SUPPLEMENT TO COMPATIBILITY ADDENDUM

SUPPLEMENT TO
COMPATIBILITY ADDENDUM
TO FCI
INSTALLATION/OPERATING MANUALS 9000-0427
1.0 Analog Sensors/Addressable Monitor Modules
The sensors, monitor modules and addressable stations listed in Tables 1 and 1A are compatible with the
signaling line circuits in the FCI, E3 Series™ Control Panel, Manual P/N 9000-0574. See Table 1B for a list
of compatible sensor bases. This includes the ILI-MB-E3 and ILI-S-E3.
Table 1 Approved Sensors
Model
Description
Supervisory Current
ASD-IL2F
Analog Ionization Sensor
.00030 A
ASD-PL2F
Analog Photoelectronic Sensor, Low Profile .00030 A
ASD-PTL2F
Analog PE Sensor, Low Profile w/thermal .00030 A
ASD-FILTREXF Analog Photo. Sensor for harsh environ- .00036 A
ments
ADPF
Analog Photo. Sensor, Duct mount
.00036 A
ADPRF
Analog PE Sensor, Duct mount, w/relays .00036 A
ABD-RT2F
Analog Beam Detector
.002 A
ABD-2F
Analog Beam Detector
.002 A
ATD-L2F/-RL2F Thermal Sensor, Low Profile
.00030 A
ATD-HL2F
Thermal Sensor, Low Profile
.00030 A
MCSAnalog Multi-Criteria Sensor
.00030 A
Acclimate2F
Table 1-A Approved Addressable Modules, Stations
Description
Supervisory Current
Addressable Monitor Module
.00040 A
Addressable Dual Monitor Module
.00075 A
Addressable Monitor Module
.00040 A
Addressable Sub-loop Module
.00030 A
Addressable Multiple Monitor Module
.00200 A
Addressable Multiple Monitor Module
.00350 A
Addressable Multiple Output Relay Control .00145 A
Module
MMO-6SF
Addressable Multiple Output Module
.00225 A
AOM-2RF
Addressable Output Relay Control Module .00030 A
AOM-2SF
Addressable Output Module
.00030 A
AOM-MUXF
Addressable Audio Evac. Module
.00035 A
AOM-TELF
Addressable Audio Evac. Module
.0024 A
M500X*
Fault Isolator Module
.00045 A
Addressable Manual Stations
MS-7AF
Addressable Manual Station
.00030 A
* Device Listed by System Sensor
Model
AMM-2F
AMM-2IF
AMM-4F
AMM-4SF
MMI-SF
MMI-10F
MMO-RF
FIRE CONTROL INSTRUMENTS
www.firecontrolinstruments.com
Alarm Current
.0065 A
.0065 A
.0065 A
.007 A
.0065 A
.0065 A
.0085 A
.0085 A
.0065 A
.0065 A
.0065 A
Alarm Current
.0006 A
.00475 A
.00575 A
.0054 A
.040 A
.055 A
.032 A
.035 A
.00030 A
.00030 A
.007 A
.0081 A
.005 A (isolated)
.0006 A
16 Southwest Park, Westwood, MA 02090 • Tel 781-471-3000 • Fax: 781-471-3099
Page 1 of 2
9020-0651 Rev. A
Table 1-B Sensor Bases
Supervisory Current
N/A
Model
Description
ADB-F, FL
Plug-in Base
ADB-FF, FLF
B501B, B210LP* Plug-in Base
B501BH/T*
Sounder base
B501*
Base
B224RB/B524RB* Relay Base
B224BI/B524BI*
Isolator Base for Style 7 Operation
ABD FILTREXF
Base for FILTREX sensor
*Devices Listed by System Sensor
N/A
N/A
N/A
.0005 A
.00045 A
N/A
FIRE CONTROL INSTRUMENTS
www.firecontrolinstruments.com
Alarm Current
N/A
N/A
N/A
N/A
.0005 A
.005 A (isolated)
N/A
16 Southwest Park, Westwood, MA 02090 • Tel 781-471-3000 • Fax: 781-471-3099
Page 2 of 2
9020-0651 Rev. A