BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters FEATURES · 0...100 mbar to 0...10 bar, 0...2 to 0...150 psi gage or absolute · For corrosive media · 0...10 V, 1...6 V, 0...20 mA or 4...20 mA output · Field interchangeable · For harsh environments MEDIA COMPATIBILITY Wetted materials: stainless steel 1.4404 (316L), PVC, PUR, NBR11 Housing: protection class IP 68 (according to DIN EN 60529) respectively NEMA 6P1 ELECTRICAL CONNECTION 0...10 V, 1...6 V output sensor SPECIFICATIONS9,10 Maximum ratings Supply voltage (reverse polarity protection) 13...30 V BTE(M)/PTU6...0..., 1... 12...36 V BTE(M)/PTU6...4..., 5...2 Maximum load current BTE(M)/PTU6...0..., 1... Temperature limits Storage Operating Compensated Vibration (5 to 500 Hz) Mechanical shock Proof pressure3 August 2008 / 104 V GND 0...20 mA output 10 mA +Vs red Iout blue -Vs black 12 to 36 V RL 4...20 mA output 10 gRMS sensor V GND bare -40 to 85°C -25 to 85°C 0 to 70°C 2 x rated pressure 13 to 30 V bare sensor 50 g +Vs red Vout yellow -Vs black +Vs red 12 to 36 V V -Vs black RL GND bare 1/6 www.sensortechnics.com BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters COMMON PERFORMANCE CHARACTERISTICS1 Characteristics Operating pressure 4 Thermal effects (0 to 70°C) (-25 to 0°C, 70 to 85°C) Min. Typ. BTEM6100... 0 100 BTEM6250... 0 250 BTEM6350... 0 350 BTEM6500... 0 500 BTE6001... 0 1 BTE6002... 0 2 BTE6005... 0 5 BTE6010... 0 10 PTU6002... 0 2 PTU6003... 0 3 PTU6005... 0 5 PTU6010... 0 10 PTU6015... 0 15 PTU6030... 0 30 PTU6050... 0 50 PTU6100... 0 100 PTU6150... 0 150 Offset 0.02 0.04 Span 0.02 0.04 Offset 0.03 Span 0.03 5 Non-linearity and hysteresis (BSL) ±0.1 Repeatability ±0.1 6 Long term stability ±0.2 Output noise (0 < f < 1 kHz) ±0.04 Response time (10 to 90 %) 1 Power supply rejection August 2008 / 104 Max. Offset 0.05 Span 0.05 Unit mbar bar p si %FSO/°C 0.25 %FSO ms %FSO/V 2/6 www.sensortechnics.com BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters INDIVIDUAL PERFORMANCE CHARACTERISTICS1 0...10 V output (VS = 15 V, RL > 100 kΩ, tamb = 25°C) Characteristics Zero pressure offset Min. Typ. Max. -0.15 0 0.15 9.9 10.0 10.1 7 Full scale span Output impedance 50 Power consumption (no load) 100 Unit V Ω mW 1...6 V output (VS = 15 V, RL > 100 kΩ, tamb = 25°C) Characteristics Min. Typ. Max. Zero pressure offset 0.85 1.0 1.15 Full scale span7 4.9 5.0 5.1 Full scale output Unit V 6.0 Output impedance 50 Power consumption (no load) 100 Ω mW 4...20 mA output (VS = 15 V, RL > 100 Ω, tamb = 25°C) Characteristics Zero pressure offset 7 Full scale span Min. Typ. Max. 3.85 4.0 4.15 15.9 16.0 16.1 Unit mA Output impedance 0.1 Ω Power consumption (IL = 20 mA) 260 mW 0...20 mA output (VS = 15 V, RL > 100 Ω, tamb = 25°C) Characteristics Zero pressure offset 7 Full scale span Min. Typ. Max. -0.15 0 0.15 19.9 20.0 20.1 Unit mA Output impedance 0.1 Ω Power consumption (IL = 20 mA) 260 mW August 2008 / 104 3/6 www.sensortechnics.com BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters ELECTROMAGNETIC CAPABILITY8 Test conditions Criterion Interference Grade 3 10 V/m, 80 MHz to 1000 MHz 80 % AMC (1 kHz) A <1 % FSO Radiated, radio frequency electromagnetic field immunity (RFI) EN61000-4-3: Electrical fast transient / burst immunity (EFT) EN61000-4-4: Grade 3 ±2 kV B <1 % FSO Electrostatic discharge immunity test (ESD) EN61000-4-2: Grade 4 ±8 kV, contact discharge B <1 % FSO Immunity to conducted disturbances induced by radio-frequency fields EN61000-4-6: Grade 3 0,15 to 80 MHz 10 V, 80 % AMC (1 kHz) A <1 % FSO Specification notes (for all devices): The package is a all-sealed housing. Gage devices are vented through an integral PE tube of the connecting cable. The minimum supply voltage is directly proportional to the load resistance seen by the transmitter. For more details see the load limitation diagrams. 3. Proof pressure is the maximum pressure which may be applied without causing damage to the sensing element. 4. Thermal effects tested and guaranteed from 0 to 70°C relative to 25°C. All specifications shown are relative to 25°C. 5. Non-linearity refers to the Best Straight Line fit measured for offset, full scale span and 1/2 full scale span. 6. Long term stability is the change in output after one year or 1 million pressure cycles. 7. Span is the arithmetic difference in transmitter output signal measured at zero pressure and the maximum operating pressure. 8. Test are in accordance with EN61000-6-2, April 1999. 9. CE-labelling is in accordance with 89/336/EEC. 10. The pressure transmitters must not be used as safety accessories according to article 1, 2.1.3 of the directive 97/23/EC. 11. Other sealing materials are available on request. 1. 2. August 2008 / 104 4/6 www.sensortechnics.com BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters OUTPUT CHARACTERISTICS Voltage output versions Current output versions Vout 10 V 9 lout 20 mA 18 8 16 7 14 6 12 BTE(M)/PTU6...0... 5 BTE(M)/PTU6...4... BTE(M)/PTU6...5... 10 4 8 BTE(M)/PTU6...1... 3 6 2 4 1 2 0 20 40 60 80 100 % operating pressure 0 20 40 60 80 100 % operating pressure LOAD LIMITATION 0...20 mA output version 4...20 mA ouput version 1400 Ohm 1200 1000 800 600 operating range 400 200 0 5 10 15 20 25 30 35 V supply voltage August 2008 / 104 5/6 www.sensortechnics.com BTE6000 / PTU6000...CS Series Submersible precision stainless steel transmitters OUTLINE DRAWING NOM 151 (5.95) NOM 70 (2.76) NOM 2000 (78.74) Ø 27 (1.06) Ø 24 (0.95) other cable lengths on request Hydrophobic filter (incl. in delivery) mass: typ. 350 g (without cable) dimensions in mm (inches) ORDERING INFORMATION BTE/PTU M 6xxx x x C x S calibration submersible BTE: calibration in bar PTU: calibration in psi cable length in m mbar-ranges cable version pressure range output signal 100: 250: 350: 500: 001: 002: 005: 010: 0...100 0...250 0...350 0...500 mbar mbar mbar mbar 0...1 bar 0...2 bar 0...5 bar 0...10 bar Note: 002: 0...2 psi 003: 0...3 psi 005: 0...5 psi 010: 0...10 psi 015: 0...15 psi 030: 0...30 psi 050: 0...50 psi 100: 0...100 psi 150: 0...150 psi 0: 1: 4: 5: 0...10 V 1...6 V 4...20 mA 0...20 mA pressure mode G: gage pressure A: absolute pressure (available for pressure ranges from 1 bar/15 psi absolute upwards only!) Other pressure ranges and options are widely available. Please contact your nearest Sensortechnics sales representative. Sensortechnics reserves the right to make changes to any products herein. Sensortechnics does not assume any liability arising out of the application or use of any product or circuit described herein, neither does it convey any license under its patent rights nor the rights of others. August 2008 / 104 6/6 www.sensortechnics.com