GAMEWELL-FCI XP95-T

XP95-T
Description
Analog Addressable Thermal Sensor
The Gamewell-FCI XP95-T Analog Addressable Thermal
Sensor operates with the Gamewell-FCI 600 Series analog
addressable fire alarm control panels (FACPs). The Series
XP95-T thermal sensor digitally transmits its address and
the chamber’s analog temperature value to the FACP for
analysis.
CS-2055ph1.wmf
Thermal sensors are readily distinguished from smoke by
the open webs in the housing designed to allow for free
movement of air around the exposed thermistor.
Operation
The XP95-T thermal sensor constantly monitors its sensing element as well as its internal electronics. The results
are digitally reported along with the unit’s address through
the integral communication electronics located in the sensor head. The thermal sensor monitors temperature by
using a single thermistor network which provides a voltage
output proportional to the external air temperature. This
signal is processed and conditioned by an on-board
advanced technology ASIC that digitally transmits the
ambient temperature data to the FACP when interrogated.
Trouble and Alarm conditions of the XP95 sensors are
determined at the FACP. The status information of each
sensor is analyzed for off–normal conditions by the control
panel. If the sensor reports a condition that matches its
programmed trouble signature, the FACP will report that
the sensor is in trouble and will follow its programmed
response sequence. Likewise, if the status reported
matches the alarm signature, the FACP will follow the programmed alarm response for the specific device in alarm.
When a sensor is in alarm, the integral LED in the sensor’s
housing will light continuously.
XP95-T
Features
•
•
•
•
•
•
•
•
•
•
The XP95-T thermal sensor is calibrated to return a normal
air temperature analog value to the FACP at 77º F. The
device connects to a two–wire loop circuit carrying both
data and a 117 to 28 VDC supply voltage, and is insensitive to loop connection polarity.
Compatible with the Gamewell-FCI 600 Series analog
addressable control panels
Fits 4.0" (10.16 cm) or 6.0" (15.24 cm) ultra low–profile,
and E-Z fit bases
Audible alarm sounder base
Address is stored in the sensor base
Address is set by XPert addressing card
Two-color status LED
Fixed point or rate-of-rise functions
Timed temperature increase causes an alarm
Thermal adjustability programming
Optional remote LED
An ISO 9000-2000 Company
SIGNALING
FM
S2527
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2055 Rev. a1 page 1 of 2
©2007 by Honeywell International Inc. All rights reserved.
Operation (Continued)
Ordering Information
A remote LED indicator can be connected. The device is
compatible with point or group–addressable relay and
sounder bases.
Engineer’s Specifications
The contractor shall furnish and install, where indicated on
the plans, electronic thermal sensors with one of the several addressable mounting base options available. The
combination sensor head and twist–lock mounting base
shall be UL Listed and UL Listed as compatible with the
Gamewell-FCI 600 Series analog addressable fire alarm
control panels.
The base shall permit free interchange of sensor heads
without requiring any additional wiring or additional programming of the head or base. The sensor shall contain an
integral LED that shall latch in when the unit goes into
alarm. It shall be the Gamewell-FCI model XP95-T.
Model
Description
XP95-T
Thermal sensor analog addressable
(55000-450)
XP95-B6EZ
6.0" (15.24 cm) ultra–low–profile EZ-Fit
mounting base with XPert card
(45681-250)
XP95-B4
4.0" (10.16 cm) mounting base with XPert
Addressing Card (45681-210)
XP95-B6R4
6.0" (15.24 cm) relay base (four-wire) with
XPert addressing card
XP95-B6SNDR 6.0" (15.24 cm) mounting base with XPert
addressing card and audible alarm
sounder
71112
Additional blank XPert addressing cards
30203
Remote LED (24 V)
Specifications
Standby Current:
Alarm LED Current:
Remote Alarm
Output:
Temperature Range:
Relative Humidity:
Recommended
Spacing:
Thermal Sensor
Performance
Features:
250 µA
4 mA
4 mA @ 5 VDC
-4°F to 154°F
(non-condensing) 0% to 95%
Smooth ceiling 60ft. (18.288 m) to
walls 25 ft. ( 7.62 m)
1) Thermal sensors have a thermal
adjustability programming range
from 25°C to 90°C
(77°F to 194°F) in 1°C
increments.
2) Thermal Sensors have a thermal
rate-of-rise feature. When
enabled in programming, should
the XP95-T sensor increase
temperature by greater than
15°F in less than one minute, an
alarm will be generated.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2055 Rev. a1 page 2 of 2
www.gamewell-fci.com