GAMEWELL-FCI ASD-PL2F

Velociti® Series
ASD-PL2F and
ASD-PTL2F
Description
Analog, Addressable Photoelectronic
Smoke Sensor
The Gamewell-FCI Velociti® Series, analog addressable plug-in smoke sensors with integral communication provide features that surpass conventional
sensors. Sensitivity can be programmed in the control panel software, and is continuously monitored
and reported to the panel. Point ID capability allows
each sensor’s address to be set, providing exact
locations for selective maintenance when the chamber contamination reaches an unacceptable level.
The ASD-PL2F photoelectric sensor’s unique optical
sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual
electronic thermistors add 135°F (57°C) fixed-temperature thermal sensing on the ASD-PTL2F model.
The Velociti® Series use a communication protocol
that substantially increases the speed of communication between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the panel’s
microprocessor stops the group poll and concentrates on the single device. The net effect is a
response speed up to five times greater than earlier
designs.
ASD-PTL2F
ASD-PL2F
Features
• Sleek, low-profile design
• Visual rotary, decimal switch addressing (01-159)
• Built-in functional test switch activated by an external
magnet
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm*
• Optional relay, isolator, or sounder bases
• Low standby current
• Analog addressable communication
• Stable communication technique with noise immunity
• Optional remote, single-gang LED Indicator (RA400Z)
Ordering Information
• Suitable for installation in ducts
• Compatible with Gamewell-FCI analog addressable
Model
Description
ASD-PL2F Analog, addressable photoelectronic
smoke sensor
ASD-PTL2F Analog, addressable photoelectronic smoke
sensor with thermal sensing
panels
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
An ISO 9001-2000 Company
SIGNALING
FM
Velociti® is a registered trademark of Honeywell International Inc.
®
UL is a registered trademark of Underwriters Laboratories Inc.
S1913
MEA
Approved
3023594 219-02-E Vol.VI 07272-0694:263
APPR OVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0617 Rev. E1 page 1 of 2
©2008 by Honeywell International Inc. All rights reserved.
Installation
Specifications
ASD-PL2F plug-in sensors use a separate base to
simplify installation, service, and maintenance. A
special tool allows maintenance personnel to plug-in
and remove sensors without using a ladder.
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
• 4.0" (10.2 cm) square box
• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box
2.1” (5.1 cm) high x 4.1” (10.4 cm)
diameter installed in B501 base, 6.1”
(15.5 cm) diameter installed in ADB-FL
base.
Shipping Weight: 5.2 oz. (147 g)
Operating
Temperature:
ASD-PL2F:
32° F to 120° F (0° C to 49° C)
ASD-PTL2F:
32° F to 100° F (0° C to 38° C)
Size:
UL®-Listed
Velocity Range:
• Single-gang box (except relay or isolator bases)
• With B501BH or B501BHT base, use a 4.0" (10.2 cm)
square box
0-4000 ft./min. (1,219.2 m/min.),
suitable for installation in ducts.
Relative
Humidity:
10-93% (non-condensing)
Thermal Ratings: Fixed-temperature setpoint
135° F (57° C)
• With B224RB or B224BI base, use a 3.5" (8.9 cm)
octagonal box, or a 4.0" (10.2 cm) octagonal or square
box
NOTE: Because of the inherent supervision provided
by the SLC, end-of-line resistors are not required.
Wiring “T-taps” or branches are permitted for Style 4
(Class “B”) wiring.
Sensor Spacing
Gamewell-FCI recommends spacing sensors in compliance with NFPA 72. In low airflow applications with
smooth ceilings, space sensors 30 feet (9.1 m). For
specific information regarding sensor spacing, placement and special applications, refer to NFPA 72.
Electrical Specifications
VoltageRange:
15 – 32 volts DC peak
Standby Current: (max. avg.): .0003 A @ 24 VDC
(one communication every 5
seconds with LED enabled)
Maximum Alarm
Current:
.0065 A @ 24 VDC (LED) lit).
Bases and Options
ADB-FL
B501
B501BH or
B501BHT
B224RB
Relay Base
RA400Z
BCK-200
GAMEWELL-FCI
6.1” (15.5 cm) diameter
4.1” (10.4 cm) diameter
Sounder base assembly (B501BHT
produces a temporal pattern).
Includes B501 base
Screw terminals:
Up to 14 AWG (2.0 mm2)
Relay type: Form-C
Rating:
2.0A @ 30 VDC resistive;
0.3 A @ 110 VDC inductive;
1.0 A @ 30 VDC inductive.
Dimensions:
6.2” x 1.2” (15.7 x 3.0 cm)
Maximum: 25 devices between
isolator bases.
Remote alarm indicator, LED.
Black detector covers (box of 10)
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0617 Rev. E page 2 of 2
www.gamewell-fci.com