire run to provide supervision of connections.
U.L. LISTED COMPATIBLE
CONTROL PANEL
+
3
2
3
2
3
1
1
1
2
+
CLASS A OPTIONAL WIRING
A78-1253-01
d. Turn the sensor clockwise until it drops into place.
e. Continue turning the sensor clockwise until it locks
into place.
Testing
Before testing, notify the proper authorities that the smoke
sensor system is undergoing maintenance, and therefore
the system will temporarily be out of service. Disable the
zone or system undergoing maintenance to prevent unwanted alarms.
Sensors must be tested after installation and periodic maintenance. The sensor may be tested in the following ways:
WARNING
Sensor will not detect smoke if dust cover is installed.
2. Tamper-proof feature:
The sensor bases include a tamper-proof feature that,
when activated, prevents removal of the sensor without
the use of a tool. See the installation instruction manual
for the sensor base for details in using this feature.
A. Test Magnet (Model No. M02-04-00)
1. Place the magnet against the cover opposite the test
module socket to activate the test feature (see Figure 2).
2. The LEDs should latch on within 10 seconds indicating alarm and annunciating the panel.
3. After all sensors have been installed, apply power to the
control unit.
B. Test Module (Model No. MOD400R)
The MOD400R is used with your DMM or voltmeter to
check the sensor sensitivity as described in the
MOD400R’s manual.
4. Test all sensors per the TESTING section of this manual.
Figure 2. Views showing position of test magnet (model 2551HR shown):
LED
TEST
MAGNET
TEST MODULE
SOCKET
PAINTED
SURFACE
TEST
MAGNET
A78-1410-02
LED
D500-41-00
2
I56-1437-00
NOTE: If the sensor’s sensitivity limits or the MOD400R
limits do not appear on the back of the sensor, the
MOD400R is not suitable for field sensitivity testing of that unit.
After testing, detectors must be reset from the control
panel. Notify the proper authorities that the system is back
on line.
Sensors that fail these tests should be cleaned as described
under CLEANING and retested. If the sensors still fail these
tests they should be returned for repair.
C. Smoke Entry Test per NFPA 72
The field test tool is the Gemini Model 501 aerosol generator. Set the generator to represent 4%/ft to 5%/ft obscuration as described in the Gemini 501 manual. Using
the bowl shaped applicator, apply aerosol until unit
alarms. If the Gemini unit is not available, a punk, cotton wick, or cigarette are acceptable means of generating
smoke to test all System Sensor ionization and photoelectronic sensors.
CAUTION
Dust cover is not a substitute for removing sensor during
new construction or heavy remodeling. Cover only helps
limit dust entry.
Cleaning the Sensor
NOTE: Before cleaning, notify the proper authorities that
the smoke sensor system is undergoing maintenance and will temporarily be out of service. Disable the loop or system undergoing maintenance to
prevent unwanted alarms.
NOTE: This test only verifies proper operation of the sensor and is not used to test sensitivity.
Figure 3:
It is recommended that the sensor be removed from its
mounting base to facilitate easier cleaning (see Figure 3).
The sensor is cleaned as follows:
1. Remove the sensor cover by placing a small bladed
screwdriver in the side slot of the sensor cover, twisting
it slightly until the cover can be turned counterclockwise
for removal.
2. Vacuum the screen carefully without removing it. If further cleaning is required continue with Step 3, otherwise
skip to Step 6.
3. Remove the screen by pulling it straight out. Vacuum the
inside.
4. Clean the vaned chamber piece by vacuuming or blowing out dust and particles.
5. To replace the screen, orient it so that the arrow on top
aligns with the field test slot on the base of the detector.
Carefully push the screen onto the base making sure it
fits tightly to the chamber.
6. Replace the cover by gently rotating it clockwise until it
locks in place.
REMOVABLE COVER
TEST SLOT
REMOVABLE SCREEN
P/N RS24 (W/O THERMAL)
RS24T (W/THERMAL
A78-1941-01
D500-41-00
3
I56-1437-00
WARNING
The Limitations of Property Protection Smoke Detectors
smoldering type. This is to ensure that both can detect a wide range of
types of fires. Ionization detectors offer a broad range of fire sensing capability but they are somewhat better at detecting fast flaming fires than
slow smoldering fires. Photoelectric detectors sense smoldering fires better
than flaming fires which have little, if any, visible smoke. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always
provide early warning of a specific type of fire.
This smoke detector is designed to activate and initiate emergency action, but will do so only when it is used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72.
Smoke detectors will not work without power. AC or DC powered
smoke detectors will not work if the power supply is cut off.
Smoke detectors will not sense fires which start where smoke does not
reach the detectors. Smoldering fires typically do not generate a lot of
heat which is needed to drive the smoke up to the ceiling where the
smoke detector is usually located. For this reason, there may be large delays in detecting a smoldering fire with either an ionization type detector
or a photoelectric type detector. Either one of them may alarm only after
flaming has initiated which will generate the heat needed to drive the
smoke to the ceiling.
In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gases which ignite, improper storage of flammable liquids like
cleaning solvents which ignite, other similar safety hazards, arson, smoking in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges. Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent maintenance.
Smoke from fires in chimneys, in walls, on roofs or on the other side of a
closed door(s) may not reach the smoke detector and alarm it. A detector
cannot detect a fire developing on another level of a building quickly or at
all. For these reasons, detectors shall be located on every level and in
every bedroom within a building.
Smoke detectors cannot last forever. Smoke detectors contain electronic
parts. Even though smoke detectors are made to last over 10 years, any
part can fail at any time. Therefore, smoke detectors shall be replaced after
being in service for 10 years. The smoke detector system that this detector
is used in must be tested regularly per NFPA 72. This smoke detector
should be cleaned regularly per NFPA 72 or at least once a year.
Smoke detectors have sensing limitations, too. Ionization detectors and
photoelectric detectors are required to pass fire tests of the flaming and
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair DepartD500-41-00
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.