ETC 6CIF21B

Bussmann®
HRCI-CA Industrial Ceramic Body Fuse
CIF21B
Bolt-On Mounting
Dimensional Data
A
C
D
E
H
F
G
CATALOG SYMBOL: CIF21B
1 - 30 Amps
600 Volts AC; 250 Volts DC
INTERRUPTING RATING: 200,000A RMS SYMMETRICAL
CSA C22.2 NO. 106-M92
• Provides both overload and short-circuit protection to HRCI
requirements.
• Offset blades for bolt-on mounting.
• CIF21B fuse fits the Bussmann-Camaster Fuseholder.
Type
HRCI-CA
12-21-98
SB98107
Catalog
Symbol
CIF21B
Rev. A
Amps
1-30A
Dimensions in Inches and (mm)
Overall
Tags
A
E
F
Mounting
G
H
Body
C
D
2.15
(54.50)
.03
(0.81)
1.75
(44.50)
.19
(4.70)
1.44
(35.50)
.54
(13.80)
.44
(11.10)
Form No. HRCI-CA
Page 1 of 2
BIF Doc #4127
Bussmann®
HRCI-CA Industrial Ceramic Body Fuse
CIF21B
Bolt-On Mounting
100
10
30
25
20
15
10
6
1
3
AMPERE
RATING
10
1
.1
100
10
1
.1
0.1
AMPERE
RATING
10
15
20
25
30
100
TIME IN SECONDS
1,000
PEAK CURRENT (KA)
1,000
6
Time/Current-Curves (Cat. No. CIF21B)
3
Peak Let-Through Curves (Cat. No. CIF21B)
PROSPECTIVE CURRENT (SYM. RMS KA)
Energy Let-Through Curves (Cat. No. CIF21B)
10,000
1,000
100
100,000
10
1
.01
CURRENT IN AMPERES
10,000
AMPERE2 SECONDS (I2t)
Total I2t at 600V
Ref
3CIF21B
6CIF21B
10CIF21B
15CIF21B
20CIF21B
25CIF21B
30CIF21B
Total I2t at 460V
Pre-Arcing I2t
1,000
Power Dissipation @ Rated Amps
Watts
1.8
1.5
3.4
2.4
3.2
3.6
3.6
100
30
25
20
15
10
6
1
3
10
FUSE RATING (AMPERES)
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled.This bulletin is intended to