EPCOS B84143-A6-R206

3-Line Filters
B84143-A*-R206
for Converters and Power Electronics
Power line filters for three-phase systems
Rated voltage 480/275 V~, 50/60 Hz
Rated current 6 to 25 A
Construction
■ Three-line filter
■ Metal case
■ Footprint filter
Features
■
■
■
■
Low leakage current
Easy to install
UL approval
Optimized for long motor cables
and operation under full load
Applications
■ Frequency converters for motor drives, e.g.
–
–
–
–
elevators
pumps
conveyor systems
HVAC systems (heating, ventilation and air conditioning)
Terminals
■ Line: Safe-to-touch terminal blocks
■ Load: Litz wires
Marking
Marking on component:
Manufacturer’s logo, ordering code, rated current,
rated voltage, rated temperature, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Upon request the dimensions as well as the fixing points of the filters can be matched to
customer requirements.
The dimensions shown on the following pages are also available for 1-phase systems up to
22 A.
228 03/01
3-Line Filters
B84143-A*-R206
for Converters and Power Electronics
Typical circuit diagram
LINE
LOAD
L1
L1’
L2
L2’
L3
L3’
SSB1664-T
Technical data
Rated voltage V R
480/275 V~, 50/60 Hz
Rated current IR
Referred to 40 °C ambient temperature
Test voltage V P
1770 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability
1,5 · IR for 3 min per hour or
2,5 · IR for 30 s per hour
Leakage current I leak
at 480 V~, 50 Hz
Climatic category
25/100/21 (– 25 °C/100 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
Terminal
cross section
mm2
I leak
mA
6
2,5
< 3,5
12
2,5
< 3,5
25
4
<6
IR
A
Ordering code
mΩ
Approx.
weight
kg
72
0,8
B84143-A6-R206
21
1,5
B84143-A12-R206
2,3
B84143-A25-R206
Rtyp
8,5
229 03/01
3-Line Filters
B84143-A*-R206
for Converters and Power Electronics
Dimensional drawings
B84143-A6-R206
Terminal blocks
Anschlussklemmen
2,5 mm
mm2
2,5
43,5
174
Marking
LOAD
3
LINE
PE M4
240±10
200±10
4 × ø4,8
L1
L2
L3
59,6±0,2
73
56±0,4
PE
4 × Gewinde
M4
Thread M4
min.55mm
mmdeep
tief
min.
Litz Litze
wire
Wire
end ferrule
Aderendhülse
160±0,4
2 2
Terminal
blocks 2,5 2,5
mmmm
Anschlussklemmen
L1’
L2’
L3’
187±0,5
200
SSB1584-2
B84143-A12-R206
2 2
Terminal blocks 2,5
Anschlussklemmen
2,5mm
mm
43
187
Marking
LOAD
2
LINE
PE M4
400±10
300±10
4 × ø4,8
120±0,3
149
138±0,3
PE
L1’
L2’
L3’
L1
L2
L3
Litz wire
Litze
WireAderendhülse
end ferrule
174±0,3
2 2
Terminal
blocks 2,52,5
mm
Anschlussklemmen
mm
Thread M4
4 × Gewinde
M4
200±0,3
213
230 03/01
SSB1585-A
3-Line Filters
B84143-A*-R206
for Converters and Power Electronics
B84143-A25-R206
2 2
Terminal blocks 4 mm
Anschlussklemmen
4 mm
55
219
Marking
LOAD
2
LINE
PE M4
450±10
350±10
4 × ø5,8
156±0,3
185
174±0,3
PE
L 3’
L 2’
L 1’
L1
L2
L3
Litz wire
Litze
WireAderendhülse
end ferrule
204±0,3
Thread M5
4 ×× Gewinde
M5
232±0,4
245
231 03/01
SSB1586-I
3-Line Filters
B84143-A*-R206
for Converters and Power Electronics
Insertion loss (typical values at Z = 50 Ω)
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
B84143-A6-R206
B84143-A12-R206
SSB1581-C
120
dB
αe
αe
100
100
90
90
80
80
70
70
60
60
50
50
40
40
30
30
20
20
10
10
0
10 4
10 5
10 6
10 7
Hz 10 8
f
0
10 4
B84143-A25-R206
SSB1583-T
120
dB
αe
100
90
80
70
60
50
40
30
20
10
0
10 4
10 5
10 6
10 7
SSB1582-K
120
dB
Hz 10 8
f
232 03/01
10 5
10 6
10 7
Hz 10 8
f
Herausgegeben von EPCOS AG
Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND
 EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und
Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG
nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigenschaften
zugesichert. Bestellungen unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen
für Erzeugnisse und Leistungen der Elektroindustrie, soweit nichts anderes vereinbart wird.
Diese Broschüre ersetzt die vorige Ausgabe.
Fragen über Technik, Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere Vertriebsgesellschaften im Ausland.
Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten. Auskünfte
darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft einzuholen.
Published by EPCOS AG
Marketing Communications, P.O. Box 80 17 09, 81617 Munich, GERMANY
 EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be considered as guaranteed characteristics. Purchase orders are subject to the General Conditions for
the Supply of Products and Services of the Electrical and Electronics Industry recommended by the
ZVEI (German Electrical and Electronic Manufacturers’ Association), unless otherwise agreed.
This brochure replaces the previous edition.
For questions on technology, prices and delivery please contact the Sales Offices of EPCOS AG or
the international Representatives.
Due to technical requirements components may contain dangerous substances. For information on
the type in question please also contact one of our Sales Offices.
1