SUPPLEMENT TO COMPATIBILITY ADDENDUM TO FCI INSTALLATION/OPERATING MANUALS 9000-0427 1.0 Analog Sensors/Addressable Monitor Modules The sensors, monitor modules and addressable stations listed in Tables 1 and 1A are compatible with the signaling line circuits in the FCI, E3 Series™ Control Panel, Manual P/N 9000-0574. See Table 1B for a list of compatible sensor bases. This includes the ILI-MB-E3 and ILI-S-E3. Table 1 Approved Sensors Model Description Supervisory Current ASD-IL2F Analog Ionization Sensor .00030 A ASD-PL2F Analog Photoelectronic Sensor, Low Profile .00030 A ASD-PTL2F Analog PE Sensor, Low Profile w/thermal .00030 A ASD-FILTREXF Analog Photo. Sensor for harsh environ- .00036 A ments ADPF Analog Photo. Sensor, Duct mount .00036 A ADPRF Analog PE Sensor, Duct mount, w/relays .00036 A ABD-RT2F Analog Beam Detector .002 A ABD-2F Analog Beam Detector .002 A ATD-L2F/-RL2F Thermal Sensor, Low Profile .00030 A ATD-HL2F Thermal Sensor, Low Profile .00030 A MCSAnalog Multi-Criteria Sensor .00030 A Acclimate2F Table 1-A Approved Addressable Modules, Stations Description Supervisory Current Addressable Monitor Module .00040 A Addressable Dual Monitor Module .00075 A Addressable Monitor Module .00040 A Addressable Sub-loop Module .00030 A Addressable Multiple Monitor Module .00200 A Addressable Multiple Monitor Module .00350 A Addressable Multiple Output Relay Control .00145 A Module MMO-6SF Addressable Multiple Output Module .00225 A AOM-2RF Addressable Output Relay Control Module .00030 A AOM-2SF Addressable Output Module .00030 A AOM-MUXF Addressable Audio Evac. Module .00035 A AOM-TELF Addressable Audio Evac. Module .0024 A M500X* Fault Isolator Module .00045 A Addressable Manual Stations MS-7AF Addressable Manual Station .00030 A * Device Listed by System Sensor Model AMM-2F AMM-2IF AMM-4F AMM-4SF MMI-SF MMI-10F MMO-RF FIRE CONTROL INSTRUMENTS www.firecontrolinstruments.com Alarm Current .0065 A .0065 A .0065 A .007 A .0065 A .0065 A .0085 A .0085 A .0065 A .0065 A .0065 A Alarm Current .0006 A .00475 A .00575 A .0054 A .040 A .055 A .032 A .035 A .00030 A .00030 A .007 A .0081 A .005 A (isolated) .0006 A 16 Southwest Park, Westwood, MA 02090 • Tel 781-471-3000 • Fax: 781-471-3099 Page 1 of 2 9020-0651 Rev. A Table 1-B Sensor Bases Supervisory Current N/A Model Description ADB-F, FL Plug-in Base ADB-FF, FLF B501B, B210LP* Plug-in Base B501BH/T* Sounder base B501* Base B224RB/B524RB* Relay Base B224BI/B524BI* Isolator Base for Style 7 Operation ABD FILTREXF Base for FILTREX sensor *Devices Listed by System Sensor N/A N/A N/A .0005 A .00045 A N/A FIRE CONTROL INSTRUMENTS www.firecontrolinstruments.com Alarm Current N/A N/A N/A N/A .0005 A .005 A (isolated) N/A 16 Southwest Park, Westwood, MA 02090 • Tel 781-471-3000 • Fax: 781-471-3099 Page 2 of 2 9020-0651 Rev. A