ESTAsym CPR Datasheet

ESTAsym CPR
www.vishay.com
Vishay ESTA
Unbalance Protection Relay
FEATURES
• Separately adjustable thresholds for alarm and trip
• Separately adjustable delay time for alarm and trip
• Compensation of the natural unbalance
• Adjustable transformer ratio (voltage / current)
• With low pass filter
• One free programmable output relay
APPLICATIONS
• Monitoring unbalance currents of capacitor banks
- Double-star connection
- Bridge connection
• Monitoring unbalance voltages of capacitor banks
QUICK REFERENCE DATA
Description
Type
Supply voltage
Unbalance protection relay for capacitor banks connected in double-star or bridge connection
Unbalance protection relay
40 VAC to 250 VAC, 50 Hz to 60 Hz / 40 VDC to 300 VDC
Measuring voltage
0.2 V to 20 V, burden 284 k
Measuring current
20 mA to 5 A
Relay outputs
Digital input
Interfaces
Temperature
Humidity
Overvoltage class standards
Standards
AC: max. 1250 VA
DC: 30 V / 5 A, 60 V / 1 A, 110 V / 0.5 A, 220 V / 0.3 A
Blocking alarm / trip via digital input
TTL, rear (optional: RS485, Modbus RTU)
Operation: -20 °C to +70 °C
Storage: -40 °C to +85 °C
0 % to 95 %, without moisture condensation
II, polution degree 3 (IEC 60664-1)
IEC 60664-1, IEC 61010-1, IEC 61326
Conformity and listing
Terminals
Casing front
Protection level
Weight
CE
Screw type, maximum 4 mm2
Instrument casing plastic (UL 94 V-0), rear: metal
IP50, IP54 by using a gasket; rear: IP20
0.65 kg
Note
• Complete mounting instructions / manual available at www.vishay.com/doc?13172
Revision: 12-Nov-14
Document Number: 13176
1
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
ESTAsym CPR
www.vishay.com
Vishay ESTA
The operation of high- and medium-voltage capacitors needs to be monitored constantly. Most such capacitors use insulating
oil for their dielectrics, and monitoring is required to avoid any combustion of this material in event of failure. This monitoring
can be done either by monitoring the unbalance current or unbalance voltage of capacitor groups.
However, this voltage/current may change in case of any failure of one capacitor, for instance caused by a flashover inside the
wound foils.
APPLICATIONS
MONITORING UNBALANCING CURRENT
Double-Star Connection
In a double-star connection, the star points of two capacitor
groups are connected together as shown in Fig. 1. In the
event of a failure, i.e., element breakdown or group
short-circuit, the star point of the respective branch is
shifted and causes a current flow between the star points.
The intensity of the current is determined by the capacitor
construction and the number of capacitors.
CPR
Fig. 1 - Double-star connection
Bridge Connection
In a bridge connection, as shown in Fig. 2, the capacitor
bank is built up with four bridge branches, with two
branches each constituting a series connection. The
medium potentials of the branches are connected by a
current transformer. The division of the bridge branches
preferably should be symmetrical. An unsymmetrical
structure would also be possible. However, with an
unsymmetrical structure, the pick-up values must be set to
the more sensitive branch.
CPR
Fig. 2 - Bridge connection
MONITORING UNBALANCE VOLTAGE
To monitor the capacitor bank via the voltage, the voltage of
the capacitors of the three phases is connected to three
two-pole insulated PTs, which are on the secondary side
connected in series. In Fig. 3, the ESTAsym CPR is
measuring the voltage at this open delta.
L1
L2
L3
CPR
20 mA - 5 A
0.2 V - 20 V
Fig. 3
Revision: 12-Nov-14
Document Number: 13176
2
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
ESTAsym CPR
www.vishay.com
Vishay ESTA
OPTIONAL FEATURES
Interface RS485, Modbus RTU
Programming via USB 2.0 interface
FUNCTION
The ESTAsym CPR is designed to monitor medium- and high-voltage capacitors. The ESTAsym CPR can be set from the menu
to monitor current or voltage. The device can monitor two threshold levels for alarm / trip. All thresholds / readings can be set
either as a specific current or voltage value or as a percentage of the maximum value. Once the alarm or trip level is reached,
the appropriate relay will operate, after the programmed delay time has elapsed. Both output relays can be programmed to be
held in the alarm / trip position until reset by the user. Alternatively they can be set to automatically reset if the fault condition
has cleared. A further output relay can be used to operate when the alarm / trip or both alarm and trip have operated. The
ESTAsym CPR can record details of the last five alarm and trip operations. An natural unbalance (out of balance or asymmetrical
value) can be programmed into the device if required. This natural unbalance is subtracted from the measured value and allows
a more exact setting of the thresholds.
Measured Value
- Natural Unbalance
= Value
Revision: 12-Nov-14
Comparator
Adjusted Threshold
Value > Limit
Alarm / Trip
Delay Time
Adjusted Delay Time
Alarm / Trip
for Alarm / Trip
Monitoring
Blocked via DI1
and DI2
Switch Output Relay
Output Relay 1
Trip
Output Relay 2
Alarm
Output Relay 3
Progr.
Document Number: 13176
3
For technical questions, contact: [email protected]
THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE. THE PRODUCTS DESCRIBED HEREIN AND THIS DOCUMENT
ARE SUBJECT TO SPECIFIC DISCLAIMERS, SET FORTH AT www.vishay.com/doc?91000
Legal Disclaimer Notice
www.vishay.com
Vishay
Disclaimer
ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE
RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.
Vishay Intertechnology, Inc., its affiliates, agents, and employees, and all persons acting on its or their behalf (collectively,
“Vishay”), disclaim any and all liability for any errors, inaccuracies or incompleteness contained in any datasheet or in any other
disclosure relating to any product.
Vishay makes no warranty, representation or guarantee regarding the suitability of the products for any particular purpose or
the continuing production of any product. To the maximum extent permitted by applicable law, Vishay disclaims (i) any and all
liability arising out of the application or use of any product, (ii) any and all liability, including without limitation special,
consequential or incidental damages, and (iii) any and all implied warranties, including warranties of fitness for particular
purpose, non-infringement and merchantability.
Statements regarding the suitability of products for certain types of applications are based on Vishay’s knowledge of typical
requirements that are often placed on Vishay products in generic applications. Such statements are not binding statements
about the suitability of products for a particular application. It is the customer’s responsibility to validate that a particular
product with the properties described in the product specification is suitable for use in a particular application. Parameters
provided in datasheets and/or specifications may vary in different applications and performance may vary over time. All
operating parameters, including typical parameters, must be validated for each customer application by the customer’s
technical experts. Product specifications do not expand or otherwise modify Vishay’s terms and conditions of purchase,
including but not limited to the warranty expressed therein.
Except as expressly indicated in writing, Vishay products are not designed for use in medical, life-saving, or life-sustaining
applications or for any other application in which the failure of the Vishay product could result in personal injury or death.
Customers using or selling Vishay products not expressly indicated for use in such applications do so at their own risk. Please
contact authorized Vishay personnel to obtain written terms and conditions regarding products designed for such applications.
No license, express or implied, by estoppel or otherwise, to any intellectual property rights is granted by this document or by
any conduct of Vishay. Product names and markings noted herein may be trademarks of their respective owners.
Material Category Policy
Vishay Intertechnology, Inc. hereby certifies that all its products that are identified as RoHS-Compliant fulfill the
definitions and restrictions defined under Directive 2011/65/EU of The European Parliament and of the Council
of June 8, 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment
(EEE) - recast, unless otherwise specified as non-compliant.
Please note that some Vishay documentation may still make reference to RoHS Directive 2002/95/EC. We confirm that
all the products identified as being compliant to Directive 2002/95/EC conform to Directive 2011/65/EU.
Vishay Intertechnology, Inc. hereby certifies that all its products that are identified as Halogen-Free follow Halogen-Free
requirements as per JEDEC JS709A standards. Please note that some Vishay documentation may still make reference
to the IEC 61249-2-21 definition. We confirm that all the products identified as being compliant to IEC 61249-2-21
conform to JEDEC JS709A standards.
Revision: 02-Oct-12
1
Document Number: 91000