OMRON S8PE

Three phase input switch mode Power Supply
S8PE
DIN-rail mounting, 3-phase input Switch
mode Power Supply with a range of 5A to
40A output current
• 3 phase 400/480 or 200/230 VAC input
• 5, 10, 20 and 40A; 24 VDC output
• Higher stability, lower ripple and noise level
• Compact and attractive design, easily mounted to DIN rail
(for 5, 10 and 20A types)
• Natural ventilation, no fan for less maintenance
• UL60950 (CSA22.2-60950), UL508 listing (CSA22.2-14) in addition to the CE mark
• Conform to EN61000-3-2
• All types can be used for parallel & serial operation
Ordering Information
■ S8PE
Input voltage
Power rating
400/480 VAC
3-phase
200/230 VAC
3-phase
Output voltage
Output current
With Front
mounting Bracket
With DIN rail
mounting Bracket
120 W
24 V
5A
–
240 W
24 V
10 A
–
S8PE-F12024CD
S8PE-F24024CD
480 W
24 V
20 A
S8PE-F48024C
S8PE-F48024CD
960 W
24 V
40 A
S8PE-F96024C
–
120 W
24 V
5A
–
S8PE-J12024CD
240 W
24 V
10 A
–
S8PE-J24024CD
480 W
24 V
20 A
–
S8PE-J48024CD
960 W
24 V
40 A
S8PE-J96024C
–
■ Model Number Legend
S8PE 1
2
3
4
3. Output Voltage
F: 400-480 VAC 3-phase
J: 200-230 VAC 3-phase
24: 24 V
2. Power Rating
4. Configuration
120:
240:
480:
960:
C: Covered type with Front-mounting bracket
CD: Covered type with DIN-rail track-mounting bracket
120 W
240 W
480 W
960 W
Power
Supplies
1. Input Voltage
Three phase input switch mode Power Supply
S8PE
L-99
Specifications
Item
Nominal Input Voltage
F: 400...480 VAC
J: 200...230 VAC
Nominal Output Current
5A
10 A
20 A
40 A
5A
10 A
20 A
40 A
Efficiency
(typical)
(Vin = 400 VAC, Pmax)
(Vin = 480 VAC, Pmax)
(Vin = 230 VAC, Pmax)
85%
84%
–
88%
88%
–
87%
87%
–
90%
90%
–
–
–
86%
–
–
88%
–
–
89%
–
–
91%
Input
Voltage range
340...766 VAC
180..264 VAC
Frequency
Current (max.)
(Vin = Range min., Pmax)
0.5 A
1.0 A
1.5 A
2.5 A
1.0 A
2.0 A
3.0 A
5.0 A
Power factor (typical)
(Vin = 400 VAC, Pmax)
(Vin = 480 VAC, Pmax)
(Vin = 230 VAC, Pmax)
0.58
0.52
–
0.64
0.59
–
0.89
0.84
–
0.89
0.84
–
–
–
0.55
–
–
0.55
–
–
0.9
–
–
0.89
Leakage current (max.)
(Vin = 400 VAC, Pmax)
(Vin = 480 VAC, Pmax)
(Vin = 230 VAC, Pmax)
0.4 mA
0.5 mA
–
0.9 mA
1.1 mA
–
1.3 mA
1.6 mA
–
0.7 mA
0.9 mA
–
–
–
0.3 mA
–
–
0.4 mA
–
–
0.7 mA
–
–
1.4 mA
30 A
30 A
40 A
50 A
35 A
35 A
75 A
75 A
Inrush current (max.)
(Pmax) (Note 1)
Output
50/60 Hz
Voltage adjustment range
22.5..26.4 VDC min.
± 0.5%
Tolerance adjustment accuracy
Ripple & noise (Pmax.)
200 mV max.
Load variation influence
± 2% max.
Input variation influence
± 0.5% max.
± 0.01%/°C
Temperature variation influence
Startup time (max.)
1.7 s
1.5 s
1.0 s
0.1 s
0.9 s
1.0 s
1.3 s
0.1 s
Hold time (min.)
(Vin = 200 VAC, Pmax)
(Vin = 400 VAC, Pmax)
(Vin = 480 VAC, Pmax)
(Vin = 230 VAC, Pmax)
–
21 ms
25 ms
–
–
17 ms
26 ms
–
–
11 ms
24 ms
–
–
14 ms
26 ms
–
10 ms
–
–
20 ms
4 ms
–
–
10 ms
4 ms
–
–
8 ms
5 ms
–
–
13 ms
2.65 kg
4.75 kg
Protection
Others
- Short circuit protection with automatic reset
- Over load protection
- Over voltage protection (Note 4)
Parallel operation
Yes (for two units)
Serial operation
Yes (for two units)
Indicator
Yes (Green LED)
Heat radiation
Natural air cooling
Ambient temperature (Note 2)
-10..60 °C (de-rating: 2%/°C for 50..60 °C)
Storage temperature
-25..85 °C
Ambient humidity
25..85%
Dielectric strength
500 VAC 50/60 Hz (Output - P.E.)
Comply to EN60950 F: 2.5 kVAC 50/60 Hz (Input - P.E.)
J: 1.5 kVAC 50/60 Hz (Input - P.E.)
500 M Ω min. at 500 VDC: P.E. - Output
Insulation resistance
EMC
EN55022 class A, EN55011 class A, EN50081-2
EN61000-6-2, EN61000-3-2 class A
Approved standards
IEC60950, EN60950, UL60950, CSA22.2-60950
UL508 (Listing), CSA22.2-14, EN50178, EN60204-1
Life expectancy (Note 3)
Weight
10 years (typical)
750 g
1.0 kg
2.65 kg
4.75 kg
750 g
Note 1. Measured at 25 °C, and cold start condition. (F: Vin = 480 VAC, J: Vin = 230 VAC, duration < 500 µs)
2. For UL and CSA, -105 to 50 °C (de-rating: 2%/°C for 40-50 °C only for 40 A model).
3. Under the ambient temperature of 40 °C, and a load rate of 50%.
4. Over voltage protection is provided for 5A, 10A and 20A models.
For 40A model, no overvoltage protection is provided.
L-100
Three phase input switch mode Power Supply S8PE
1.0 kg
Engineering Data
■ Definition of Inrush Current, Start up Time and Hold Time
Input OFF
Input ON
AC input
voltage
Inrush current input application
AC input
current
90%
Output
voltage
Start up time
96.5%
Hold time
■ Overload Protction
■ Overvoltage Protction
The Power supply is provided with an overload protec tion function
that protect the load and the power sup ply from possible damage by
over current. When the output current rises above between 105 to
130% of the rated current, the protection function is triggered,
decreasing the output voltage. When output current falls within the
rated range, the overload protection function is automatically cleared.
(except for 40 A model)
If output voltage exceed the rated voltage more than 20% (50% at
maximum) by some reason, then the output voltage will be turned
OFF automatically for safety. To restart the S8PE, turn OFF the input
voltage, wait for about one minute, then apply the input power again.
Load (%)
■ De-rating Curve
Ambient temperature (°C)
Power
Supplies
For UL and CSA the maximum temperature is 50% (with derating of
2%/°C from 40 °C to 50 °C, only for 40 A model)
Three phase input switch mode Power Supply
S8PE
L-101
Operation
■ Block Diagram
RFI filter
Input
Line Fuses
S8PE-F12024CD/J12024CD (5 A)
S8PE-F24024CD/J24024CD (10 A)
Control
Module
Opto-isolator
P.E.
Supply
Voltage
Control
And
Adjustment
Module
RFI filter
Input
Line Fuses
S8PE-F48024C (20 A)
S8PE-F48024CD/J48024CD (20 A)
P.E.
Control
Module
Opto-isolator
Driving
Output
Voltage
Control
Module
RFI filter
Input
Line Fuses
S8PE-F96024C/J96024C (40 A)
P.E.
Control
Module
L-102
Three phase input switch mode Power Supply S8PE
Opto-isolator
Driving
Output
Voltage
Control
Module
Dimensions and Installation
Note: All dimensions shown are in millimeters.
S8PE-F12024CD/J12024CD (5 A)
bottom view
side view
top view
front view
S8PE-F24024CD/J24024CD (10 A)
side view
top view
bottom view
front view
AC INPUT L1
⑥
Output Voltage adjustment trimmer V.ADJ
②
AC INPUT L2
⑦
DC OUTPUT -V
③
AC INPUT L3
⑧
DC OUTPUT +V
④
Protective Earth (P.E.)
⑨
35 mm DIN-rail attachment
⑤
DC OUTPUT indicator
Power
Supplies
①
Three phase input switch mode Power Supply
S8PE
L-103
S8PE-F48024C (20 A)
S8PE-F48024CD/J48024CD (20 A)
top view
side view
side view
front view
bottom view
S8PE-F96024C/J96024C (40 A)
front view
side view
top view
bottom view
L-104
①
AC INPUT L1
⑥
Output Voltage adjustment trimmer V.ADJ
②
AC INPUT L2
⑦
DC OUTPUT -V
③
AC INPUT L3
⑧
DC OUTPUT +V
④
Protective Earth (P.E.)
⑨
35 mm DIN-rail attachment for S8PEF48024CD/J48024CD type only
⑤
DC OUTPUT indicator
⑩
Fixing bracket for S8PE-F48024C type only
Three phase input switch mode Power Supply S8PE
Notice
Three phase input operation when one phase is missing
Serial Operation
The S8PE will in most cases continue to operate even after the loss
of one phase of the supply. The perfor mance specifications are of
course not guaranteed under these conditions. As the loss of one
phase puts additional stress on some components, the life span of
the unit could be shortened. It is prudent therefore to regularly check
for signs of the following possible conditions.
As shown below, the output voltage from each S8PE can be added.
Types must be the same.
+V
−V
Load
1. Input terminals wiring open/loose.
2. Incorrect / no voltage on one or more phases of the supply.
3. Abrupt or periodical loss of input voltage.
+V
Three phase input switch off
−V
Mounting
To improve and maintain the reliability of the Power Supply over a
long period, adequate consideration must be taken to heat radiation.
The S8PE is designed to radiate heat by natural air cooling, therefore, mount the S8PE so that enough air flow takes place around the
power supply.
Parallel Operation
As shown below, The Power supply can use for paral lel operation.
All the output voltage of each S8PEs should be exactly the same.
Also, make sure that the thickness and the length of all wires connected to the load are the same to ensure that the wires will have no
voltage drop difference. Types must be the same.
If installing S8PEs closely, keep the minimum dis tance of 10 cm at
50 °C ambient, 5 cm at 20 °C am bient.
+V
±) Output Voltage
Generating (±
−V
Load
In order to switch off the Power Supply completely: all 3 phases need
to be switched off.
An output of ± can be generated as shown below, since the S8PE
has a floating output.
+V
−V
−V
Load
+V
Load
+V
Power
Supplies
−V
Three phase input switch mode Power Supply
S8PE
L-105
Safety Precautions
■ Safety Signal words
This document uses the following signal words to mark safety precautions for the S8PE. These precautions pro vide important information for the
safe application of the product. You must be sure to follow the instructions pro vided with safety signal words.
!WARNING
Indicates information that, if ignored, could possibly result in loss of life or seriously injury.
Indicates information that, if ignored, could result in relatively serious or minor injury, damage to the product, or faulty
operation.
!Caution
!WARNING
!Caution
Be sure to connect the grounding line Not doing so may result in
electric shock.
Do not touch the S8PE while the power is being supplied or immediately after the power is turned OFF. Otherwise hot Switching
Power Supply.
!Caution
Do not attempt to disassemble the Power Supply or touch its internal parts while power is being supplied. Doing so may result in
electric shock.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. M044-E1-04
L-106
In the interest of product improvement, specifications are subject to change without notice.
Three phase input switch mode Power Supply S8PE