EPCOS B84142-A20-R

2-Line Filters
B84142-A*-R
for Converters and Power Electronics
Power line filters for single-phase systems
Rated voltage 250 V~, 50/60 Hz
Rated current 10 to 60 A
Construction
■ Two-line filter
■ Metal case
Features
■
■
■
■
■
High insertion loss
Easy to install
Degree of protection: IP 20 1)
Space-saving design
Design complies with
EN 133 200, UL 1283, CSA 22.2 No.8 1986
■ Optimized for long motor cables
and operation under full load
■ EN, UL and CSA approval pending
Applications
■ Frequency converters for motor drives, e.g.
– elevators
– conveyor systems
– pumps
– traction systems
– HVAC systems (heating, ventilation and air conditioning)
■ Power supplies
Terminals
■ Safe-to-touch terminal blocks
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current,
rated temperature, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
1) In accordance with IEC 60529: 1989; EN 60529: 1991; DIN VDE 0470-1
173 03/01
2-Line Filters
B84142-A*-R
for Converters and Power Electronics
Typical circuit diagram
LINE
LOAD
L
L’
N
N’
SSB1515-U
Technical data
Rated voltage V R
250 V~, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage VP
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
Leakage current Ileak
at 250 V~, 50 Hz
Climatic category
25/100/21 (– 25 °C/+ 100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
IR
A
Terminal
Ileak
cross section
mm2
mA
R typ
Ordering code
mΩ
Approx.
weight
kg
10
4
< 8
18
0,55
B84142-A10-R
20
4
< 8
10
1,0
B84142-A20-R
30
6
< 8
5
1,0
B84142-A30-R
40
6
< 17
3,6
1,0
B84142-A40-R
50
16
< 26
1,8
2,5
B84142-A50-R
60
16
< 26
1,4
2,5
B84142-A60-R
174 03/01
2-Line Filters
B84142-A*-R
for Converters and Power Electronics
Dimensional drawings
_ 0,6
44,5 +1
19
30
B84142-A10-R
7,5
0,8±0,1
Terminal blocks 44mm
mm2 2
Anschlussklemmen
50,8
70
101,6±0,3
Marking
LINE
LOAD
_ 0,5
60,4 +0,1
PE M4 x 15
ø4,7±0,1
133
154,8
SSB1522-C
B84142-A20-R
50,8±0,3
35±1
6,3
0,8±0,1
Terminal blocks
Anschluss4 mm2 4 mm 2
klemmen
LOAD
84
105
16±1
LINE
_ 0,5
95,2 +0,1
Marking
20
4,3±0,1
11
2
Terminal
blocks 4 4mm
Anschlussklemmen
mm 2
PE M5 x 20
24±1
35±1
99
24±1
_ 0,6
68 +1
121+1
SSB1523-K
175 03/01
2-Line Filters
B84142-A*-R
for Converters and Power Electronics
B84142-A30-R, B84142-A40-R
50,8±0,3
40±1
6,3
0,8±0,1
Terminal
blocks 6 mm²
20
84
16±1
LOAD
105
_ 0,5
95,2 +0,1
Marking
LINE
11
4,3±0,1
Terminal blocks 6 mm²
PE M5 x 20
24±1
99
40±1
24±1
_ 0,6
68 +1
130
SSB1524-T
17
42
1+0,1
60
B84142-A50-R, B84142-A60-R
13±1
36
85
180
115±0,2
100±0,3
Marking
115
Terminal blocks 16 mm²
Load
Line
6,6
PExM6
PE M6
25 × 25
245
176 03/01
SSB1525-2
2-Line Filters
B84142-A*-R
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84142-A10-R
B84142-A20-R
SSB1516-3
120
dB
αe
αe
100
100
90
90
80
80
70
70
60
60
50
50
40
40
30
30
20
20
10
10
0 4
10
10 5
10 6
10 7
SSB1517-B
120
dB
0 4
10
Hz 10 8
10 5
10 6
10 7
f
B84142-A30-R
B84142-A40-R
SSB1518-J
120
dB
αe
100
90
90
80
80
70
70
60
60
50
50
40
40
30
30
20
20
10
10
10 5
10 6
10 7
Hz 10 8
SSB1519-S
120
dB
αe
100
0 4
10
Hz 10 8
f
0 4
10
10 5
10 6
10 7
Hz 10 8
f
f
177 03/01
2-Line Filters
B84142-A*-R
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84142-A50-R
B84142-A60-R
SSB1520-V
120
dB
αe
αe
100
100
90
90
80
80
70
70
60
60
50
50
40
40
30
30
20
20
10
10
0 4
10
10 5
10 6
10 7
Hz 10 8
SSB1521-4
120
dB
0 4
10
f
10 5
10 6
10 7
Hz 10 8
f
178 03/01
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
 EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
 EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1