MEANWELL SC-150-13.5

150W Single Output Switching Power Supply
SC-150
series
Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage
Charger for lead-acid batteries
Built-in constant current limiting circuit
Built-in temperature compensation circuit
Alarm signal output
Fixed switching frequency at 25KHz
2 years warranty
SPECIFICATION
MODEL
SC-150-13.5
SC-150-27
DC VOLTAGE
13.5V
27V
54V
RATED CURRENT
11.2A
5.6A
2.8A
CURRENT RANGE
0 ~ 11.2A
0 ~ 5.6A
0 ~ 2.8A
RATED POWER
151.2W
151.2W
151.2W
240mVp-p
240mVp-p
RIPPLE & NOISE (max.) Note.2 180mVp-p
OUTPUT
INPUT
12 ~ 15V
24 ~ 30V
48 ~ 56V
VOLTAGE TOLERANCE Note.3
1.0%
1.0%
1.0%
LINE REGULATION
0.3%
0.2%
0.2%
LOAD REGULATION
0.3%
0.2%
0.2%
VOLTAGE ADJ. RANGE
SETUP, RISE TIME
100ms, 50ms at full load
HOLD UP TIME (Typ.)
24ms at full load
VOLTAGE RANGE
88 ~ 132VAC/176 ~ 264VAC selected by switch
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
83%
3.2A/115VAC
1.6A/230VAC
COLD START 35A
LEAKAGE CURRENT
<3.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
EMC
(Note 4)
OTHERS
86%
15.53 ~ 18.23V
86%
31.05 ~ 36.45V
62.1 ~ 72.9V
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
/ 70% RH
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
234.1K Hrs min. MIL-HDBK-217F (25
199*110*50mm (L*W*H)
0.8Kg; 16pcs/13.9Kg/0.95CUFT
DIMENSION
PACKING
NOTE
248 ~ 370VDC
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
PROTECTION
SAFETY &
SC-150-54
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:SC-150-SPEC 2010-10-18
SC-150
150W Single Output Switching Power Supply
Mechanical Specification
Case No. 906
series
Unit:mm
192
5
172
3.5
12
6
100
1
9.5
2
3
97
110
4
8.2
5
6
5-M3
37
7
199
6
6.5
3.5
50
3M3
20
Terminal Pin No. Assignment
20
12
24.5
3.5
Pin No.
1
2
3
4
25
16.5
190.5
Assignment Pin No.
Assignment
RTH(Thermistor)
5
AC/L
AC/N
6
DC OUTPUT -V
7
DC OUTPUT +V
FG
PSF(Power Supply Foult)
159
Block Diagram
230
115
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
fosc : 25KHz
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
O.C.P.
FG
O.V.P.
PWM
CONTROL
DRIVER
Static Characteristics (27V)
Derating Curve
OUTPUT VOLTAGE (V)
100
80
LOAD (%)
60
40
20
-10
-10
0
0
10
20
30
40
50
45
AMBIENT TEMPERATURE ( )
60
55
(VERTICAL)
(HORIZONTAL)
320
30
280
27
240
24
200
21
160
18
120
15
80
80
160
85
170
90
180
95
190
100
200
105
210
110
220
115
230
120
240
125
250
OUTPUT RIPPLE (mVp-p)
Ta=25
33
130
260
INPUT VOLTAGE (V)
File Name:SC-150-SPEC 2010-10-18